FAS ELECTRONICS FNI IOL-716-000-K023 Signal Converters
FNI IOL-716-000-K023
Notes
Struture of the guide
The guide is organized so that the sections build on one another. Section 2: Basic safety information.
Typographical conventions
The following typographical conventions are used in this guide.
Enumertions
Enumertions are shown in list form with bullet points:
- Entry 1
- Entry 2
Action
Action instructions are indicated by a preceding triangle. The result of an
action is indicated by an arrow.
- Action instruction 1
- Action instruction 2
- Action instruction 2
Syntax
Numbers:
Decimal numbers are shown without additional indicators (e.g. 123),
Hexadecimal numbers are shown with the additional indicator hex (e.g. 00hex).
Cross references
Cross references indicate where additional information on the topic can be
found.
Symbols
Note
This symbol indicates general notes.
Attention!
This symbol indicates a security notice which most be observed.
Abbreviations
- FNI FAS Network Interface FAS
- O-Port Standard output port
- DPP Direct parameter page
- IOL IO-Link
- EMC Electromagnetic compatibility
- FE Function ground
- SPDU Service Protocol Data Unit
Deviating views
Product views and illustrations in this user’s guide may differ from the
actual product. They are intended only as illustrative material.
Safety
Intended use
This guide describes the FAS Network Interface FNI IOL-716-000-K023 for the
application as peripheral output module to connect analogue sensors. Hereby it
is about an IO-Link device which communicates by means of IO-Link protocol
with the superordinate IO- Link master assembly.
Installation and startup
Attention!
Installation and startup are to be performed only by trained specialists.
Qualified personnel are persons who are familiar with the installation and
operation of the product, and who fulfills the qualifications required for
this activity. Any damage resulting from unauthorized manipulation or improper
use voids the manufacturer’s guarantee and warranty. The Operator is
responsible for ensuring that applicable of safety and accident prevention
regulations are complied with.
General safety notes
Commissioning and inspection
Before commissioning, carefully read the operating manual. The system must not
be used in applications in which the safety of persons is dependent o the
function of the device.
Authorized Personnel
Installation and commissioning may only be performed by trained specialist
personnel.
Intended use
Warranty and liability claims against the manufacturer are rendered void by:
- Unauthorized tampering
- Improper use
- Use, installation or handling contrary to the instructions provided in this operating manual
Obligations of the Operating Company
The device is a piece of equipment from EMC Class A. Such equipment may
generate RF noise. The operator must take appropriate precautionary measures.
The device may only used with an approved power supply. Only approved cables
may be used.
Malfunctions
In the event of defects and device malfunctions that cannot be rectified, the
device must b taken out of operation and protected against unauthorized use.
Intended use is ensured only when the housing is fully installed.
Resistance to aggressive substances
Attention
The FNI modules generally have a good chemical and oil resistance. When
used in aggressive media (eg chemicals, oils, lubricants and coolants each in
high concentration (ie, low water content)) must be checked prior application-
related material compatibility. In the event of failure or damage to the FNI
modules due to such aggressive media are no claims for defects. FNI
FAS Network Interface / IO-Link
Hazardous voltage
Attention!
Disconnect all power before servicing equipment.
Note
In the interest of product improvement, the FAS reserves the right to
change the specifications of the product and the contents of this manual at
any
time without notice.
Getting started
Connection overview
- Status LED: Supply, Communication
- Label
- IO-Link interface IO-Link
- Analogue output port
Mechanical connection
To avoid long, shielded analogue cables, the FNI IOL-716-000-K023 modules
should be attached to the analogue unit which has to be connected. No further
mechanical attachment is required.
Electrical connection
The FNI IOL-716-000-K023 modules require no separate supply voltage
connection. Power is provided through the IO-Link interface by the
superordinate IO-Link Master Assembly. FNI IOL-716-000-K023.
IO-Link interface
IO-Link (M12, A-coded, male)
- Pin : Signal
- Supply voltage, +24V-
- GND, reference potential GND
- C/Q, IO-Link Data transmission channel C/Q, IO-Link
Connecting the module
Connect the FNI IOL-…-K023 either to an IO-Link Master directly or to an analogue sensor.
Note
A standard 3 wire sensor cable is used for connection to the host IO-Link
master.
Note
A shielded 4 wire sensor cable is used for connection to the analog actuator.
Module versions
Module versions | Analogue port |
---|---|
FNI IOL-716-000-K023 | PT100 input |
Sensor interface
Analogue input port (M12, A-coded, female)
FAS Network Interface / IO-Link
IO-Link interface
Data transmission rate | COM2 (38,4 kBaud) |
---|---|
Frame type | 2.V |
Minimal cycle time | 3 ms |
Prozess data length | 2 Byte input |
Process data / input dataoutput data
Input data
Byte0 | Byte1 |
---|---|
7 | 6 |
MSB
| PT100 input value (only in case of FNI IOL-716-000-K023)|
LSB
|
Flag
Onput data
Byte0 | Byte1 |
---|---|
7 | 6 |
–
|
–
|
–
|
–
|
–
|
–
|
–
|
–
|
–
|
–
|
–
|
–
|
–
|
–
|
–
| –
Note
The flag: 0: Positive temperature
- Negative temperature
- eg: The value is 0x1795, so the temperature is -30.18℃
- The value is 0x2710, so the temperature is 100℃
Technical data
Dimensions
Figure 5-1: Dimensions FNI IOL-…-K023
Mechanical data
Housing materials | Plastic, Macromelt 6208 |
---|---|
IO-Link port | M12, A-coded, male |
I-port | M12, A-coded, female |
Enclosure rating per IEC 60529 | IP 67 (only when plugged in and threaded in) |
Dimensions (W x H x D in mm) | 40 x 50.4 x 14.2 |
Weight | ca. 50 g |
Electrical data
Operating voltage | 18. 30.2 V DC, per EN 61131-2 |
---|---|
Ripple | < 1% |
Current draw without load | <= 30 mA |
Resolution | 15bit |
Operating Conditions
Operating temperature | -5 °C … 70 °C |
---|---|
Storage temperature | -25 C … 70 °C |
LED indicators
Status LED
LED| Indicator| Function
---|---|---
LED 1| Green / Green flashing
| Communication error / Communication ok
LED 2| Green| Supply sensor