FAS ELECTRONICS IOL-712 IO-Link Analog Adapter User Guide
- June 13, 2024
- FAS ELECTRONICS
Table of Contents
FNI IOL-712-000-K023
FNI IOL-714-000-K023
User’s Guide FAS Network Interface / 10-Link
Notes
1.1. Structure of the guide
The guide is organized so that the sections build on one another.
Section 2: Basic safety information.
1.2. Typographical conventions
The following typographical conventions are used in this guide.
Enumerations
Enumerations are shown in list form with bullet points:
- Entry1
- Entry2
Actions
Action instructions are indicated by a preceding triangle. The result of an
action is indicated by an arrow.
- Action instruction 1
- Action result
- Action instruction 2
Syntax
Numbers:
Decimal numbers are shown without additional indicators (e.g. 123),
Hexadecimal numbers are shown with the additional indicator hex (e.g. 00hex).
Cross references
Cross references indicate where additional information on the topic can be
found.
1.3. Symbols
Note
This symbol indicates general notes.
Attention!
This symbol indicates a security notice which most be observed.
1.4. Abbreviations
FNI | FAS Network Interface |
---|---|
I-Port | Standard input port |
DPP | Direct parameter page |
1oL | 10-Link |
EMC | Electromagnetic compatibility |
FE | Function ground |
SPDU | Service Protocol Data Unit |
1.5. Deviating views
Product views and illustrations in this user’s guide may differ from the
actual product. They are intended only as illustrative material.
Safety
2.1. Intended use
This guide describes the FAS Network Interface FNI 10L-712/714-000-K023 for
the application as peripheral output module to connect analogue sensors.
Hereby it is about an 10-Link device which communicates by means of |O-Link
protocol with the superordinate 10-Link master assembly.
2.2. Installation and startup
Attention!
Installation and startup are to be performed only by trained specialists.
Qualified personnel are persons who are familiar with the installation and
operation of the product, and who fulfills the qualifications required for
this activity. Any damage resulting from unauthorized manipulation or improper
use voids the manufacturer’s guarantee and warranty. The Operator is
responsible for ensuring that applicable of safety and accident prevention
regulations are complied with.
2.3. General safety notes
Commissioning and inspection
Before commissioning, carefully read the operating manual.
The system must not be used in applications in which the safety of persons is
dependent on the function of the device.
Authorized Personnel
Installation and commissioning may only be performed by trained specialist
personnel.
Intended use
Warranty and liability claims against the manufacturer are rendered void by:
- Unauthorized tampering
- Improper use
- Use, installation or handling contrary to the instructions provided in this operating manual
Obligations of the Operating Company
The device is a piece of equipment from EMC Class A. Such equipment may
generate RF noise. The operator must take appropriate precautionary measures.
The device may only be used with an approved power supply. Only approved
cables may be used.
Malfunctions
In the event of defects and device malfunctions that cannot be rectified, the
device must be taken out of operation and protected against unauthorized use.
Intended use is ensured only when the housing is fully installed.
2.4. Resistance to aggressive substances
Attention!
The FNI modules generally have a good chemical and oil resistance. When
used in aggressive media (eg chemicals, oils, lubricants and coolants each in
high concentration (ie, low water content)) must be checked prior application-
related material compatibility. In the event of failure or damage to the FNI
modules due to such aggressive media are no claims for defects.
Hazardous voltage
Attention!
Disconnect all power before servicing equipment.
Note
In the interest of product improvement, the FAS reserves the right to change
the specifications of the product and the contents of this manual at any time
without notice.
Getting started
3.1. Connection overview
- Status LED: Supply, Communication
- Label
- 10-Link interface
- Analogue input port
3.2. Mechanical connection
To avoid long, shielded analogue cables, the FNI IOL-712/714-000-K023
modules should be attached to the analogue unit which has to be connected. No
further mechanical attachment is required.
3.3. Electrical connection
The FNI IOL-712/714-000-K023 modules require no separate supply voltage
connection. Power is provided through the I0-Link interface by the
superordinate |0-Link Master Assembly.
3.4. 10-Link interface
10-Link (M12, A-coded, male)
| Pin| Signal
---|---|---
1| Supply voltage, +24V
2| –
3| GND, reference potential
4| C/Q, IO-Link Data transmission channel
Connecting the module
» Connect the FNI IOL-…-K023 either to an 10-Link Master directly or to an
analogue sensor.
» Connect the male plugs unconnected by using cables.
Note
A standard 3 wire sensor cable is used for connection to the host 10-Link
master.
Note
A shielded 4 wire sensor cable is used for connection to the analog actuator.
Getting started
Module versions
Module versions | Analogue port |
---|---|
FNI IOL-712-000-K023 | Current input(4-20mA) |
ENIIOL-714-000-K023 | Voltage input (0-10V) |
3.5. Sensor interface
Analogue input port (M12, A-coded, female)
| Pin| Signal
---|---|---
1| +24V, mA*
2| Voltage input 0-10V2
3| GND
4| Current input 0-20mA”
- Only in case of FNI 10L-712-000-K023
- Only in case of FNI 10L-714-000-K023
- Depending on the I0-Link master, but max. 2A.
lO-Link interface
4.1. 10-Link data
FNIIOL-712-000-K023
Data transmission rate | COM2 (38,4 k Baud) |
---|---|
Frame type | 2.2 |
Minimal cycle time | 3ms |
Process data cycles | 3 ms, at minimal cycle time |
Prozess data length | 2 byte input |
FNIIOL-714-000-K023
Data transmission rate | COM2 (38,4 k Baud) |
---|---|
Frame type | 2.2 |
Minimal cycle time | 3ms |
Process data cycles | 3 ms, at minimal cycle time |
Prozess data length | 2 byte input |
4.2. Process data / input data
FNI IOL-712-000- K023
FNI IOL-714-000- K023
Note
The measuring range from 0 —21.15 mA (for FNI IOL-712-000-K023) will be shown
in 16384 steps.
Note
The measuring range from 0 – 10 Volt (for FNI IOL-714-000-K023) will be shown
in 16384 steps.
4.3. Parameter data/ Request data
| DPP| SPDU| Object name| Length| Range| Default
value
---|---|---|---|---|---|---
Index| Index| Sub- Index
Identification Data| 0x07| | | Vendor ID| 2 Byte| read only| 0x0454
0x08
0x09| Device ID| 3 Byte| 0x099BE2
0x099BE1
0x0A
0x0B
| 0x10| 0| Vendor name| 18 Byte| FAS(Fujian)Co.,LTD
0x11| 0| Vendor text| 16 Byte| www.fas-elec.com
0x12| 0| Product name| 19 Byte| FNI IOL-712-000-K023
FNI IOL-714-000-K023
0x13| 0| Product ID| 7 Byte| 0AC021
0AC001
0x14| 0| Product text| 18 Byte| IO-Link 1AI 0…20mA
IO-Link 1AI 0…10V
0x16| 0| Hardware Revision| 1 Byte| 1.0
0x17| 0| Firmware Revision| 23 Byte| 1.0
Parameter Data| | –| | | | |
4.4. Errors
Error Code | Additional Code |
---|---|
Device application error | Index not available |
0x80 | 0x11 |
Device application error | Subindex not available |
0x80 | 0x12 |
Device application error | Value out of range |
0x80 | 0x30 |
4.5. Events
Class / Qualifier | Code ( high + low) |
---|---|
Mode | Type |
Appears | Error |
24V
0xC0| 0x30| 0x03| 0x5000| 0x0100| 0x0010| 0x0002
0xF3| 0x5112
Disappears| Error| AL| Device Hardware| Supply| Supply low voltage| U2 =
Supply + 24V
0x80| 0x30| 0x03| 0x5000| 0x0100| 0x0010| 0x0002
0xB3| 0x5112
Technical data
5.1. Dimensions
5.2. Mechanical data
Housing materials | Plastic, Macromelt 6208 |
---|---|
IO-Link port | M12, A-coded, male |
I-port | M12, A-coded, female |
Enclosure rating per IEC 60529 | IP 67 (only when plugged in and threaded in) |
Dimensions (W x H x D in mm) | 40 x 50.4 x 14.2 |
Weight | ca. 50 g |
5.3. Electrical data
Operating voltage | 18. 30.2 V DC, per EN 61131-2 |
---|---|
Ripple | < 1% |
Current draw without load | <= 30 mA |
Resolution | 12bit |
Sampling rate | 3ms |
5.4. Operating conditions
Operating temperature | -5 °C … 70 °C |
---|---|
Storage temperature | -25 C … 70 °C |
5.5. LED indicators
Status LED
FNI IOL-71x-000-K023
LED | Indicator | Function |
---|---|---|
LED 1 | Green / Green flashing | Communication error / Communication ok |
LED 2 | Green / Green flashing | Supply sensor & module ok / Undervoltage |
Appendix
6.1. Product ordering code
6.2. Order information
Order code| Material number| Product ordering code| Label
color| Printing IN or OUT
---|---|---|---|---
0AC021| 213978| FNI IOL-712-000-K023| Red (RAL5015)| I
0AC001| 213979| FNI IOL-714-000-K023| Blue (RAL3020)| I
6.3. Scope of delivery
FNI IOL-…-K023 consists of the following components:
- 10-Link module
- User’s guide
www.fas-elec.com
FAS Electronics
Room 05, Floor 18,
Wangneng Building,Keji East
Road, Shangjie Town, Fuzhou
Tel. +86 591 2278 1506
Fax +86 591 2278 1506
sales@fas-elec.com
” www.fas-elec.com
Nr. 920741-726 E °03,.126846 eEdition G18 eReplaces Edition F18 «Subject to modification.