ZURN WILKINS 760 Dual Check Valve Backflow Preventer Instruction Manual

June 13, 2024
ZURN WILKINS

ZURN WILKINS 760 Dual Check Valve Backflow Preventer

Product Information

The ZURN WILKINS Model 760 is a Dual Check Valve Backflow Preventer with Intermediate Atmospheric Vent. It is designed to be installed on boiler-fill water lines to protect against both back siphonage and back pressure of polluted water into the potable water supply. This assembly provides protection where there is no potential health hazard.

The proper performance of the Model 760 depends on following the installation instructions and prevailing governmental and industry standards and codes. It is important to note that annual inspection and maintenance are required for all plumbing system components, including this product, to ensure proper performance and maximum life.

Product Usage Instructions

  1. Before installation, flush the pipelines thoroughly to remove sediment, pipe scale, and other foreign material.
  2. The Model 760 can be installed in a horizontal or vertical position downstream of a shut-off valve. It should be installed in an accessible location for easy servicing. If installed vertically, an elbow must be installed at the vent to ensure a downward flow.
  3. Under certain backflow conditions, the Model 760 may spill water from the vent port. It is important to collect this spillage through an air gap, funnel, or other means. The vent port should never be directly piped into a drainage ditch, sewer, or pump. The vent port or drain line should never be plugged.
  4. When installing the valve with solder connections, do not attempt to solder with the valve assembled. First, remove both end connections and slide union nuts over the tubing. Prepare the solder joint, solder the end connections onto the tubing, and reassemble the valve once the solder has cooled.

Remember that installation of the Model 760 must be performed by qualified, licensed personnel to ensure the proper functioning of the device. Faulty installation can lead to improper device functioning. Following the installation instructions and conducting regular inspections, testing, and cleaning will help maintain the performance and longevity of the product.

Model 760
Dual Check Valve Backflow Preventer With Intermediate Atmospheric Vent ( 1/2” & 3/4”)

Installation Instructions

CAUTION : Installation of Model 760 must be performed by qualified, licensed personnel. Faulty installation could result in an improperly functioning device.

ZURN WILKINS Model 760 Dual Check Valve Backflow Preventer with Intermediate Atmospheric Vent is designed for installation on boiler fill water lines to protect against both back siphonage and backpressure of polluted water into the potable water supply. Assembly shall provide protection where a potential health hazard does not exist.

Proper performance depends upon following these installation instructions and prevailing governmental and industry standards and codes. Failure to do so releases ZURN WILKINS of any liability that it might otherwise have concerning that device. NOTICE: Annual inspection and maintenance is required of all plumbing system components. To ensure proper performance and maximum life, this product must be subject to regular inspection, testing, and cleaning.

  1. Before Installation of the ZURN WILKINS Model 760 Backflow Preventer, pipelines should be flushed thoroughly to remove all sediment, pipe scale, and other foreign material.
  2. The Model 760 can be installed in a horizontal or vertical position downstream of a shut-off valve and in an accessible location to facilitate servicing. When installed vertically, an elbow must be installed at the vent to ensure a downward flow. Under certain backflow conditions, the Model 760 will spill water from the vent port.
    • WARNING: Provisions should be made to collect this spillage through an air gap, funnel, or other means. The vent port should never be directly piped into a drainage ditch, sewer, or pump.
  3. Under no circumstances should the vent port or drain line be plugged.
  4. When installing the valve with solder connections, do not attempt to solder with the valve assembled. First, remove both end connections and slide union nuts over the tubing. Prepare the solder joint. Solder the end connections onto the tubing and reassemble the valve when the solder has cooled.
  5. The Model 760 Backflow Preventer must be inspected periodically for any discharge from the vent port which will provide a visual indication of the need for maintenance or repair

WARNING : Cancer and Reproductive Harm www.P65Warnings.ca.gov

WARRANTY

ZURN WILKINS Valves are guaranteed against defects of material or workmanship when used for the services recommended. If in any recommended service, a defect develops due to material or workmanship, and the device is returned, freight prepaid, to ZURN WILKINS within 12 months from the date of purchase, it will be repaired or replaced free of charge. ZURN WILKINS’ liability shall be limited to our agreement to repair or replace the valve only.

WARNING : This product is NOT Free by U.S. Federal Law and is illegal in the U.S. for use in potable services or for installation in water systems anticipated for human consumption.

ZURN WILKINS
1747 Commerce Way, Paso Robles, CA 93446

www.zurn.com

IS760 (REV. D 4/23)