DESCRIPTION
The KMC Controls BAC-5051AE is a multi-port BACnet router. It is powerful
enough for heavy network traffic and small enough to use as a control
technician’s service tool.
Routing Install the BAC-5051AE for BACnet IP, Ethernet, and MS/TP
routing. IP routing is fully compliant with BACnet Standard 134-2012, Annex J.
Browser Configuration Configure the BAC-5051AE using only an
Internet browser. There is no special software to learn or load.
Flexible Mounting Two mounting choices for permanent installations–DIN
rail or surface mount.
Diagnostics Embedded metrics include: total number of devices, frame
counts, frames in error, data frames, duplicate MAC addresses, token passing,
and poll-for-master count.
MS/TP Diagnostics Capture Troubleshoot MS/TP issues by capturing, saving,
and analyzing network traffic. Data is saved in industry standard .pcap files.
Automatically Learns Networks Detects and configures routing for the
actual discovered networks.
Enable and Disable Routing Use the router as a diagnostic tool to monitor
traffic without routing traffic.
VAV Airflow Balancing Use with an Internet browser as an airflow
balancing tool for BAC-8000 and BAC-9000 series VAV controllers.
AFMS Configuration Use the router to set up an Airflow Measurement System
(AFMS).
Zone Configuration Use the router to set up a BAC-120063CWZEC zoning Flexstat.
SPECIFICATIONS
Configuration Tools
Normal configuration from internally served browser pages.
Requires HTML5-compliant versions of Microsoft Internet Explorer, Chrome, or
Firefox.
Routing Protocols
- One MS/TP network
- One BACnet Ethernet
- Two IP ports that can be set up for any of the following protocols:
- Normal BACnet IP network routing
- BACnet broadcast management device with network and port address translation
- Foreign device registration with BACnet broadcast management devices (BBMD)
- PAD (packet assembling/disassembling) routing
MODEL
DESCRIPTION | MODEL |
---|---|
BACnet router | BAC-5051AE |
Dimensions
Hardware Features
Processor and Memory
Processor | 32-bit ARM® Cortex-M7 |
---|---|
Memory | Configuration parameters and diagnostics are stored in nonvolatile |
memory; auto restart on power failure
Indicators
- Power
- MS/TP communication
- Ethernet status
Installation
Power
AC supply voltage| 24 volts AC (–15%, +20%), 50/60 Hz, Class 2 only; non-
supervised All circuits, including supply voltage, are power limited circuits.
---|---
DC supply voltage| 24 volts DC (–15%, +20%) 5 volts DC through USB connection
for temporary service connection
Required power| 8 VA
Enclosure and Mounting
Weight | 5.4 ounces (154 grams) |
---|---|
Case material | Green and black flame retardant plastic |
Mounting | Surface mount or 35 × 7.5 mm DIN rail |
Environmental Limits
Operating | 32 to 120° F (0 to 49° C) |
---|---|
Shipping | –40 to 160° F (–40 to 71° C) |
Humidity | 0 to 95% relative humidity, non-condensing |
Network connections
BACnet Ethernet and IP
Two 10/100BaseT, RJ-45 connectors
BACnet MS/TP
- One MS/TP port, supports speeds from 9,600 to 115,200 baud
- Removable three-screw terminal block, 12–22 AWG wire
- Switched end-of-line termination
USB
USB-C connection for power and communication to use as a service tool.
Timekeeping
The router is a BACnet time master device that can maintain time with or
without an SNTP server. Time messages can be broadcast daily, weekly, or
monthly to all or selected networks. Time messages are formatted as UTC,
local, or both.
Agency and Regulatory Approvals
BTL | Pending |
---|---|
UL | UL 916 Energy Management |
Equipment
RoHS| RoHS compliant
CE| Pending
FCC| FCC Class A, Part 15, Subpart B and complies with Canadian ICES-003 Class
A*
*This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
ACCESSORIES
KMD-5567 | MS/TP network surge suppressor |
---|---|
XEE-6111-050 | 50 VA, single-hub transformer |
XEE-6112-050 | 50 VA, dual-hub transformer |
HPO-5551 | Conquest router tech cable kit |
Includes USB, Ethernet, and
MS/TP to NetSensor cables
HSO-9001| Ethernet patch cable, 50 feet
HSO-9011| Ethernet patch cable, 50 feet, plenum rated
SUPPORT
Additional resources for installation, configuration, application, operation,
programming, upgrading and much more are available on the web at
www.kmccontrols.com. To see all available files,
log-in to the KMC Partners site.
© 2023 KMC Controls, Inc.
Specifications and design subject to change without notice
922-035-03C
KMC Controls, 19476 Industrial Drive, New Paris, IN 46553 /
877-444-5622 / Fax:
574-831-5252 /
www.kmccontrols.com
References
- KMC Controls | Building Automation and Control Solutions
- Browse all of our KMC products today and find the right fit for you!
- Transformer; 120/24 50VA DUAL HUB | KMC Controls
- KMC Controls | Building Automation and Control Solutions
- FlexStat: Zoning Equipment Controller, White | KMC Controls
- Airflow Measurement System | KMC Controls
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>