HIOKI 3169-20/21 Clamp On Power Hitester User Guide
- June 13, 2024
- HIOKI
Table of Contents
QUICK START MANUAL
3169-20/21
CLAMP ON POWER
HiTESTER
Introduction
- The 3169-20/21 CLAMP ON POWER HiTESTER is supplied with a instruction manual in addition to this manual. Please be sure to read both manuals.
- This manual is a quick reference source with examples and information regarding the setting-up of and key operation for the 3169-20/21 CLAMP ON POWER HiTESTER for measurement purposes.
- For current input with this device, a clamp-on sensor (optional) is required. For details, refer to the instruction manual for the clamp-on sensor you are using.
Safety Notes
The following symbols in this manual indicate the relative importance of cautions and warnings.
Indicates that incorrect operation presents an extreme hazard that could
result in serious injury odeath to the user.
Indicates that incorrect operation presents a significant hazard that could
result in serious injury odeath to the user.
Indicates that incorrect operation presents a possibility of injury to the
user or damage to the product.
Advisory items related to performance or correct operation of the product.
Other Symbols
Indicates the prohibited action.
❖ Indicates the reference.
Indicates quick references for operation and remedies for troubleshooting.
- Indicates terminology explained at the bottom of the page.
Parts Names
❖4 “Connecting to Lines to be Measured” (page 35)
The reference pages referred to above are those in the instruction manual.
1.1 Instrument Labels and Functions
Front Panel
Front Panel Enhanced View
Top Panel
Voltage Input terminals
Connect the supplied 9438-03 VOLTAGE CORD. Current Input terminals
Connect an optional clamp-on sensor.
Left Panel
Right Panel
Rear Panel
1.2 Screen Names and Display Elements
1.2.1 Screen Configuration
The screens are divided into three basic types: measurement screens,
setting screens, and file screens. Each screen is selected using three panel
keys: MEASURE, SET UP, and FILE.
Measurement screen
1.2.2 Common Display
This section of the screen shows information common to all measurement screens
(except the zoom screen and the wiring diagram screen).
Common Display
Time | Displays the current time. |
---|---|
Range | Displays the voltage range and current range of the on-screen circuit. |
The VT(PT) ratio and CT ratio are shown under these ranges. The current range
and CT ratio of I4 are shown only when 3P4W4I is set as the wiring method.
Wiring| Displays the wiring method set on the setting screen.
No. of circuits| Displays the number of circuits to be measured as set on the
setting screen.
Synchronization method| Displays the synchronization method and frequency of
the line to be measured as set on the setting screen.
Interval| Displays the interval set on the setting screen.
1.2.3 On-Screen Indicators
| Goes on when the reactive-power-meter method is ON.
---|---
| Goes on when the displayed measurement is held.
| Goes on when the medium for saving data is set to PC card. Flashes when the
PC card is accessed.
| Goes on when the medium for saving data is set to internal memory. Flashes
when the internal memory is accessed.
| Goes on when the PC card or internal memory is full.
| Goes on when the device to be connected to the RS232C is set to PC.
| Goes on when the device to be connected to the RS232C is set to printer.
| Goes on when the PLL is unlocked; the synchronization method is
automatically switched over to the fixed clock.
| Goes on when the keys are locked.
| Goes on when the voltage or current dynamic range is exceeded.
| Displayed when the range is exceeded.
Power Measurement
2.1 Outline
This chapter explains setting and measurement procedures using the following
conditions.
Measure the power of a Three-phase 3-wire line for 7 days.
Measurement location:
A Tree-phase 3-wire 200 V line of a switchboard (50 Hz, 50 A load)
Setting:
Time-series measurement start time: 2002/06/20 08:00
Time-series measurement stop time: 2002/06/27 08:00
Data is automatically output to the PC card at 5-minute intervals.
Average value (voltage, current, and power) and integrated power are stored on
the PC card. The reactive power-meter method is not used.
Instrument and Accessories Required for Measurement 9438-03 VOLTAGE CORD
1 set (4 cords)(One each red, yellow, blue, and black cords.)
9661 CLAMP ON SENSOR x 2
Setting Screens under the Example Conditions
< MEASUREMENT>
WIRING : 3P3W2M
(Three-phase 3-wire, 2-power-meter method)
Number of circuits : X 1 (1 circuit)
SAMPLING : PLL
Measured frequency: 50 Hz VAR METHOD : OFF
AVERAGE TIMES : 1
VOLTAGE RANGE : 300 V
VT (PT) : 0001.00
CURRENT RANGE : 50 A
CT : 0001.00
SENSOR : 9661
< DATA OUTPUT>
MEAS. START : TIME
(2002/06/20 08:00) MEAS. STOP : TIME
(2002/06/27 08:00) INTERVAL TIME : 5 min
SAVE IN… : PC CARD
DATA FILE NAME : INTEG
< SAVE, PRINT ITEMS>
NORM. MEAS.: ON
HARMONIC : OFF
INTEG. & DEM.: ON
INST. : OFF
AVE. : ON
MAX. : OFF
MIN. : OFF
2.2 Measurement Procedure
Measurement Preparations (page 14)
- Connecting the Power Cord
- Connecting the Voltage Cords
- Connecting the Clamp-On Sensor
- Inserting a PC Card
- Turning the Power On
Connect to the Line to be Measured (page 18)
- Setting the wiring details
- Displaying the Wiring Diagram
- Connectting the voltage cords and clamp-on sensor to the line to be measured
- Checking the Wiring
Perform Measurement (page 26)
- Setting the measurement conditions
- Confirm range
- Start measurement
- Stop measurement
Shutdown Procedure
- Disconnect the voltage cords and clamp-on sensor from the measured line.
- Turn off the power to the 3169-20/ 21.
- Disconnect the power cord from the AC outlet.
- Remove the PC card from the 316920/21 and analyze the saveddata on PC.
2.3 Measurement Preparations
-
Connecting the Power Cord
• Before turning the product on, make sure the source voltage matches that indicated on the product’s power connector. Connection to an improper supply voltage may damage the product and present an electrical hazard.
• To avoid electric shock and ensure safe operation, connect the power cable to a grounded (3-contact) outlet.1. Connect the power cord to the AC power inlet.
2. Plug the power cord into the AC mains outlet. -
Connecting the Voltage Cords
Connect the voltage cords to the product first, and then to the active lines to be measured. Observe the following to avoid electric shock and short circuits.
• Voltage cord should only be connected to the secondary side of a breaker, so the breaker can prevent an accident if a short circuit occurs. Connections should never be made to the primary side of a breaker, because unrestricted currentflow could cause a serious accident if a short circuitoccurs.
• Do not allow Do not allow the voltage cable clips to touch two wires at the same time. Never touch the edge of themetal clips. Never touch the edge of the metal clips.
• Voltage input terminals U1, U2, and U3 are common to the N terminal and are not insulated. To avoid the risk of electric shock, do not touch the terminals.
• For safety reasons, when taking measurements, only use the 9438-03 VOLTAGE CORD provided with the product.
• The supplied voltage cords consist of one each red, yellow, blue and black cords. Connect only the cords actually needed for measurement. Cords not being used for measurement should be disconnected.Voltage input terminals
Connect the 9438-03 VOLTAGE
CORD to the voltage input terminals of the 3169-20/21.Insert plugs all the way in. -
Connecting the Clamp-On Sensor
Connect the clamp-on sensors to the product first, and then to the active lines to be measured. Observe the following to avoid electric shock and short circuits.
• Clamp sensor should only be connected to the secondary side of a breaker, so the breaker can prevent an accident if a short circuit occurs. Connections should never be made to the primary side of a breaker, because unrestricted current flow could cause a serious accident if a short circuit occurs.
• When the clamp sensor is opened, do not allow the metal part of the clamp to touch any exposed metal, or to short between two lines, and do not use over bare conductors.
• To prevent damage to the product and sensor, never connect or disconnect a sensor while thepower is on.
• The current input terminals of the 3169-20/21 are not insulated. To avoid the risk of electric shock, only use the specified optional clamp-on sensor.Current input terminas
Connect the 9661 CLAMP ON SENSOR to the current input terminals of the 3169-20/21.
3169-20/21 Current input terminal connector guide pins Align the slots in the BNC plug with the guide pins on the connector at the instrument side, then push and turn the plug clockwise. (to unplug the connector, push the plug and turn it counterclockwise before pulling it apart.)
When disconnecting the BNC connector, be sure to release the lock before pulling the connectors apart. Forcibly pulling the connector without releasing the lock, or pulling on the cable, can damage the connector. -
Inserting a PC Card
Use only PC Cards sold by HIOKI. Compatibility and performance are not guaranteed for PC cards made by other manufacturers. You may be unable to read from or save data to such cards.
• The PC card or the instrument can be damaged if the card is inserted forcefully in the wrong direction.
• Never eject a PC card while it is being accessed by the instrument. Data on the PC card may be lost.Open the cover and insert the PC card with the arrow facing up and in the direction of the PC card slot, as far as it will go.
❖ Instruction manual 7.2 “Using a PC Card” (page 117) -
Turning the Power On
Before turning the product on, make sure the source voltage matches that indicated on the product’s power connector. Connection to an improper supply voltage may damage the product and present an electrical hazard. Turn the POWER switch ON ( 1 ).
As soon as the power is turned on, the self-test screen appears. Upon completion of the self test, display switches to the measurement screen.
Screen after the ower is turned on (Self-test screen)
2.4 Connect to the Line to be Measured
- Setting the wiring details
Set the 3169-20/21 to measure a three-phase 3-wire 200 V line (50 Hz, 50 A load) using the 9661 CLAMP ON SENSOR (500 A rated).
(1) Set the wiring to “3P3W2M.”
SET UP
NEXT SCR
Press the SET UP key to display the setting screen.
Press the F5 (NEXT SCR) key to display the measurement setting screen. Move the cursor to “WIRING.”
change Press the F1 (change) key to display the selection window. Select “3P3W2M”(Three-phase 3-wire, 2-power-meter method) by using the cursor key.
select Press the F1 (select) key.
(2) Make sure the number of circuits to be measured is set to “X1 (1 circuit).”When multiple circuits of the same voltage system (the same transformer) are to be measured, use a preset between X2 (2 circuits) and X4 (4 circuits).
1P2W | X1 (1 circuit), X2 (2 circuits), X3 (3 circuits), X4 (4 circuits) |
---|---|
1P3W | X1 (1 circuit), X2 (2 circuits) |
3P3W2M | X1 (1 circuit), X2 (2 circuits) |
3P3W3M,3P4W, 3P4W4I | X1 (1 circuit) only |
(3) Make sure the synchronization method (sampling) is set to “PLL.”(4)
Make sure the frequency of the line to be measured is set to “50 Hz.”(5)
Make sure the reactive power-meter method is “OFF.”(5)
Make sure the displayed data averaging times is set to “1.”(6) Set the voltage range to “300 V.”Move the cursor to “VOLTAGE RANGE.” Select “300 V” using the
function keys.
(7) Make sure the VT (PT) ratio is set to “1.”Set the VT (PT) ratio, if necessary.
(Example)
When the primary voltage is 6.6 kV and the secondary voltage is 110 V, the VT
ratio is 60 (6600 V/110 V). In this case, as the rated measurement voltage is
110 V, set the voltage range to 150 V.
(8) Make sure “9661” is selected as the clamp-on sensor to be used.(9) Set the current range to “50 A.”Move the cursor to “CURRENT RANGE.” Select “50A” using the
function keys.
Selectable current ranges vary according to the clamp-on sensor used.
Clamp-On Sensor and Current Range:
9660, 9695-03 | 5 A, 10 A, 50 A, 100 A |
---|---|
9661 | 5 A, 10 A, 50 A, 100 A, 500 A |
9667-5 kA (5000 A range) | 5 kA |
9667-500 A (500 A range) | 500 A |
9669 | 100 A, 200 A, 1 kA |
9694 | 0.5 A, 1 A, 5 A |
9695-02 | 0.5 A, 1 A, 5 A, 10 A, 50 A |
(10) Make sure the CT ratio is set to “1.”Set
the CT ratio, if necessary.
(Example)
When the primary current is 100 A and the secondary current is 5 A, the CT
ratio is 20 (100 A/5 A). In this case, as the rated measurement current is 5
A, set the current range to 5 A.
-
Displaying the Wiring Diagram
MEASURE
Press the MEASURE key to display the measurement screen.
SCREEN Press the F1 (SCREEN) key to display the selection window. Move the cursor to “ WIRING DIAGRAM.”
select Press the F1 (select) key; the wiring diagram will appear. -
Connectting the voltage cords and clamp-on sensor to the line to be measured
Connect the 9438-03 voltage cords and the 9661 clamp-on sensor to the line to be measured, while referring to the wiring diagram.
We recommend that the color of a voltage cord be matched to that of the attached input-cord label used for the same channel. -
Checking the Wiring
MEASURE
Press the MEASURE key to display the measurement screen.
SCREEN Press the F1 (SCREEN) key to display the selection window. Move the cursor to “ WIRING CHECK.”
select Press the F1 (select) key.
The connection status is shown by the voltage, current vectors, and the connection check result.
If the wiring check result is not “OK,” check the wiring.
The wiring check function may indicate improper connection (“NG”) even when
the actual wiring is correct, or vice versa.
Check the vectors and measurement data as well.
The wiring check result is NG.
The voltage input is NG.| •Do the voltage clips grip the wires properly?
•Is the voltage cord properly inserted into the voltage input terminal of the
3169-20/21?
---|---
The current input is NG.| •Is the clamp-on sensor securely inserted into the
current input terminals?
•Is the set current range too large for the input level?
The voltage phase is NG.| •Are the voltage cords connected to the correct
terminals?
The current phase is NG.| •Does the arrow of the clamp-on sensor point to the
load side?
•Is the clamp-on sensor connected to the correct terminals?
The phase difference (I-U) is NG.| •Are the voltage cords and clamp-on sensor
properly connected?
•Does the arrow of the clamp-on sensor point to the load side?
•Is the power factor of the line to be measured too low, such as 0.5 or less?
The voltage balance is NG.| •Does the connection method of the line to be
measured differ from that set?
•Do the voltage clips grip the wires properly?
•Is the voltage cord properly inserted into the voltage input terminal?
2.5 Perform Measurement
- Setting the measurement conditionsDATA OUTPUT
• Measurement start: 2002/06/20 08:00
• Measurement stop: 2002/06/27 08:00
• Data is automatically output to the PC card at 5-minute intervals.
• Data file name: INTEG SAVE, PRINT ITEMS
Saves the average value (voltage, Current, and Power) and integrated power on a PC card
(1) Set the measurement start time to “2002/06/20 08:00.”
Before setting the measurement start time, make sure the current date and time displayed on the screen are correct.
❖ Instruction manual 5.5.7 “Setting the Clock” (page 92)
SET UP
Press the SET UP key to display the setting screen.
NEXT SCR Press the F5 ( NEXT SCR ) key to display the data-output setting screen. Move the cursor to “MEAS. START.” TIME Press the F2 (TIME) key.MANUAL| Measurement starts when the START/STOP key is pressed (default setting).
---|---
TIME| Measurement starts at the time set by users.
JUST| Measurement will begin as soon as the internal clock reaches a time that is evenly divisible by the set interval.
❖Instruction manual 5.3.1 “Setting the Time-Series Measurement Start Method”
(page 69)
Move the cursor to the measurement start time. Set the measurement start time
to “2002/06/20 08:00” using the function keys. (Cursor : Moves left to next
digit ; Cursor : Moves right to next digit)
– | Decrements the number. |
---|---|
+ | Increments the number. |
If F3 (AUTO) key is pressed when the cursor is at the measurement start time,
the start time will be set to a date and time close to the current time.
(2) Set the measurement stop time to “2002/06/27 08:00.” TIME Press the F2 (TIME) key.
MANUAL| Measurement stops when the START/STOP key is pressed (default
setting).
---|---
TIME| Measurement stops at the time set by users.
TIMER| Measurement stops when the duration set by the users has elapsed. 1
second to 8784 hours
Move the cursor to the measurement stop time and set it to “2002/06/27 08:00.”
(3) Set the interval time to “5 minutes.”
Move the cursor to “ INTERVAL TIME.”
change Press the F1 (change) key to display the selection
window. Select “5 min” using the cursor key.
select Press the F1 (select) key.
Storable Data According to Interval Setting
Interval setting| Normal measurement data| integrated power/
demand measurement data| Harmonic measurement data
---|---|---|---
| | |
1/2/5/10/15/30/60 minutes| Yes| Yes| Yes
1/2/5/10/15/30 seconds| Yes| Yes| No
All wave/100/200/ 500 ms| Yes (Instantaneous values only) Binary data| No| No
(4) Make sure the medium for saving data to is set to “PC card.”
(5) Set the data output file name to “INTEG.”
Move the cursor to “ DATA FILE NAME.”
change Press the F1 (change) key to display the selection
window.Enter “INTEG” using the cursor and F1 (input) key.
To make a correction, press the F2 (BS) key. Pressing the F2 key once will
delete one letter. Press the F3 (enter) key.
• The file is saved as “INTEG.csv” on the PC card.
• If a filename is not specified or a file with the same name exists on the PC
card, the file will automatically be named “69MEASXX” (XX: 00 to 99).
(6) Set the data output items
NEXT SCR Press the F5 (NEXT SCR) key to display the save/print items
setting screen. Move the cursor to “ NORM. MEAS..”
Press the F1 (ON) key.
ON Turn ON “AVE.” and “ INTEG. & DEM.” in a similar way.
All other items shall be turned OFF.
• Check the storable time. This indicates the length of time for which the
currently installed PC card stores data. If the storable time is shorter than
the measurement time (7 days), delete unnecessary files from the PC card or
replace it with a larger-capacity PC card.
• If the number of output is greater of equal to 256, all of the data may not
be read into common spreadsheet software.
• For details on settings for harmonics measurement-data output, see 5.4.4
“Setting Harmonic Measurement-data Output Items”(page 82) of the instruction
manual.
-
Confirm range Press the MEASURE key to display the measurement screen.
Press the U RANGE key or I RANGE key to select an appropriate range.
If you press the I RANGE Key, it selects a current range with a sufficient margin, in consideration of fluctuations in the load current of the line to be measured. -
Start measurement
Press the MEASURE key to display the measurement screen.
Press the START/STOP key to place the 3169-20/21 in standby mode (LED blinking)Switch Over to Another Screen.
SCREEN Press the F1 (SCREEN) key to display the selection window. Select a screen to be viewed using the cursor key.
select Press the F1 (select) key. -
Stop measurement
The 3169-20/21 will automatically stop measurement at the stop time. The measurement data “INTEG.csv” has been saved on the PC card.
Interrupt Measurement.
Press the START/STOP key. The message “Do you want to stop the time-series measurement?” is displayed for you to confirm. yes Press the F1 (yes) key.
All measurement data before the interruption is saved on the PC card if the
measurement is interrupted.
Shutdown Procedure
- Disconnect the voltage cords and clamp-on sensor from the measured line.
- Turn off the power to the 3169-20/21.
- Disconnect the power cord from the AC outlet.
- Remove the PC card from the 3169-20/21 and analyze the saved data on PC.
HIOKI 3169-20/21 CLAMP ON POWER HiTESTER
Quick Start Manual
Publication date: October 2003 Revised edition 2 Edited and published by HIOKI
E.E. CORPORATION
Technical Support Section
All inquiries to International Sales and Marketing Department 81 Koizumi,
Ueda, Nagano, 386-1192, Japan
TEL: +81-268-28-0562 / FAX: +81-268-28-0568
E-mail: os-com@hioki.co.jp
URL http://www.hioki.co.jp/
Printed in Japan 3169A983-02
- All reasonable care has been taken in the production of this manual, but if you find any points which are unclear or in error, please contact your supplier or the International Sales and Marketing Department at HIOKI headquarters.
- In the interests of product development, the contents of this manual are subject to revision without prior notice.
- Unauthorized reproduction or copying of this manual is prohibited.
HEAD OFFICE
81 Koizumi, Ueda, Nagano 386-1192, Japan
TEL +81-268-28-0562 / FAX +81-268-28-0568
E-mail:os-com@hioki.co.jp / URL
http://www.hioki.co.jp/
HIOKI USA CORPORATION
6 Corporate Drive, Cranbury, NJ 08512, USA
TEL +1-609-409-9109 / FAX
+1-609-409-9108
3169A983-02 03-10H
Printed on recycled paper
https://manual-hub.com/
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>