Raritan NX1-B3101 PDU BASIC 0U Locking Outlets Instruction Manual

June 13, 2024
Raritan

Raritan NX1-B3101 PDU BASIC 0U Locking Outlets

Raritan-NX1-B3101-PDU-BASIC-0U-Locking-Outlets-PRODUCT

Product Information

  • Product Name: PDU BASIC 0U, 3 PHASE 16A, 24 C13 + 6 C19 LOCKING OUTLETS, IEC 60309
  • Product Category: Power Distribution Unit
  • Manufacturer: Raritan Europe
  • Manufacturer Address: Jan van Galenstraat 59, 3115 JG, Schiedam, The Netherlands
  • Manufacturer Contact: Phone: (31) 10-284-4040, Fax: (31) 10-284-4049
  • Manufacturer Website: www.raritan.com/eu
  • Catalog Number: NX1-B3101

Product Features

  • Provides electric power for IT equipment in 19″ enclosures
  • Specifically designed for Data Center applications
  • Cable locking system on C13/C19 sockets to prevent unintended disconnection
  • Pull-out force of 100 N
  • Compatible with any standard compliant cord type on the market
  • Zero-U casing made of aluminium
  • 24 C13 outlets and 6 C19 outlets
    • Nominal output voltage: 230V
    • IP rating: 20
    • IK rating: 04
  • Includes mounting solutions for rack installation
  • Complies with safety standards, circuit breaker standards, and electromagnetic compatibility standards
    • Regulatory approvals : CE, UKCA, CMIM, RoHS directive, REACH regulations

Product Usage Instructions

  1. Ensure that the PDU is installed in a suitable 19″ enclosure or rack.
  2. Connect the input plug to a power source using the provided cord.
  3. Make sure the cord entry is secured and compatible with the cable type being used.
  4. Check that the maximum input current does not exceed the PDU’s capacity.
  5. Verify that the nominal input voltage matches the power source voltage.
  6. Ensure that the input frequency is within the acceptable range for the PDU.
  7. Connect the IT equipment to the appropriate outlets on the PDU.
  8. Use the cable locking system on C13/C19 sockets to secure the cords and prevent unintended disconnection.
  9. If necessary, adjust the mounting position of the PDU using the included mounting solutions.
  10. Refer to the circuit breaker type and handle any circuit breaker issues accordingly.
  11. Observe the environmental characteristics such as storage and operating temperature, humidity, and elevation.

KEY FEATURES

NX1 PDUs provide electric power for IT equipment in 19” enclosures.

  • They have been designed with specific features for Data Center applications.
  • Each C13 and C19 outlets are numbered and equipped with a cord locking (100 Newton retention force).
  • The circuits of the 32A PDUs are equipped with hydraulic magnetic circuit protection. Hydraulic magnetic circuit breakers are not affected by ambient temperature.
  • High ambient temperature rating: 55°C
  • Easy installation thanks to 330° rotating cable input and button-type brackets

INPUT

Input Plug IEC 60309 16A 3P+N+E
Cord Length 3m – 9.84 ft
Cord Entry Rotating (330°), bottom front
Cable Type HO7RNF 5G2.5 LSZH
Maximum Input Current 16A
Nominal Input Voltage 400V, 3-phases
Rated Input Voltage 346-415V
Input Frequency 50/60Hz
Power Capacity 11.1kW at 400V

OUTPUT

Nominal Output Voltage 230V
Outlet type 24 C13 + 6 C19
Cord locking system Yes
Cord Retention 100 N
Circuit breakers No
Circuit breakers type No

Cable locking system on C13/C19 sockets

  • The cable is locked mechanically into the socket to prevent any unintended disconnection (caused by maintenance, vibrations, etc.). Pull-out force 100 N
  • This universal solution is compatible with any standard compliant cord type on the market.

Raritan-NX1-B3101-PDU-BASIC-0U-Locking-Outlets-FIG-1

MECHANICAL FEATURES

  • Casings: 6060 T5-R19 natural anodised aluminium

  • Outlet modules:
    PC/ABS CW507L (CuZn 36) brass

  • Fixing brackets:
    DC01-A-m galvanised steel

Color Aluminium grey (casing) / black (outlet modules)
Casing Zero-U, aluminium
IP 20
IK 04

ENVIRONMENTAL CHARACTERISTICS

Raritan-NX1-B3101-PDU-BASIC-0U-Locking-Outlets-FIG-2

DIMENSIONS

Raritan-NX1-B3101-PDU-BASIC-0U-Locking-Outlets-
FIG-3

MOUNTING SOLUTIONS

INCLUDED

Delivered with 2 different sets for mounting in a rack.

Set of 2 buttons
Screwless fixing. The height of the fixing centre can be set at any point along the full height of the PDU by sliding the button slots into the groove on the rear of the PDU. Tightened using a screwdriver.

Raritan-NX1-B3101-PDU-BASIC-0U-Locking-Outlets-FIG-4

Set of 2 standard fixing brackets
Screw-fixing (screws not included)

Raritan-NX1-B3101-PDU-BASIC-0U-Locking-Outlets-FIG-5

OPTION
Brackets for Nexpand racks
Screw-fixing (2 screws included)
Ref. 981227 Set of 2 brackets (for 1 PDU) Ref. 981228 Set of 20 brackets (for 10 PDUs)

Raritan-NX1-B3101-PDU-BASIC-0U-Locking-Outlets-FIG-6

STANDARDS AND REGULATIONS

STANDARDS

Application Standards
Safety IEC 62368-1
C13 and C19 connectors for electrical equipment IEC 60320-2-2

IEC 62368-1

Circuit breakers| Not Applicable
Industrial plugs| IEC 60309-1
Information and communication technology equipment| IEC 62368-1
Electromagnetic compatibility| EN 62311 (2008) EMF

EN 50491-5-2

EN 50491-5-3

EN 55035

EN 55032

EN 61000-4-11

EN 61000-4-2

EN 61000-4-3

EN 61000-4-4

EN 61000-4-5

EN 61000-4-6

EN 61000-3-2

REGULATORY APPROVALS

  • CE, UKCA, CMIM
  • RoHS directive (Restriction of Hazardous Substances).
  • REACH regulations (Registration, Evaluation, Authorisation & restriction of CHemicals).

CONTACT

  • ADDRESS: Raritan Europe – Jan van Galenstraat 59 – 3115 JG, Schiedam The Netherlands
  • Phone: (31) 10-284-4040
  • Fax: (31) 10-284-4049
  • www.raritan.com/eu
  • Technical data sheet: FT-NX1-B3101-EN-00