Raritan NX1-BHD3301 Rack Power Distribution Units Instruction Manual

June 13, 2024
Raritan

Raritan Europe – Jan van Galenstraat 59 – 3115 JG, Schiedam
The Netherlands Phone: (31) 10-284-4040 Fax: (31) 10-284-4049
www.raritan.com/eu
PDU HD BASIC 0U, 3 PHASE 32A,
36 C13 + 12 C19 LOCKING OUTLETS, IEC 60309
Cat. No: NX1-BHD3301

Raritan NX1 BHD3301 Rack Power Distribution Units -

KEY FEATURES

NX1 PDUs provide electric power for IT equipment in 19” enclosures.
They have been designed with specific features for Data Center applications.
Each C13 and C19 outlets are numbered and equipped with a cord locking (100 Newton retention force).
The circuits of the 32A PDUs are equipped with hydraulic magnetic circuit protection. Hydraulic magnetic circuit breakers are not affected by ambient temperature.
High ambient temperature rating: 55°C
Easy installation thanks to 330° rotating cable input and button-type brackets

INPUT

Input Plug IEC 60309 32A 3P+N+E
Cord Length 3m – 9.84 ft
Cord Entry Rotating (330°), bottom front
Cable Type HO7RNF 5G6 LSZH
Maximum Input Current 32A
Nominal Input Voltage 400V, 3-phases
Rated Input Voltage 346-415V
Input Frequency 50/60Hz
Power Capacity 22.2kW at 400V

OUTPUT

Nominal Output Voltage 230V
Outlet type 36 C13 + 12 C19
Cord locking system Yes
Cord Retention 100 N
Circuit breakers Yes
Circuit breakers type Mecanic Hydraulic (curve D)

Cable locking system on C13/C19 sockets
The cable is locked mechanically into the socket to prevent any unintended disconnection (caused by maintenance, vibrations, etc.).
Pull-out force 100 N
This universal solution is compatible with any standard compliant cord type on the market.

Raritan NX1 BHD3301 Rack Power Distribution Units -
fig1

MECHANICAL FEATURES

– Casings: 6060 T5-R19 natural anodised aluminium
– Outlet modules: PC/ABS CW507L (CuZn 36) brass
– Fixing brackets:
DC01-A-m galvanised steel

Color Aluminium grey (casing) / black (outlet modules)
Casing Zero-U, aluminium
IP 20
IK 04

ENVIRONMENTAL CHARACTERISTICS

Storage and transport tempe- rature -20 to +70°C
Operating temperature +5°C to +55°C
Operating Relative Humidity 5% to 95%
Operating Elevation 0 – 2000 m

ELECTRICAL DIAGRAM

Raritan NX1 BHD3301 Rack Power Distribution Units -
fig2

DIMENSIONS

Raritan NX1 BHD3301 Rack Power Distribution Units -
fig3

MOUNTING SOLUTIONS

8.1 INCLUDED
Delivered with 2 different sets for mounting in a rack.
Set of 2 buttons
Screwless fixing. The height of the fixing centre can be set at any point along the full height of the PDU by sliding the button slots into the groove on the rear of the PDU. Tightened using a screwdriver.

Raritan NX1 BHD3301 Rack Power Distribution Units -
fig4

Set of 2 standard fixing brackets
Screw-fixing (screws not included)

Raritan NX1 BHD3301 Rack Power Distribution Units -
fig5

Fixing centres (min.-max.) with standard brackets : 1752mm -1772mm

8.2 OPTION
Brackets for Nexpand racks
Screw-fixing (2 screws included)
Ref. 981227 Set of 2 brackets (for 1 PDU)
Ref. 981228 Set of 20 brackets (for 10 PDUs)

Raritan NX1 BHD3301 Rack Power Distribution Units -
fig6

STANDARDS AND REGULATIONS

9.1 STANDARDS

Application Standards
Safety IEC 62368-1
C13 and C19 connectors for electrical equipment IEC 60320-2-2 IEC 62368-1
Circuit breakers IEC 60934
Industrial plugs IEC 60309-1
Information and communication technology equipment IEC 62368-1
Electromagnetic compatibility EN 62311 (2008) EMF

EN 50491-5-2
EN 50491-5-3
EN 55035
EN 55032
EN 61000-4-11
EN 61000-4-2
EN 61000-4-3
EN 61000 4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-3-2

9.2 REGULATORY APPROVALS
CE, UKCA, CMIM
RoHS directive (Restriction of Hazardous Substances).
REACH regulations (Registration, Evaluation, Authorisation & restriction of CHemicals).

Technical data sheet: FT-NX1-BHD3301-EN-00
Updated: Created: 15/05/2023