SYSTEM SENSOR P2RL-SP Indoor SelectableOutput Horns Strobes and Horn Strobes for Wall Applications Instruction Manual

June 13, 2024
SYSTEM SENSOR

SYSTEM-SENSOR-LOGO

SYSTEM SENSOR P2RL-SP Indoor SelectableOutput Horns Strobes and Horn

Strobes for Wall Applications

SYSTEM-SENSOR-P2RL-SP-Indoor-Selectable-utput-Horns-Strobes-and-Horn-
Strobes-for-Wall-Applications-PRODUCT

Product Information

The System Sensor L-Series is a line of indoor selectable output horns, strobes, and horn strobes designed for wall applications. These audible visible notification products are packed with features that make installation quick and easy, while also providing a modern aesthetic. The L-Series offers versatile options to meet various application requirements, including different housing colors, device sizes, and printed designs. With a lower current draw and a range of features, the L-Series is a reliable choice for fire protective service.

Features

  • Plug-in designs for fast and foolproof installations
  • Minimal intrusion into the back box
  • Universal mounting plate with an onboard shorting spring for testing wiring continuity
  • Field-selectable candela settings for adaptable application requirements
  • Automatic selection of 12- or 24-volt operation
  • Rotary switch for horn tones with two volume selections

Specifications

Strobe:
The strobe is a System Sensor L-Series Model ___ listed to UL 1971 and approved for fire protective service. It complies with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light consists of a xenon flash tube and associated lens/reflector system.

Physical/Electrical Specifications:

  • Standard Operating Temperature: 10 to 93% non-condensing
  • Strobe Flash Rate: 1 flash per second
  • Nominal Voltage: Regulated 12 DC or regulated 24 DC/FWR
  • Operating Voltage Range: 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
  • Input Terminal Wire Gauge: 12 to 18 AWG
  • Wall-Mount Dimensions (including lens): 5.26 L x 3.46 W x 1.91 D (133 mm L x 88 mm W x 49 mm D)
  • Compact Wall-Mount Dimensions (including lens): 5.25 L x 3.45 W x 1.25 D (133mm L x 88mm W x 32mm D)

Note: Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source used on some power supply and panel outputs. Strobe products will operate at 12 V nominal only for 15cd and 30 cd.

UL Current Draw Data:

Candela DC FWR
15 88 mA RMS 43 mA RMS
30 143 mA RMS 60 mA RMS
75 N/A 63 mA RMS
95 N/A 83 mA RMS
110 N/A 107 mA RMS
135 N/A 136 mA RMS
185 N/A 121 mA RMS
DC N/A 155 mA RMS
FWR N/A 148 mA RMS
43 N/A 179 mA RMS
60 N/A 172 mA RMS
63 N/A 209 mA RMS
83 N/A 222 mA RMS

Product Usage Instructions

Installation:

  1. Select the appropriate System Sensor L-Series audible visible notification product based on your application requirements.
  2. Ensure the device is compatible with your power supply or panel outputs.
  3. Choose the desired candela setting and voltage operation (12 V or 24 V) using the field-selectable options.
  4. Mount the device on the wall using the universal mounting plate and secure it in place.
  5. Connect the device to the power supply or panel using 12 to 18 AWG wire.

Note: Before connecting the device, test wiring continuity using the onboard shorting spring on the universal mounting plate.

Operation:

  1. Ensure the power supply or panel is providing the correct voltage within the operating voltage range.
  2. Activate the device to test the selected horn tone and volume settings.
  3. Observe the strobe light flashing at a rate of 1 flash per second.

Please refer to the user manual for additional information and troubleshooting guidelines.

Indoor Selectable Output Horns, Strobes, and Horn Strobes for Wall Applications

System Sensor L-Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with a lower current draw and modern aesthetics.

SYSTEM-SENSOR-P2RL-SP-Indoor-Selectable-utput-Horns-Strobes-and-Horn-
Strobes-for-Wall-Applications-FIG-1

Features

  • Updated Modern Aesthetics
  • Small profile devices for Horns and Horn Strobes
  • Plug-in design with minimal intrusion into the back box
  • Tamper-resistant construction
  • Automatic selection of 12- or 24-volt operation at 15 and 30-candela
  • Field-selectable candela settings on wall units: 15, 30, 75, 95, 110, 135, and 185
  • Horn rated at 88+ dBA at 16 volts
  • Rotary switch for horn tone and two volume selections
  • Mounting plate for all standard and all compact wall units
  • Mounting plate shorting spring checks wiring continuity before device installation
  • Electrically Compatible with legacy SpectrAlert and SpectAlert Advance devices
  • Compatible with MDL3 sync module
  • Listed for wall mounting only

Agency Listings

SYSTEM-SENSOR-P2RL-SP-Indoor-Selectable-utput-Horns-Strobes-and-Horn-
Strobes-for-Wall-Applications-FIG-2

The System Sensor L-Series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry with lower current draws and modern aesthetics. With white and red plastic housings, standard and compact devices, and plain, FIRE, and FUEGO-printed devices, System Sensor L-Series can meet virtually any application requirement.

The L-Series line of wall-mount horns, strobes, and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults.

To further simplify installation and protect devices from construction damage, the L-Series utilizes a universal mounting plate for all models with an onboard shorting spring, so installers can test wiring continuity before the device is installed.

Installers can also easily adapt devices to suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections.

L-Series Specifications

Architect/Engineer Specifications

General
L-Series standard horns, strobes, and horn strobes shall mount to a standard 2 x 4 x 1 7/8-inch back box, 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-gang back box. L-Series compact products shall mount to a single- gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, and 185.

Strobe
The strobe shall be a System Sensor L-Series Model ___ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.

Horn Strobe Combination
The horn strobe shall be a System Sensor L-Series Model ___ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three-pattern and a non-temporal (continuous) pattern. These options are set by a multiple-position switch. The horn-on-horn strobe models shall operate on a coded or non-coded power supply.

Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 411⁄16 × 411⁄16 × 21⁄8-inch back box. The module shall also control two Style Y (Class B) circuits or one Style Z (Class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.

Physical/Electrical Specifications

  • Standard Operating Temperature 32°F to 120°F (0°C to 49°C)
  • Humidity Range 10 to 93% non-condensing
  • Strobe Flash Rate 1 flash per second
  • Nominal Voltage Regulated 12 DC or regulated 24 DC/FWR1,2
  • Operating Voltage Range 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
  • Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)
  • Input Terminal Wire Gauge 12 to 18 AWG
  • Wall-Mount Dimensions (including lens) 5.6˝ L × 4.7˝ W × 1.91˝ D (143 mm L × 119 mm W × 49 mm D)
  • Compact Wall-Mount Dimensions (including lens) 5.26” L x 3.46” W x 1.91” D (133 mm L x 88 mm W x 49 mm D)
  • Horn Dimensions 5.6˝ L × 4.7˝ W × 1.25˝ D (143 mm L × 119 mm W × 32 mm D)
  • Compact Horn Dimensions 5.25” L x 3.45” W x 1.25” D (133mm L x 88mm W x 32mm D)
  1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.
  2. Strobe products will operate at 12 V nominal only for 15 cd and 30 cd.

UL Current Draw Data

UL Max. Strobe Current Draw (mA RMS)
UL Max. Horn Current Draw (mA RMS)

8–17.5 Volts 16–33 Volts 8–17.5 Volts 16–33 Volts
Candela DC DC FOR
DC DC FOR
Candela 15 88 43
Range 30 143 63
75 N/A 107 136
95 N/A 121 155
110 N/A 148 179
135 N/A 172 209
185 N/A 222 257

UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Candela Range (15–115 cd)

| 8-17.5 Volts| | 16-33 Volts|
---|---|---|---|---
DC Input| 15cd| 30cd| 15cd| 30cd| 75cd| 95cd| 110cd| 135cd| 185cd
Temporal High| 98| 158| 54| 74| 121| 142| 162| 196| 245
Temporal Low| 93| 154| 44| 65| 111| 133| 157| 184| 235
Non-Temporal High| 106| 166| 73| 94| 139| 160| 182| 211| 262
Non-Temporal Low| 93| 156| 51| 71| 119| 139| 162| 190| 239
3.1K Temporal High| 93| 156| 53| 73| 119| 140| 164| 190| 242
3.1K Temporal Low| 91| 154| 45| 66| 112| 133| 160| 185| 235
3.1K Non-Temporal High| 99| 162| 69| 90| 135| 157| 175| 208| 261
3.1K Non-Temporal Low| 93| 156| 52| 72| 119| 138| 162| 192| 242
| 16-33 Volts| | | | | | | |
FWR Input| 15cd| 30cd| 75cd| 95cd| 110cd| 135cd| 185cd| |
Temporal High| 83| 107| 156| 177| 198| 234| 287| |
Temporal Low| 68| 91| 145| 165| 185| 223| 271| |
Non-Temporal High| 111| 135| 185| 207| 230| 264| 316| |
Non-Temporal Low| 79| 104| 157| 175| 197| 235| 283| |
3.1K Temporal High| 81| 105| 155| 177| 196| 234| 284| |
3.1K Temporal Low| 68| 90| 145| 166| 186| 222| 276| |
3.1K Non-Temporal High| 104| 131| 177| 204| 230| 264| 326| |
3.1K Non-Temporal Low| 77| 102| 156| 177| 199| 234| 291| |

Horn Tones and Sound Output Data

Horn and Horn Strobe Output (dBA)


Switch

| | | 8–17.5

Volts

| 16–33

Volts

|
---|---|---|---|---|---
Position| Sound Pattern| dB| DC| DC| FOR
1| Temporal| High| 84| 89| 89
2| Temporal| Low| 75| 83| 83
3| Non-Temporal| High| 85| 90| 90
4| Non-Temporal| Low| 76| 84| 84
5| 3.1 KHz Temporal| High| 83| 88| 88
6| 3.1 KHz Temporal| Low| 76| 82| 82
7| 3.1 KHz Non-Temporal| High| 84| 89| 89
8| 3.1 KHz Non-Temporal| Low| 77| 83| 83
9| Coded| High| 85| 90| 90
10
| 3.1 KHz Coded| High| 84| 89| 89

Settings 9 and 10 are not available on the 2-wire horn strobes

L-Series Dimensions

SYSTEM-SENSOR-P2RL-SP-Indoor-Selectable-utput-Horns-Strobes-and-Horn-
Strobes-for-Wall-Applications-FIG-3

L-Series Ordering Information

Wall Horn Strobes

  • P2RL: 2-Wire, Horn Strobe, Red
  • P2WL : 2-Wire, Horn Strobe, White
  • P2GRL : 2-Wire, Compact Horn Strobe, Red
  • P2GWL : 2-Wire, Compact Horn Strobe, White
  • P2RL-P: 2-Wire, Horn Strobe, Red, Plain
  • P2WLP :2-Wire, Horn Strobe, White, Plain
  • P2RLSP : 2-Wire, Horn Strobe, Red, FUEGO
  • P2WLSP : 2-Wire, Horn Strobe, White, FUEGO

Wall Strobes

  • SRL : Strobe, Red
  • SWL : Strobe, White
  • SGRL: Compact Strobe, Red
  • SGWL : Compact Strobe, White
  • SRL-P: Strobe, Red, Plain
  • SWL-P : Strobe, White, Plain
  • SRL-SP : Strobe, Red, FUEGO
  • SWL-CLR-ALERT : Strobe, White, ALERT

Horns

  • HRL : Horn, Red
  • HWL : Horn, White
  • HGRL : Compact Horn, Red
  • HGWL : Compact Horn, White

Accessories

  • TR-2: Universal Wall Trim Ring Red
  • TR-2W : Universal Wall Trim Ring White
  • SBBRL : Wall Surface Mount Back Box, Red
  • SBBWL : Wall Surface Mount Back Box, White
  • SBBGRL : Compact Wall Surface Mount Back Box, Red
  • SBBGWL : Compact Wall Surface Mount Back Box, White

Notes:

  1. All -P models have plain housing (no “FIRE” marking on the cover)
  2. All -SP models have a “FUEGO” marking on the cover
  3. All -ALERT models have an “ALERT” marking on the cover

3825 Ohio Avenue St. Charles, IL 60174 Phone : 800-SENSOR2 Fax : 630-377-6495 www.systemsensor.com

©2017 System Sensor. Product specifications are subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS86503  03/17

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

SYSTEM SENSOR User Manuals

Related Manuals