Solplanet QG0049 Three Phase Hybrid Inverter Installation Guide
- June 13, 2024
- solplanet
Table of Contents
- QG0049 Three Phase Hybrid Inverter
- GENERAL INFORMATION
- SAFETY
- SYSTEM WIRING DIAGRAM
- EU DECLARATION OF CONFORMITY
- OVERVIEW
- SCOPE OF DELIVERY
- MOUNTING ENVIRONMENT
- DIMENSIONS
- MOUNTING
- SECOND PROTECTIVE GROUNDING
- EPS CONNECTION
- PV CONNECTION
- BATTERY CONNECTION
- COMMUNICATION SETUP
- CONTACT
- Documents / Resources
ASW05kH/06kH/08kH/10kH/12kH-T2
ASW05kH/06kH/08kH/10kH/12kH-T2-O
ASW08kH/10kH/12kH-T3
ASW08kH/10kH/12kH-T3-O
Three phase hybrid inverter
Quick Installation Guide
QG0049 Three Phase Hybrid Inverter
|
---|---
https://play.google.com/store/apps/details?id=com.aiswei.international|
https://apps.apple.com/us/app/ai-energy/id1607454432
GENERAL INFORMATION
This quick installation guide does not replace the description in the user
manual.
The contents of this guide may be updated or revised due to product
development. The information in this guide is subject to change without
notice. The latest version of this document and the manual for installation,
commissioning, configuration and decommissioning are to be found in PDF
format at www.solplanet.net.
SAFETY
2.1 Intended use
The product is a transformerless hybrid inverter with 2 or 3 MPP trackers and
a battery connection that feeds the direct current of the PV array into the
connected battery or converts it to grid-compliant three-phase current and
then feeds it into the utility grid.
The product also can convert the direct current supplied by the battery into
grid-compliant three-phase current. The product has a backup function that can
continue to supply selected circuits with power from the battery or PV system
in the event of a grid fault.
The product is intended for indoor and outdoor applications.
The product must only be connected with PV modules of protection class II (in
accordance with IEC 61730, application class A). Do not connect any sources of
energy other than PV modules to the product.
The product is not equipped with an integrated transformer and therefore has
no galvanic isolation. The product must not be operated with PV modules which
require functional grounding of either the positive or negative PV conductors.
This can cause the product to be irreparably damaged. The product may be
operated with PV modules with frames that require protective earthing.
All components must remain within their permitted operating ranges and their
installation requirements at all times.
Use the product only in accordance with the information provided in the user
manual and with the locally applicable standards and directives. Any other
application may cause personal injury or damage to property.
2.2 Important safety instructions
The product has been designed and tested strictly according to the
international safety requirements. As with all electrical or electronical
devices, there are residual risks despite careful construction. To prevent
personal injury and property damage and to ensure long-term operation of the
product, read this section carefully and observe all safety information at all
times.
The product must only be operated in connection with an intrinsically safe
lithium-ion battery approved by AISWEI. The entire battery voltage range must
be completely within the permissible input voltage range of the product.
The product must only be used in countries for which it is approved by AISWEI
and the grid operator.
The type label must be permanently attached to the product and must be in a
legible condition.
This document does not replace any regional, state, provincial, federal or
national laws, regulations or standards that apply to the installation,
electrical safety and use of the product.
DANGER
Danger to life due to high voltages of the PV array or the battery!
The DC cables connected to the battery or the PV array may be live. Touching
the DC conductors or the live components can cause to lethal electric shocks.
If you disconnect the DC connectors from the product under load, an electric
arc may occur leading to electric shock and burns.
- Do not touch non-insulated cable ends.
- Do not touch the DC conductors.
- Do not touch any live components of the product.
- Do not open the product.
- Observe all safety information of the battery manufacturer.
- All work on the product must only be carried out by qualified personnel who have read and fully understood all safety information contained in this document and the user manual.
- Disconnect the product from all voltage and energy sources and ensure it cannot be reconnected before working on the product.
- Wear suitable personal protective equipment for all work on the product.
DANGER
Danger to life due to electric shock when touching live components in backup
mode!
Even if the AC breaker and the PV switch of the inverter are disconnected, the
parts of the system may still be live when the battery is switched on due to
backup mode.
- Do not open the product.
- Disconnect the product from all voltage and energy sources and ensure it can not be reconnected before working on the product.
DANGER
Danger to life due to fire or explosion when batteries are fully discharged!
A fire may occur due to incorrect charging of fully discharged batteries. This
can result in death or serious injury.
- Make sure that the battery is not fully discharged before commissioning the system.
- Contact the battery manufacturer for further proceedings if the battery is fully discharged.
DANGER
Danger to life due to burns caused by electric arcs through short-circuit
currents!
Short-circuit currents in the battery can cause heat accumulation and electric
arcs if the battery is short circuited or wrongly installed. Heat accumulation
and electric arcs may result in lethal injuries due to burns.
- Disconnect the battery from all voltages sources prior to performing any work on the battery.
- Only use properly insulated tools to prevent accidental electric shock or short circuits during installation.
- Observe all safety information of the battery manufacturer.
DANGER
Danger to life due to electric shock when touching live system components in
case of a ground fault!
If a ground fault occurs, parts of the system may still be live. Touching live
parts and cables may result in death or lethal injuries due to electric shock.
- Disconnect the product from voltage and energy sources and ensure it cannot be reconnected before working on the device.
- Only touch the cables of the PV modules on their insulation.
- Do not touch any parts of the substructure or frame of the PV array.
- Do not connect PV strings with ground faults to the product.
WARNING
Danger to life due to electric shock from destruction of the measuring device
due to overvoltage!
Overvoltage can damage a measuring device and result in voltage being present
in the enclosure of the measuring device. Touching the live enclosure of the
measuring device results in death or lethal injuries due to electric shock.
- Only use measuring devices with the measurement span higher than the DC input voltage range equal to or higher than the voltage rating of the product.
CAUTION
Risk of burns due to high temperature.
Some parts of the enclosure can become hot during operation.
- During operation, do not touch any parts other than the enclosure lid of the product.
CAUTION
Risk of injury due to weight of product .
Injuries may result if the product is lifted incorrectly or dropped while
being transported or mounted.
- Transport and lift the product carefully. Take the weight of the product into account.
- Wear suitable personal protective equipment for all work on the product.
2.3 Symbols on the label
| Beware of a danger zone!
This symbol indicates that the product must be additionally grounded if
additional grounding or equipotential bonding is required at the installation
site.
---|---
| Beware of high voltage and operating current!
The inverter operates at high voltage and current. Work on the inverter must
only be carried out by skilled and authorized electricians.
| Beware of hot surfaces!
The inverter can get hot during operation. Avoid contact during operation.
| WEEE designation
Do not dispose of the product together with the household waste but in
accordance with the disposal regulations for electronic waste applicable at
the installation site.
| CE marking
The product complies with the requirements of the applicable EU directives.
| Certification mark
The product has been tested by TUV and got the quality certification mark.
| RCM (Regulatory Compliance Mark)
The product complies with the requirements of the applicable Australian
standards.
| Capacitor discharge
Danger to life due to high voltages in the inverter. Do not touch live parts
for 5 minutes after disconnection from the power sources.
| Observe the documentation
Observe all documentation supplied with the product.
SYSTEM WIRING DIAGRAM
EU DECLARATION OF CONFORMITY
Within the scope of the EU directives
Radio Equipment Directive 2014/53/EU
(L 153/62-106. May 22. 2014) (RED)
Restriction of the use of certain hazardous substances 2011/65/EU
(L 174/88, June 8, 2011) and 2015/863/EU (L 137/10, March 31,2015) (RoHS)
AISWEI Technology Co., Ltd. confirms herewith that the products described in
this document are in compliance with the fundamental requirements and other
relevant provisions of the above mentioned directives. The entire EU
Declaration of Conformity can be found at
www.solplanet.net.
OVERVIEW
Object | Description |
---|---|
1 | Battery Port |
2 | DC-switch |
3 | PV Input |
4 | Ai-Dongle |
5 | Communication ports |
6 | AC connector |
7 | EPS connector (Not used in T2-O and T3-O series inverter) |
8 | Additional grounding screw |
SCOPE OF DELIVERY
MOUNTING ENVIRONMENT
DIMENSIONS
MOUNTING
SECOND PROTECTIVE GROUNDING
AC CONNECTION
EPS CONNECTION
PV CONNECTION
TYPE 1 – Phoenix Contact
TYPE 2
BATTERY CONNECTION
COMMUNICATION SETUP
15.1 Communication connection
Object | Description | Terminal | PIN definition |
---|---|---|---|
1 | 2 | 3 | 4 |
RJ45-3 | Monitor | COM2 | RS485A |
RJ45-4 | BMS | COM5 | X |
Object Description Terminal | PIN Definition | ||
--- | --- | ||
1 | 2 | 3 | 4 |
Terminal-1 | DO1/DO2 | 4pin | Multifunction Relay 1 |
B | A | B | A |
Terminal-2 | | 6pin | Smart Meter | PT100 Temperture Sensor |
RS485A | RS485B | Positive | Negative |
Terminal-3 | DI*4/DRM0 | 6pin | Ripple Control Receiver Device |
DI_4 | DI_3 | DI_2 | DI_1 |
or GND
Terminal-4| CT| 6pin| Current Transformer L1(U)| Current Transformer L2(V)|
Current Transformer L3(W)
Red| Black| Red| Black| Red| Black
15.2 Current Transformer connection (optional)
15.3 Smart meter connection (optional)
15.4 Ai-Dongle connection
CONTACT
Please contact our Service Department if you have any technical questions
about our products.
The following information is needed to provide necessary assistance:
——Inverter model
——Inverter serial number
——Photovoltaic module model
——Photovoltaic modules number and strings number connected to each MPPT
——Fault code
——Installation location
EMEA
Service email: service.EMEA@solplanet.net
APAC
Service email: service.APAC@solplanet.net
LATAM
Service email:
service.LATAM@solplanet.net
Aiswei Greater China
Service email: service.china@aiswei-tech.com
Hotline: +86 400 801 9996
Taiwan
Service email: service.taiwan@aiswei-tech.com
Hotline: +886 809089212
https://solplanet.net/contact-us
Scan QR code: | Scan QR code: |
---|
Android
https://play.google.com/store/apps/details?id=com.aiswei.international|
iOS
https://apps.apple.com/us/app/ai-energy/id1607454432
AISWEI Technology CO., Ltd
Documents / Resources
|
Solplanet QG0049 Three Phase Hybrid
Inverter
[pdf] Installation Guide
QG0049 Three Phase Hybrid Inverter, QG0049, Three Phase Hybrid Inverter, Phase
Hybrid Inverter, Hybrid Inverter, Inverter
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>