FAS ELECTRONICS FNI IOL-106-006-K20 IP20 Hub 32xDO NPN User Manual

June 10, 2024
FAS ELECTRONICS

FAS ELECTRONICS FNI IOL-106-006-K20 IP20 Hub 32xDO NPN

FAS-ELECTRONICS-FNI-IOL-106-006-K20-IP20-Hub-32xDO-NPN-
product

Product Information

  • The FNI IOL-106-006-K20 is a digital input/output module developed by Fuyansheng Electronics (Fujian) Co. LTD. It features an IO-Link interface, digital I/O terminal blocks, 24V terminal block, GND terminal, and status LEDs for digital I/O point 32, IO-Link, power, and actuator. The product also includes a pin illustration for power supply, actuator power supply, GND, and C/Q channel for IO-Link data transfer.
  • The digital output points are numbered from 1 to 32, with a bit descriptions and addresses assigned based on the input starts address assigned in the configuration project. The product also has a data transmission baud rate of 384 kbit/s, a minimum cycle time of 2ms, and process data cycle time of 3ms.
  • The product has an error code feature that includes device app errors, additional codes for index and subindex unavailable, and value out of range. It also has a hardware power supply feature for low voltage supply at +24V.

Product Usage Instructions

To use the FNI IOL-106-006-K20 digital input/output module:

  1. Connect the IO-Link interface, digital I/O terminal blocks, 24V terminal block, and GND terminal as shown in Figure 1.
  2. Refer to Pin Illustration in Figure 2 for power supply (+24V), actuator power supply (+24V), GND, and C/Q channel for IO-Link data transfer.
  3. Assign input start address in the configuration project to determine the numbering and bit description of the digital output points. The first point address is based on the assigned start address.
  4. Refer to Table 1-1 for data transmission baud rate, frame type, minimum cycle time, process data cycle time, and process data length.
  5. Use the error code feature to troubleshoot device app errors, index and subindex unavailable, and value out-of-range issues. See Figure 5 for additional codes and patterns.
  6. Refer to Figure 6 for the hardware power supply feature for low voltage supply at +24V.

Connection diagram

As shown in Figure 1.FAS-ELECTRONICS-FNI-IOL-106-006-K20-IP20-Hub-32xDO-
NPN-fig-1

  1. 10-Link interface
  2. Digital I/0 Terminal Blocks
  3. 24V terminal block
  4. ND terminal
  5. Status LED: Digital I/O point 32
  6. Status LEDs: I0-Link
  7. Status LED: Power
  8. Status LEDs: Actuator

I0-Link interface diagram

As shown in Figure 2.

Pin Illustrate
1 Power supply, +24V
2 Actuator power supply, +24V
3 GND
4 C/Q, IO-Link data transfer channel

10-Link data

Parameter As shown in

Table 1-1. Surface 1-1

Process data length| Process data cycle time| Minimum cycle time| Frame type| Data transmission baud rate
---|---|---|---|---
4 bytes output| 3ms, consistent with minimum cycle time| 3ms| 2 V| COM2 (38 4kbit/s)

Process data/input data

As shown in Figure 3.

Describe| Bit|  | Describe| Bit|
---|---|---|---|---|---
Digital output point  24| 7| 2| Digital output point  8| 7| 0
Digital output point  23| 6| Digital output point  7| 6
Digital output point  22| 5| Digital output   point 6| 5
Digital output point  21| 4| Digital output  point  5| 4
Digital output point  20| 3| Digital output   point  4| 3
Digital output point  19| 2| Digital output   point  3| 2
Digital output  point  18| 1| Digital output  point   2| 1
Digital output point  17| 0| Digital output   point  1| 0
Digital output  point   32| 7| 3| Digital output  point  16| 7| 1
Digital output  point   31| 6| Digital output  point  15| 6
Digital output  point   30| 5| Digital output  point  14| 5
Digital output  point   29| 4| Digital output  point  13| 4
Digital output point   28| 3| Digital output  point  12| 3
Digital ioutput point   27| 2| Digital output  point  11| 2
Digital output  point   26| 1| Digital output point  10| 1
Digital output  point   25| 0| Digital output point   9| 0

  • E. g: The input start address assigned in the configuration project is 64, then the first point address is 64.0
  • The 32nd point address is 67.7.
parameter data/request data

As shown in Figure 4.

  DPP SPDU Object name len gth Scope Defaults
Index Inde x Subi ndex
        Supplier ID 2  
  Device ID 3 0x099CE9
  0x10 0 Supplier name 19

Read only

| FAS(Fujian)Co.,LTD
0x11| 0| Supplier text| 16| www.fas-elec.com
0x12| 0| Product name| 13| FNI IOL-106-006-K20
0x13| 0| Product ID| 6| 00BS14
0x14| 0| Product text| 44| IO-Link IP20 NPN 32DO
0x16| 0| Hardware version| 8| 20200615
0x17| 0| Firmware version| 4| 2.00

Mistake

As shown in Figure 5.

Error code Additional code
Device app error 0x80 Index unavailable 0x11

Subindex unavailable 0x12
Value out of range 0x30

Event

As shown in

Class/Qualifier|

Code(High Bit + Low Bit)

---|---
Pattern| Type| Instance
Appear| Error| AL| Hardware| Powered by| Power supply low voltage| U2=Power supply+24V
0xC0| 0x30| 0x03| 0x5000| 0x0100| 0x0010| 0x0002
0xF3| 0x5112
Disappear| Error| AL| Hardware| Powered by| Power supply low voltage| U2=Power supply+24V
0x80| 0x30| 0x03| 0x5000| 0x0100| 0x0010| 0x0002
0xB3| 0x5112
Appear| Error| AL| Hardware| Powered by| Peripheral power supply
0xC0| 0x30| 0x03| 0x5000| 0x0100| 0x0060
0xF3| 0x5160
Disappear| Error| AL| Hardware| Powered by| Peripheral power supply
0x80| 0x30| 0x03| 0x5000| 0x0100| 0x0060
0xB3| 0x5160

www.fas-elec.com