INTARCON MCC-ND-1 017 Waterloop Evaporator with Built In Compressor User Manual
- June 13, 2024
- INTARCON
Table of Contents
Evaporator with built-in compressor User Manual
Compact unit condensed by water.
Minimal R-290 refrigerant charge.
Easy and safe installation with connection to the condensation water circuit.
Waterloop evaporator units with compressor are compact units for
installation inside small cold rooms, designed with natural refrigerant R-290
and waterloop condensed.
Features
230V 50Hz or 400V 3N 50Hz power supply. Available in 60 Hz. Others voltages by
request.
R-290 refrigerant charge low than 0.25 kg.
Bodywork in aluminium sheet and structure in galvanised steel lacquered in
polyester paint.
Alternative hermetic or scroll compressor integrated in thermally insulated
compartment, with crankcase heater.
Refrigeration circuit in annealed copper tube, with high pressure switch,
filter drier and load valve.
Evaporation coil in copper pipes and aluminium fins, thermostatic expansion
valve and hot gas defrost.
Axial motor fans.
Stainless steel brazed plates heat exchanger.
Threaded hydraulic connections.
Control panel in white lacquered sheet metal cabinet, with MCB protection and
multifunction electronic control (optional).
Installation
Installation of a closed loop water evaporator unit with an air cooler and
general electrical panel: Compact R-290 system
The waterloop evaporator units are hermetically sealed compact systems with a
minimum charge of R-290, exempt from the application EN 378.
They have a minimum R-290 refrigerant charge lower than the practical limit of
the refrigerated volume.
Electrical board (optional)
Electrical power and control board for outside installation.
MCB protection of compressor and manoeuvre.
Electronic control with temperature control and recording of maximum and
minimum temperatures.
Jet Cool function.
Energy saving function.
Optional air condenser management with water loop temperature control and
frost protection.
230V 50Hz / 400V 3N 50Hz | Positive temperature | Hermetic compressor – Scroll
compressor | R-290230V 50Hz / 400V 3N 50Hz | Negative temperature | Hermetic
compressor – Scroll compressor | R-290
Options
Electrical board for one unit.
Electrical board for two units in the same cold room.
Water solenoid valve for multi-equipment waterloop installation.
Dimensions
(1)Nominal performances refer to operation with cold room
temperatures of 0 ºC (PT) and -20 ºC (NT) and water inlet condensation
temperature of 40 ºC. Estimated cold room volume according to conditions of
the calculation bases (page 12).
(2)Condenser pressure drop in the water circuit.
(3)A3 refrigerant charge less than 0.5 kg, units exempt from, Regulation (EU)
No 517/2014.
(4)Recommended air cooler model to combine with the evaporator unit.
Electrical interconnections
For the electrical interconnection from the electrical panel to the unit and
to the air condenser (optional), the following interconnection cables must be
provided:
Cabinet – Evaporator | Connection |
---|---|
Compressor for single-phase units (except MCC-ND-1 034)* | 3 x 1.5 mm2 + T |
Compressor for three-phase units and MCC-ND-1 034 | 3 x 2.5 mm2 + T |
Manoeuvre | 7 x 1 mm2 |
Probes | 5 x 1 mm2 |
Cabinet – Dry-cooler | Connection |
Pump (1 +1 system) | 2 x 1.5 mm2 + T |
Fan (1 +1 system) | 3 x 1 mm2 |
Probes (1 + 1 system) | 3 x 1 mm2 |
Pumping permit (multi system) | 2 x 1 mm2 |