Type Desc| Voltage (V)| Frequency (Hz)| Power (W)| L(mm)| W(mm)| H (mm)|
Weight (Kg)| CCT| Optics
---|---|---|---|---|---|---|---|---|---
BY698X G5 LED105 Connected| 220-240~| 50/60| 68| 530| 393| 99| 5.3| CW/NW|
NB/WB
BY698X G5 LED150 Connected| 220-240~| 50/60| 98| 530| 393| 99| 5.3| CW/NW|
NB/WB
BY698X G5 LED200 Connected| 220-240~| 50/60| 133| 530| 393| 99| 5.3| CW/NW|
NB/WB
BY698X G5 LED250 Connected| 220-240~| 50/60| 166| 530| 393| 126| 6.6| CW/NW|
NB/WB
BY698X G5 LED300 Connected| 220-240~| 50/60| 203| 530| 393| 126| 6.6| CW/NW|
NB/WB
Dimensions in mm
- Luminaire should be parallel to the floor, should not exceed < 2 °.
- For communication between luminaires, this would NOT allow a luminaire to luminaire distance to be greater than 10 meters.
- Don’t touch the sensor when you mount luminaires.
Accessory
Bracket
Pipe
911401501071
BY5702 Pipe accessory
Safety string
- Safetey string has to be mounted for this luminaire.
- Safety string is not provided by Signify, need to be prepared by user.
- Material spec of safety string should be robust and not less than SUS304 Ø3.
- String length:d~d+30cm.
Suspension Mounting
Pipe Mounting
Bracket Mounting
Connect Power Cable
Brown – L
Blue – N
Yellow+Green- GND
Insulation between LV mains and control conductors is basic insulation.
Please use IP65 or above terminal box (dimension can not smaller than
10x20x25), it is not provided by Signify.
Inrush current
MODEL| Run current| Start(Inrush)current(A)| start current
Duration(us)
fT(@SO% of| *Touch current or protective| Maximum Number of Luminaire| Maximum
Number of Luminaire
---|---|---|---|---|---|---
| (A) @230V0| flpeak(A)| Ipeak)(us)| conductor current(mA)| on MCB I 6A Type B
(pcs)| on MCB I6A Type C (pcs)
BY698X LEDIOS Connected| 0.33| 5.1| 760| 0.7| 12| 20
BY698X LEDI 50 Connected| 0.47| 5.1| 760| 0.7| 12| 20
BY698X LED200 Connected| 0.64| 5.1| 760| 0.7| 12| 20
BY698X LED250 Connected| 0.79| 10| 850| 0.7| 6| 10
BY698X LED300 Connected| 0.97| 10| 850| 0.7| 6| 10
The leakage current *(touch current or protective conductor current) of electrical circuit may be greatly dependent upon electrical supply cables used such as its rating and length, proper connection of electrical supply cables to luminaires and wiring connection topology of luminaires to the supply electrical circuit amongst other site conditions.
- In some cases referred to as Earth Leakage Current.
Top View
Side View
Sensor far away from heat source
Sensor far away from air outlet
Disclaimer:
- In these plots, the white areas are blind spots and the detection is based on subject’s motion. An idle subject may not continue to trigger occupancy detection once the hold time expires.
- As PIR based sensing works on temperature difference between the subject and the ground level, the occupancy detection could vary due to clothing and size of subject.
Warning:
Place heat radiating devices outside of the monitoring cone.
Avoid drafts (e.g. from ventilators or heating systems).
Light sensor:
The light sensor measures the total amount of light with an opening angle of
10° whereas PIR has 30°, all calculated from normal. The following aspects
should be observed during installation: Minimum distance from the window ‐
refer below graph
Prevent light reflections from outside entering the sensor (for example
sunlight reflection from a car/truck bonnet) as this will lead to incorrect
light regulation.
As a guideline the formula 0.174 x H can be used to calculate the minimum
distance between the window and sensor whereby H is the height from the top of
the window to the ceiling.
- Please read this manual carefully before installation or using the product.
- The sensor should be installed far away from the door or window where there is wind speed and convection, otherwise there
- The recommended height to place the sensor in the ceiling is 3 meter to assure movement coverage and detection.
- Sensor away from signal devices such as routers (Zigbee, WIFI, etc.).
- : CMIIT ID:2021DJ10118
This marking indicates that this product should not be disposed with other
household wastes throughout the EU. To prevent possible harm to the
environment or human health from uncontrolled waste disposal, recycle it
responsibly to promote the sustainable reuse of material resources. To return
your used device, please use the return and collection systems or contact the
retailer where the product was purchased. They can take this product for
environmental safe recycling.
his marking indicates that this product should not be disposed with other
household wastes throughout the EU. To prevent possible harm to the
environment or human health from uncontrolled waste disposal, recycle it
responsibly to promote the sustainable reuse of material resources. To return
your used device, please use the return and collection systems or contact the
retailer where the product was purchased. They can take this product for
environmental safe recycling.
Warning
-
The luminaire shall be installed by a qualified electrician and wired in accordance with the latest IEE electrical regulat ions or the national requirements.
-
Turn power off before inspection, installation or removal.
-
Before using, external earthing is must required. Earthing is also must required in its whole life.
-
The Luminaire must be used within the applicable product specifications, installation instructions and environmental conditions for storage & operations according to application guidelines provided by Signify for product Warranty to be valid.
-
The corrosive atmosphere or hazardous materials such as sulfur, chlorine, phthalate, etc must be avoided during the use and storage.
-
The manufacturer will not take responsibility caused by improper use or self -modifications of the product.
Power Connection -
If the external flexible cable or cord of this luminaire is damaged. It shall be exclusively replaced by the manufacturer or his service agent or a similar qualified person in order to avoid a hazard.
Application -
For Indoor use only. This product is not suitable for cold storage areas where obvious temperature gradients are present, such as ventilation opening, door, etc.
-
The height between luminous surface and ground suggested be more than 5m; the height between bottom of luminaire and mounting surface must be more than 0.3m.
-
Similar installation or application like flood and tunnel luminaires are NOT allowed.
-
Not suitable for use in harsh vibration and often causing vibration or swinging environment. Also, not suitable for area prone to hurricane and extreme winds.
-
If customer require the luminous surface levelness<1°,the pipe mounting method is recommended, and suggest to use gradienter to precisely measure and adjust.
Maintenance -
Periodic cleaning of the luminaire optical lens cover will ensure maximum optical efficiency.Luminaire shall be cleaned with a dry soft cloth only.
-
The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.
-
The control gear contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.
-
This product contains a light source of energy efficiency class: C.