PHILIPS BY698X G5 GreenPerform LED Highbay Instruction Manual

June 13, 2024
Philips

PHILIPS logo GreenPerform Highbay G5
BY698X G5
LED Highbay
Mounting instruction

BY698X G5 GreenPerform LED Highbay

PHILIPS BY698X G5 GreenPerform LED Highbay - Icon 1

Type Desc| Voltage (V)| Frequency (Hz)| Power (W)| L(mm)| W(mm)| H (mm)| Weight (Kg)| CCT| Optics
---|---|---|---|---|---|---|---|---|---
BY698X G5 LED105 Connected| 220-240~| 50/60| 68| 530| 393| 99| 5.3| CW/NW| NB/WB
BY698X G5 LED150 Connected| 220-240~| 50/60| 98| 530| 393| 99| 5.3| CW/NW| NB/WB
BY698X G5 LED200 Connected| 220-240~| 50/60| 133| 530| 393| 99| 5.3| CW/NW| NB/WB
BY698X G5 LED250 Connected| 220-240~| 50/60| 166| 530| 393| 126| 6.6| CW/NW| NB/WB
BY698X G5 LED300 Connected| 220-240~| 50/60| 203| 530| 393| 126| 6.6| CW/NW| NB/WB

Dimensions in mm

  1. Luminaire should be parallel to the floor, should not exceed < 2 °.
  2. For communication between luminaires, this would NOT allow a luminaire to luminaire distance to be greater than 10 meters.
  3. Don’t touch the sensor when you mount luminaires.

Accessory

Bracket

PHILIPS BY698X G5 GreenPerform LED Highbay - Bracket

Pipe

911401501071
BY5702 Pipe accessory

PHILIPS BY698X G5 GreenPerform LED Highbay - Pipe
accessory

Safety string

PHILIPS BY698X G5 GreenPerform LED Highbay - Safety
string

  1. Safetey string has to be mounted for this luminaire.
  2. Safety string is not provided by Signify, need to be prepared by user.
  3. Material spec of safety string should be robust and not less than SUS304 Ø3.
  4. String length:d~d+30cm.

Suspension Mounting

PHILIPS BY698X G5 GreenPerform LED Highbay - Suspension Mounting
1

PHILIPS BY698X G5 GreenPerform LED Highbay - Suspension Mounting
2

PHILIPS BY698X G5 GreenPerform LED Highbay - Suspension Mounting
3

Pipe Mounting

PHILIPS BY698X G5 GreenPerform LED Highbay - Suspension Mounting
4PHILIPS BY698X G5
GreenPerform LED Highbay - Suspension Mounting 5

Bracket Mounting

PHILIPS BY698X G5 GreenPerform LED Highbay - Bracket
Mounting

Connect Power Cable

PHILIPS BY698X G5 GreenPerform LED Highbay - Power
Cable

Brown – L
Blue – N
Yellow+Green- GND

Insulation between LV mains and control conductors is basic insulation.
Please use IP65 or above terminal box (dimension can not smaller than 10x20x25), it is not provided by Signify.

Inrush current

PHILIPS BY698X G5 GreenPerform LED Highbay - Inrush
current

MODEL| Run current| Start(Inrush)current(A)| start current
Duration(us)
fT(@SO% of| *Touch current or protective| Maximum Number of Luminaire| Maximum Number of Luminaire
---|---|---|---|---|---|---
| (A) @230V0| flpeak(A)| Ipeak)(us)| conductor current(mA)| on MCB I 6A Type B (pcs)| on MCB I6A Type C (pcs)
BY698X LEDIOS Connected| 0.33| 5.1| 760| 0.7| 12| 20
BY698X LEDI 50 Connected| 0.47| 5.1| 760| 0.7| 12| 20
BY698X LED200 Connected| 0.64| 5.1| 760| 0.7| 12| 20
BY698X LED250 Connected| 0.79| 10| 850| 0.7| 6| 10
BY698X LED300 Connected| 0.97| 10| 850| 0.7| 6| 10

The leakage current *(touch current or protective conductor current) of electrical circuit may be greatly dependent upon electrical supply cables used such as its rating and length, proper connection of electrical supply cables to luminaires and wiring connection  topology of luminaires to the supply electrical circuit amongst other site conditions.

  • In some cases referred to as Earth Leakage Current.

Top View

PHILIPS BY698X G5 GreenPerform LED Highbay - Top View

Side View

PHILIPS BY698X G5 GreenPerform LED Highbay - Side View

Sensor far away from heat source

PHILIPS BY698X G5 GreenPerform LED Highbay - heat
source

Sensor far away from air outlet

PHILIPS BY698X G5 GreenPerform LED Highbay - air
outlet

Disclaimer:

  1. In these plots, the white areas are blind spots and the detection is based on subject’s motion. An idle subject may not continue to trigger occupancy detection once the hold time expires.
  2. As PIR based sensing works on temperature difference between the subject and the ground level, the occupancy detection could vary due to clothing and size of subject.

Warning:
Place heat radiating devices outside of the monitoring cone.
Avoid drafts (e.g. from ventilators or heating systems).

PHILIPS BY698X G5 GreenPerform LED Highbay -
2023-10-08_021731

Light sensor:
The light sensor measures the total amount of light with an opening angle of 10° whereas PIR has 30°, all calculated from normal. The following aspects should be observed during installation: Minimum distance from the window ‐ refer below graph
Prevent light reflections from outside entering the sensor (for example sunlight reflection from a car/truck bonnet) as this will lead to incorrect light regulation.
As a guideline the formula 0.174 x H can be used to calculate the minimum distance between the window and sensor whereby H is the height from the top of the window to the ceiling.

  1. Please read this manual carefully before installation or using the product.
  2. The sensor should be installed far away from the door or window where there is wind speed and convection, otherwise there
  3. The recommended height to place the sensor in the ceiling is 3 meter to assure movement coverage and detection.
  4. Sensor away from signal devices such as routers (Zigbee, WIFI, etc.).
  5. : CMIIT ID:2021DJ10118

This marking indicates that this product should not be disposed with other household wastes throughout the EU. To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly to promote the sustainable  reuse of material resources. To return your used device, please use the return and collection systems or contact the retailer where the product was purchased. They can take this product for environmental safe recycling.
his marking indicates that this product should not be disposed with other household wastes throughout the EU. To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly to promote the sustainable  reuse of material resources. To return your used device, please use the return and collection systems or contact the retailer where the product was purchased. They can take this product for environmental safe recycling.

Warning

  1. The luminaire shall be installed by a qualified electrician and wired in accordance with the latest IEE electrical regulat ions or the national requirements.

  2. Turn power off before inspection, installation or removal.

  3. Before using, external earthing is must required. Earthing is also must required in its whole life.

  4. The Luminaire must be used within the applicable product specifications, installation instructions and environmental conditions for storage & operations according to application guidelines provided by Signify for product Warranty to be valid.

  5. The corrosive atmosphere or hazardous materials such as sulfur, chlorine, phthalate, etc must be avoided during the use and storage.

  6. The manufacturer will not take responsibility caused by improper use or self -modifications of the product.
    Power Connection

  7. If the external flexible cable or cord of this luminaire is damaged. It shall be exclusively replaced by the manufacturer or his service agent or a similar qualified person in order to avoid a hazard.
    Application

  8. For Indoor use only. This product is not suitable for cold storage areas where obvious temperature gradients are present, such as ventilation opening, door, etc.

  9. The height between luminous surface and ground suggested be more than 5m; the height between bottom of luminaire and mounting surface must be more than 0.3m.

  10. Similar installation or application like flood and tunnel luminaires are NOT allowed.

  11. Not suitable for use in harsh vibration and often causing vibration or swinging environment. Also, not suitable for area prone to hurricane and extreme winds.

  12. If customer require the luminous surface levelness<1°,the pipe mounting method is recommended, and suggest to use gradienter to precisely measure and adjust.
    Maintenance

  13. Periodic cleaning of the luminaire optical lens cover will ensure maximum optical efficiency.Luminaire shall be cleaned with a dry soft cloth only.

  14. The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.

  15. The control gear contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.

  16. This product contains a light source of energy efficiency class: C.

PHILIPS logo Philips and the Philips shield emblem are registered trademarks of Koninklijke Philips N.V.

Signify (China) Investment Co., Ltd.
Address: Building 9 #, Lane 888, Tianlin Road, Minhang District, Shanghai City, P.R. China
Postalcode: 200233

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals