MAJESTIC 33LDVR LDVR Series Direct Vent Gas Fireplace Instruction Manual

June 13, 2024
Majestic

33LDVR LDVR Series Direct Vent Gas Fireplace

Product Information: Product Name: Builder Rear Vent Direct Vent
Models: 33LDVR, 36LDVR, 39LDVR, 43LDVR Manufacturer: Vermont
Castings Group Product Usage Instructions: 1. Installation: – This
gas fireplace should be installed by a qualified installer who is
preferably NFI or WETT (Canada) certified. – Install the fireplace
in accordance with local building codes and with current CSA-B149.1
Installation codes for Gas Burning Appliances and Equipment. – For
USA installations, follow local codes and/or the current National
Fuel Gas Code (ANSI Z3.1/NFPA 54). 2. Safety Precautions: – The
fireplace gives off high temperatures, so it should be located out
of high traffic areas and away from furniture and draperies. –
Children and adults should be aware of the hazards of high surface
temperatures and should stay away from the fireplace to avoid burns
or ignition of clothing. – Due to the high glass surface
temperature, children should be carefully supervised when in the
same room as the fireplace. 3. Ventilation: – Ensure that the
fireplace has adequate ventilation and combustion air to operate
properly. – Do not connect the fireplace to a chimney flue serving
a separate solid fuel burning fireplace. 4. Gas Valve: – When the
fireplace is not in use, it is recommended to leave the gas valve
in the OFF position. 5. Bedroom Use: – These units have been
approved for bedroom use. 6. Electronic Devices: – Check with your
electronics manufacturer before installing a television or other
electronic device above this fireplace. 7. Modifications and
Repairs: – Under no circumstances should the fireplace be modified.
– Parts removed for servicing should be replaced prior to operating
the fireplace again. – Installation and any repairs must be
performed by a qualified installer, service agency, or gas
supplier. – It is recommended to have a professional service person
inspect the fireplace annually. – Gas fireplaces should be checked
annually, and more frequent cleaning may be required due to excess
lint and dust. Please refer to the complete Installation &
Operating Instructions in the provided manual for more detailed
information and specific guidelines for your model.

Builder Rear Vent Direct Vent
Models: 33LDVR, 36LDVR, 39LDVR, 43LDVR

INSTALLER/CONSUMER SAFETY INFORMATION
PLEASE READ THIS MANUAL BEFORE INSTALLING AND USING APPLIANCE
WARNING! IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY Installation and service must be performed by a qualified installer, service agency or the gas supplier.
WHAT TO DO IF YOU SMELL GAS: · Do not try to light any appliance. · Do not touch any electric switch; do not use any phone in your building. · Immediately call your gas supplier from your neighbor’s phone. Follow the gas suppliers instructions. · If you cannot reach your gas supplier call the fire department.
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.

Installation Instructions and Homeowner’s Manual

– Ê

,/
Ê

,/

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
10007317 1/13 Rev. 17

LDVR Series Direct Vent Gas Fireplace

Table of Contents
PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS BEFORE USING APPLIANCE. Thank you and congratulations on your purchase of an Vermont Castings Group fireplace. IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these instructions fully may result in a possible fire hazard and will void the warranty.

Installation & Operating Instructions
General Venting Information
Operating Instructions
Maintenance Replacement Parts Optional Accessories Warranty Energuide

General Information, Cautions, Warning……………………………………………………………..3 Requirements for the Commonwealth of Massachusetts……………………………………….4 Fireplace Dimensions……………………………………………………………………………………….5 Locating Your Fireplace…………………………………………………………………………………….6 Clearance to Combustibles ……………………………………………………………………………….6 Mantels…………………………………………………………………………………………………………..6 Hearth ……………………………………………………………………………………………………………7 Framing and Finishing………………………………………………………………………………………7 Final Finishing …………………………………………………………………………………………………7 Gas Specifications …………………………………………………………………………………………..7 Air Shutter Adjustment ……………………………………………………………………………………..7 Gas Inlet and Manifold Pressures ………………………………………………………………………7 High Elevations ……………………………………………………………………………………………….8 Gas Line Installation…………………………………………………………………………………………8 Remote ON/OFF Switch …………………………………………………………………………………..8 Alternate Switch Location………………………………………………………………………………….8 EB-1 Electrical Box ………………………………………………………………………………………….9 Electronic Gas Control Valve …………………………………………………………………………….9 Wiring Diagrams…………………………………………………………………………………………….10 General Venting ……………………………………………………………………………………………. 11 General Venting Information- Termination Location ……………………………………………..1 General Information Assembling Vent Pipes………………………………………………………13 How to Use the Vent Graph …………………………………………………………………………….14 Rear Wall Venting Applications & Installation……………………………………………………..14 Vertical Sidewall Applications & Installation ……………………………………………………….16 Below Grade Installation …………………………………………………………………………………19 Vertical Through-the-Roof Applications & Installation ………………………………………….0 Venting Components………………………………………………………………………………………3 Glass Information …………………………………………………………………………………………..4 Louvre Removal …………………………………………………………………………………………….4 Window Frame Assembly Removal ………………………………………………………………….4 Glass Cleaning………………………………………………………………………………………………4 Installation of Logs, Lava Rock & Ember Material ………………………………………………5 Flame & Temperature Adjustment…………………………………………………………………….7 Flame Characteristics …………………………………………………………………………………….7 Lighting and Operating Instructions (SIT80 Valve)…………………………………………….9 Lighting and Operating Instructions (SIT8 Valve)…………………………………………….30 Lighting and Operating Instructions (AF4000 Valve)……………………………………………31 Troubleshooting (SIT80 Valve)……………………………………………………………………….3 Troubleshooting (SIT8 Valve)……………………………………………………………………….33 Troubleshooting (AF4000 Valve)………………………………………………………………………34 Gas Control System Error Codes (AF4000 Valve)………………………………………………36 Fuel Conversion Instructions……………………………………………………………………………37 Cleaning the Standing Pilot Control System ………………………………………………………39 ……………………………………………………………………………………………………………………40 Fan Kits ………………………………………………………………………………………………………..43 Ceramic Refractory Lining……………………………………………………………………………….44 Remote Controls ……………………………………………………………………………………………44 Trim Kits ……………………………………………………………………………………………………….45 Screen Door Kits ……………………………………………………………………………………………45 Filigree Louvre Kits ………………………………………………………………………………………..45 ……………………………………………………………………………………………………………………47 ……………………………………………………………………………………………………………………48

10007317

LDVR Series Direct Vent Gas Fireplace

Installation & Operating Instructions

This gas fireplace should be installed by a qualified installer, preferably NFI or WETT (Canada) certified, in accordance with local building codes and with current CSA-B149.1 Installation codes for Gas Burning Appliances and Equipment. For USA Installations follow local codes and/or the current National Fuel Gas Code. ANSI Z3.1/NFPA 54.
FOR SAFE INSTALLATION AND OPERATION PLEASE NOTE
THE FOLLOWING:
1. This fireplace gives off high temperatures and should be located out of high traffic areas and away from furniture and draperies.
. Children and adults should be alerted to the hazards of high surface temperatures of this fireplace and should stay away to avoid burns or ignition of clothing.
3. CAUTION: Due to high glass surface temperature children should be carefully supervised when in the same room as fireplace.

1. This fireplace requires adequate ventilation and combustion air to operate properly.
13. This fireplace must not be connected to a chimney flue serving a separate solid fuel burning fireplace.
14. When the fireplace is not in use it is recommended that the gas valve be left in the OFF position.
15. These units have been approved for bedroom use.
WARNING: Check with your electronics manufacturer before installing a television or other electronic device above this fireplace.
33LDVR / 36LDVR / 39LDVR / 43LDVR Certified To
ANSI Z21.88-2009 / CSA 2.33-2009 Vented Gas Fireplace Heaters

4. Under no circumstances should this fireplace be modified. Parts removed for servicing should be replaced prior to operating this fireplace again.
5. Installation and any repairs to this fireplace must be performed by a qualified installer, service agency or gas supplier. A professional service person should be contacted to inspect this fireplace annually. Make it a practice to have all of your gas fireplaces checked annually. More frequent cleaning may be required due to excess lint and dust from carpeting, bedding material, etc.
6. Control compartments, burners and air passages in this fireplace should be kept clean and free of dust and lint. Make sure the gas valve and pilot light are turned off before you attempt to clean this fireplace.
7. The venting system (chimney) of this fireplace should be checked at least once a year and if needed your venting system should be cleaned.
8. Keep the area around your fireplace clear of combustible materials, gasoline and other flammable vapor and liquids. This fireplace should not be used as a drying rack for clothing, nor should Christmas stockings or decorations be hung on or around the fireplace.
9. Under no circumstances should any solid fuels (wood, coal, paper or cardboard etc.) be used in this fireplace.
10. The flow of combustion and ventilation air must not be obstructed in any way.
11. When fireplace is installed directly on carpeting, vinyl tile or any combustible material other than wood, the fireplace must be installed on a metal or wood panel extending the full width and depth of the fireplace.

IMPORTANT: PLEASE REVIEW THE FOLLOWING CAREFULLY Remove any plastic from trim parts before turning the fireplace ON. It is normal for fireplaces fabricated of steel to give off some expansion and/or contraction noises during the start up or cool down cycle. Similar noises are found with your furnace heat exchanger or car engine. It is not unusual for your gas fireplace to give off some odor the first time it is burned. This is due to the curing of the paint and any undetected oil from the manufacturing process. Please ensure that your room is well ventilated open all windows. It is recommended that you burn your fireplace for at least ten (10) hours the first time you use it. If the optional fan kit has been installed, place the fan switch in the “OFF” position during this time.
This appliance may be installed in an aftermarket permanently located, manufactured home or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used. The LDVR has been approved for mobile home installations.
Proposition 65 Warning: Fuels used in gas, woodburning or oil fired appliances, and the products of combustion of such fuels, contain chemicals known to the State of California to cause cancer, birth defects and other reproductive harm. California Health & Safety Code Sec. 549.6

10007317

3

LDVR Series Direct Vent Gas Fireplace

Installation & Operating Instructions

Requirements for the Commonwealth of Massachusetts
All gas fitting and installation of this heater shall only be done by a licensed gas fitter or licensed plumber.
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontally vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

Inspection
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 48 CMR 5.08()(a)1 through 4.
Exemptions
The following equipment is exempt from 48 CMR 5.08()(a)1 through 4:
· The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
· ProductApproved side wall horizontally vented gas fueled
equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 70 and ANSI/UL 034 listed and IAS certified.
Signage
A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/) inch in size, “GAS VENT DIRECTLY BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS”.

· Detailed instructions for the installation of the venting
system design or the venting system components; and
· A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
· The referenced “special venting system” instructions shall
be included with the appliance or equipment installation instructions; and
· The “special venting systems” shall be Product
Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

4

10007317

LDVR Series Direct Vent Gas Fireplace

Fireplace Dimensions

Rough

E

Opening

Depth

S

R

F

S

U

T

Rough Opening Height

V – Rough Opening Width

Centerline of 7″ Collar

Low Voltage Access
Q B
Gas Line Access
M O P
Fig. 1 Fireplace specifications and framing dimensions.

Electrical

C

Access

D

Low

I

Voltage

Electrical

H

Access

M

A

J

Gas Line

K

N

Access

L

G

Ref.

33LDVR

36LDVR

39LDVR

43LDVR

A

33″ (838 mm)

36″ (914 mm)

39″ (991 mm)

43″ (109 mm)

B

8/” (733 mm)

34¹/” (870 mm)

34¹/” (870 mm)

37″ (940 mm)

C

31¹/” (794 mm)

34¹/” (870 mm)

37¹/” (946 mm) 41¹/” (1048 mm)

D

18³/” (466 mm)

3″ (584 mm)

3″ (584 mm) 5³/” (654 mm)

E

4/” (63 mm)

4″ (610 mm)

7″ (686 mm)

31″ (788 mm)

F

11¹/” (9 mm)

16″ (406 mm)

16″ (406 mm)

16″ (406 mm)

G

14¹/” (36 mm)

18³/” (476 mm)

18³/” (476 mm) 18³/” (476 mm)

H

19³/” (501 mm)

4¹/” (616 mm)

4¹/” (616 mm)

7″ (686 mm)

I

3¹/” (590 mm)

7³/” (705 mm)

7³/” (705 mm) 30¹/” (775 mm)

J

4³/” (11 mm)

5/” (143 mm)

5/” (143 mm) 5/” (143 mm)

K

6/” (160 mm)

8″ (03 mm)

8″ (03 mm)

8″ (03 mm)

L

8/” (5 mm)

11/” (30 mm)

11/” (30 mm) 11/” (30 mm)

M

(51 mm)

” (51 mm)

” (51 mm)

” (51 mm)

N

3³/” (86 mm)

3¹/” (83 mm)

3¹/” (83 mm)

3¹/” (83 mm)

O

4³/” (11 mm)

6³/” (17 mm)

6³/” (17 mm) 6³/” (17 mm)

P

6/” (160 mm)

9¹/” (35 mm)

9¹/” (35 mm) 9¹/” (35 mm)

Framing Dimensions

Q

9/” (753 mm)

35″ (889 mm)

35″ (889 mm) 37³/” (959 mm)

R

1″ (305 mm)

16¹/” (419 mm)

16¹/” (419 mm) 16¹/” (419 mm)

S

36″ (914 mm)

41/” (1057 mm)

44″ (1118 mm) 44¹/” (111 mm)

T

51″ 195 mm) 58/” (1495 mm)

6¹/” (1581 mm) 6³/” (1584 mm)

U

5¹/” (648 mm)

9/” (748 mm)

31¹/” (790 mm) 31¹/” (794 mm)

V

33¹/” (851 mm)

36¹/” (97 mm)

39¹/” (1003 mm) 43¹/” (1105 mm)

10007317

5

LDVR Series Direct Vent Gas Fireplace

Locating Your Fireplace

E Y

A C

B X

D Y
F

X

B

LU584-R

Fig. 2 Locate gas fireplace.

A) Flat on wall

B) Cross corner

D) Room divider E) Flat on wall corner Y) 6″ minimum

C) **Island F) Chase installation

NOTE: (Fig. ) ** Island (C) and Room Divider (D) installation is possible as long as the horizontal portion of the vent system (X) does not exceed 0′ (610cm). See details in Venting Section.

  • When you install your fireplace in(D) Room divider or (E) Flat on wall corner positions (Y), a minimum of 6″ (153mm) clearance must be maintained from the perpendicular wall and the front side edge of the fireplace. Refer to (Y) in Figure .

Clearance to Combustibles
Top of Unit to Ceiling …………………………. 36″ (914 mm) Appliance
Top …………………………………………………. 0″ (0 mm) Bottom…………………………………………….. 0″ (0 mm) Side………………………………………………… 0″ (0 mm) Back ……………………………………………….. 0″ (0 mm) Venting Concentric sections of DV Vent Top, bottom & sides ………………………… 1″ (5 mm) Rear Vent Applications: Top ……………………………………………….. ” (50 mm) Sides and Bottom……………………………. 1″ (5 mm) Flex Vent …………………………………….. 7/8″ ( mm)

Mantels
The height that a combustible mantel is fitted above the fireplace is dependent on the depth of the mantel. This also applies to the distance between the mantel leg (if fitted) and the fireplace.
For the correct mounting height and widths refer to Figs. 3a and 3b, and the following Mantel Charts.
The fitting of a bay window trim kit does not effect the distances and reference points referred to in the diagram and chart.
Noncombustible mantels and legs may be installed at any height and width around the appliance.
When using paint or lacquer to finish the mantel, such paint or lacquer must be heat resistant to prevent discoloration.

6

V W X Y Z
A BC DE

3/4″ (19 mm) Scribe Moulding for use with Vermont Castings Group Cabinets

Fireplace
Top Louvre Assembly

CFM146

Top of Combustion Chamber

Mantel Chart

Mantel Shelf Ref. or Breast Plate Ref.

Mantel from Top of Combustion Chamber

Depth

36/39/43 LDVR 33LDVR

V 10″ (54 mm) A 17″ (43 mm) 16¹/” (419 mm)

W 8″ (03 mm) B 15″ (381 mm) 14¹/” (368 mm)

X 6″ (15 mm) C 13″ (330 mm) 1¹/” (318 mm)

Y 4″ (10 mm) D 11″ (79 mm) 10¹/” (67 mm)

Z ” (51 mm) E 9″ (9 mm) 8¹/” (16 mm)

Fig. 3a Combustible mantel minimum installation.

3/4″ (19 mm) Scribe Moulding for use with Vermont Castings Group Cabinets

Black Surround Face CFM164a

Mantel Leg

Side of Combustion Chamber

J IH G F
K L M N O

CFM170

Mantel

Mantel Leg FromSide

Ref.

Leg Depth Ref. of Comb. Opening

F 10″ (54 mm) K 11¹/” (9 mm)

G

8″ (03 mm) L

9¹/” (41 mm)

H

6″ (15 mm) M

7¹/” (191 mm)

I

4″ (10 mm) N 5¹/” (140 mm)

J

” (51 mm)

O 3¹/” (89 mm)

Fig. 3b Combustible mantel leg minimum installation.

10007317

LDVR Series Direct Vent Gas Fireplace

Hearth
A hearth is not mandatory but is recommended for aesthetic purposes. We recommend a noncombustible hearth which projects out 1″ (305mm) or more from the front of the fireplace.
Cold climate installation recommendation:
When installing this unit against a noninsulated exterior wall or chase, it is mandatory that the outer walls be insulated to conform to applicable insulation codes.

Framing and Finishing
Check fireplace to make sure it is levelled and properly positioned.
To mount the appliance: 1. Choose the location. . This unit comes with four (4) flanges pre-mounted on
both sides of the fireplace to allow two different drywall thicknesses to be used. Flange “A” is for 1/” drywall while flange “B” is for 5/8″ drywall. 3. Bend the desired flanges out 90° on both sides of the fireplace. Slide the fireplace into the framed opening until the flanges contact the front surfaces of the framing. Level the unit and secure it firmly in place.

Flange Position
A B

Drywall Depth 1/” / 13 mm 5/8″ / 16 mm

Flange Location for Desired Drywall Depth

A

B

Fig. 4 Nailing flanges.

FP1539

Final Finishing
Noncombustible materials such as brick or tile may be extended over the edges of the face of the fireplace. DO NOT cover any vent or grille panels.
If a Trim Kit is going to be installed on the fireplace, the brick or tile will have to be installed flush with the edges of the fireplace.

Gas Specifications

Max.

Gas

Input

Model

Fuel

Control

BTU/h

33LDVRRN

Nat

Millivolt 16,000

33LDVRRP

Prop

Millivolt 16,000

33LDVREN

Nat 4V Hi/Lo 16,000

33LDVREP Prop* 4V Hi/Lo 16,000

33LDVRIN

Nat. 6V DC Hi/Lo 16,000

33LDVRIP Prop. 6V DC Hi/Lo 16,000

36LDVRRN

Nat

Millivolt 19,500

36LDVRRP Prop

Millivolt 19,500

36LDVREN

Nat 4V Hi/Lo 19,500

36LDVREP Prop* 4V Hi/Lo 19,500

36LDVRIN

Nat. 6V DC Hi/Lo 19,500

36LDVRIP Prop. 6V DC Hi/Lo 19,500

39LDVRRN

Nat

Millivolt 3,000

39LDVRRP Prop*

Millivolt

,500

39LDVREN

Nat 4V Hi/Lo 3,000

39LDVREP Prop* 4V Hi/Lo ,500

39LDVRIN

Nat. 6V DC Hi/Lo 3,000

39LDVRIP Prop. 6V DC Hi/Lo 3,000

43LDVRRN

Nat

Millivolt 6,000

43LDVRRP Prop*

Millivolt

4,000

43LDVREN

Nat 4V Hi/Lo 6,000

43LDVREP Prop* 4V Hi/Lo 4,000

*Using conversion kit

Min. Input BTU/h 11,00 1,000 11,00 1,000 11,00 1,000 13,650 14,65 13,650 14,65 13,650 14,65 16,100 16,875 16,100 16,875 16,100 16,875 18,00 18,000 18,00 18,000

Air Shutter Adjustment

Model 33LDV 36/39/43LDV
33/36/39/43LDV

Gas Type Natural Natural
Propane

Air Shutter Opening 3/16″ Open
Top & Bottom Hole Half Closed
Fully Open

Gas Inlet and Manifold Pressures

Inlet Minimum Inlet Maximum Manifold Pressure

Natural 5.5″ w.c. 14.0″ w.c. 3.5″ w.c.

LP (Propane) 11.0″ w.c. 14.0″ w.c. 10.0″ w.c.

10007317

7

LDVR Series Direct Vent Gas Fireplace

High Elevations
Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA, installations must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having jurisdiction.
In Canada, please consult provincial and/or local authorities having jurisdiction for installations at elevations above 4,500 feet (1,370m).

Gas Line Installation
When purging the gas lines, the front window frame assembly must be removed.
The gas pipeline can be brought in through the rear of the appliance as well as the bottom. Knockouts are provided on the bottom behind the valve to allow for the gas pipe installation and testing of any gas connection. It is most convenient to bring the gas line in from the rear right side of the valve as this allows fan installation or removal without disconnecting the gas line.
The gas line connection can be made with properly tinned 3/8″ copper tubing, 3/8″ rigid pipe or an approved flex connector. Since some municipalities have additional local codes, it is always best to consult your local authority and the National Fuel Gas Code, ANSI Z3.1/NFPA 54 in the USA or the CSA-B149.1 installation code.

1/” Gas Supply

1/” NPT x 1/” Flare Shutoff Valve
3/8″ Flex Line (From Valve)

The fireplace valve must not be subjected to any test pressures exceeding 1/ psi. Isolate or disconnect this and any other gas appliance control from the gas line when pressure testing.
Remote ON/OFF Switch
Installation
1. Thread the wiring through the holes on the end panels of the fireplace. Take care not to cut the wire or insulation on metal edges. Route the wire to a conveniently located receptacle box.
. Attach the wire to the ON/OFF switch and install the switch into the receptacle box.
3. Connect the other ends of the wire to the gas control valve. (Fig. 6)
Remote ON/OFF Switch or Thermostat or Remote Control

TP

TH

Gas

Control

TP

Valve

TH Fig. 6 Remote switch wiring diagram.

FP14

Alternate Switch Location
The remote switch can be installed on the front/side of the access door. Simply mount the switch to the bracket provided and screw the bracket to either side of the frame, lining up the screws with the pre-punched holes. (Fig. 7)

FP97A
Fig. 5 Typical gas supply installation.
Always check for gas leaks with a mild soap and water solution. Do not use an open flame for leak testing.
The gas control is equipped with a captured screw type pressure test point, therefore it is not necessary to provide a 1/8″ test point up stream of the control. When using copper or flex connector use only approved fittings. Always provide a union when using black iron pipe so the gas line can be easily disconnected for burner or fan servicing. See gas specification for pressure details and ratings.
8

FP104
Fig. 7 Alternate switch location. Do not wire the remote ON/OFF wall switch for the gas fireplace to the 120 volt power supply.
10007317

LDVR Series Direct Vent Gas Fireplace

EB-1 Electrical Box
The fireplace, when installed, must be electrically connected and grounded in accordance with local codes or, in the absence of local codes, with the current CSA C22.1 Canadian Electrical Code.
For USA installations follow local codes and the national electrical code ANSI/NFPA No. 70.
It is strongly suggested that the wiring of the EB-1 Electrical Junction Box be carried out by a licensed electrician.
Ensure that the power to the supply line has been disconnected before commencing this procedure.
The EB-1 Electrical junction box has been fitted standard on this model to allow for the easy connection of an optional fan kit.
To connect the EB-1 box to the house electrical supply follow the steps below.
1. Unscrew the retaining screw from the EB-1 base plate and remove the EB-1 assembly from the a p p l i ance. (Fig. 8)
. Remove the front cover of the EB-1 box.
3. Remove the plug socket assembly from the EB-1 box.
4. Feed the supply line in through the EB-1 opening in the side of the appliance and then through the back of the EB-1 assembly. (Fig. 8)
5. Connect the black wire of the power supply line to the brass screw (polarized) of the socket assembly.
6. Connect the white wire of the power line to the chrome screw of the socket assembly.
7. Connect the ground wire of the supply line to the green screw of the socket assembly.
8. Refit the socket assembly back into the electrical box and replace the cover plate. Secure the cable with the clamp on the outside of the EB-1 base plate and refit the EB-1 assembly to the unit with the screw removed in step

INSIDE
OUTSIDE

Electrical Box Retaining Screw

Fig. 8 EB-1 receptacle.

BACK OF UNIT

FP580

Electronic Gas Control Valve
This appliance may be fitted with a Synetek ignition module.
Installation of the remote on/off starter switch or wall thermostat on electronic ignition units.
1. Thread the wiring through the holes on the side panels of the appliance. Take care not to cut the wire or insulation on metal edges. Route the wire to a conveniently located receptacle box.
. Attach the wire to the ON/OFF switch and install the switch into the receptacle box.
3. Connect the white wire from the wall switch or wall thermostat to the white wire terminal from the electronic module. Connect the black wire from the wall switch or the red wire from the wall thermostat, to the red wire terminal from the electronic module.

10007317

9

LDVR Series Direct Vent Gas Fireplace

BLACK WHITE

L1 L2 GREEN

POWER CORD

PURPLE CLEAR

PILOT SENSING PILOT IGNITER YELLOW

MP OO

CIRCUIT BOARD

BLUE
RED WHITE

VALVE
ORANGE
ON/OFF SWITCH OR
WALL THERMOSTAT

Fig. 9 SIT8 Valve with Synetek electronic control wiring diagram.

FP1571

White or Green
Green or White White or Orange
Orange or White

Pilot

Main

AF-4000

Main Module

SI

To Pilot Ignitor To Pilot Flame Sensor
Optional Remote Battery Back-Up Pack
Remote/Off Switch Continuous Pilot ON/OFF Switch

Red Black

AC Adaptor
Fig. 10 American Flame Valve AF-4010 wiring diagram.

Black Gnd

Brown Brown

(SWI) (Connect to (SWI) ON/OFF Switch)

Red

Black

Extension Harness

FP1866

10

10007317

LDVR Series Direct Vent Gas Fireplace

General Venting

Your fireplace is approved to be vented either through the side wall, or vertically through the roof.
· Only Vermont Castings Group venting components
specifically approved and labelled for this fireplace may be used.
· Vent terminations shall not be recessed into a wall or
siding.
· Horizontal venting which incorporates the twist lock pipe
must be installed on a level plane without an inclining or declining slope.
· Horizontal venting which incorporates the use of flex
venting shall have an inclining slope from the unit of 1″ (5 mm) per 4″ (610 mm).

There must not be any obstruction such as bushes, garden sheds, fences, decks or utility buildings within 4″ (610 mm) from the front of the termination hood.
Do not locate termination hood where excessive snow or ice build up may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.
Location of Vent Termination
It is imperative the vent termination be located observing the minimum clearances as shown on the next page.
*Check with local codes or in absence of same with CSAB149.1 Installation Codes (1991) for Canada or follow the current National Fuel Gas Code, ANSI Z3.1/NFPA 54 for installations in the USA.

10007317

11

LDVR Series Direct Vent Gas Fireplace

General Venting Information – Termination Location

INSIDE CORNER DETAIL
G
V H
A
D

E V L
B
CFM145a

C

V

Fixed

Closed

F V

Operable

B

B V
Operable

B

V

A

B V Fixed Closed
B J X

M I

V KX

V VENT TERMINATION X AIR SUPPLY INLET

AREA WHERE TERMINAL IS NOT PERMITTED

Canadian Installations1

US Installations2

A = Clearance above grade, veranda, porch, deck, or balcony

1″ (30cm)

1″ (30cm)

B = Clearance to window or door that may be 6″ (15cm) for appliances

6″ (15cm) for appliances

opened

< 10,000Btuh (3kW), 1″ (30cm) for appliances > 10,000 Btuh (3kW) and < 100,000 Btuh (30kW), 36″ (91cm) for appliances > 100,000 Btuh (30kW)

< 10,000 Btuh (3kW), 9″ (3cm) for appliances > 10,000 Btuh (3kW) and < 50,000 Btuh (15kW), 1″ (30cm) for

appliances > 50,000 Btuh (15kW)

C = Clearance to permanently closed window 1″ (305mm) recommended to prevent window condensation
D = Vertical clearance to ventilated soffit located

1″ (305mm) recommended to prevent window condensation

above the terminal within a horizontal distance of ‘ (610mm) from the center line of the terminal

18″ (458mm)

18″ (458mm)

E = Clearance to unventilated soffit

1″ (305mm)

1″ (305mm)

F = Clearance to outside corner

see next page

see next page

G = Clearance to inside corner (see next page) see next page

see next page

H = Clearance to each inside of center line

3′ (91cm) within a height of 15′ (5m)

extended above meter/regulator assembly above the meter/regulator assembly

3′ (91cm) within a height of 15′ (5m) above the meter/regulator assy

I = Clearance to service regulator vent outlet 3′ (91cm)

3′ (91cm)

J = Clearance to nonmechanical air supply inlet 6″ (15cm) for appliances < 10,000 to building or the combustion air inlet to any Btuh (3kW), 1″ (30cm) for

6″ (15cm) for appliances < 10,000 Btuh (3kW), 9″

other appliances

appliances > 10,000 Btuh (3kW) and < 100,000 Btuh (30kW), 36″ (91cm) for appliances > 100,000 Btuh (30kW)

(3cm) for appliances > 10,000 Btuh (3kW) and < 50,000 Btuh (15kW), 1″ (30cm) for appliances > 50,000 Btuh (15kW)

K = Clearance to a mechanical air supply inlet 6′ (1.83m)

3′ (91cm) above if within 10 feet (3m) horizontally

L = Clearance above paved sidewalk or paved 7′ (.13m)

7′ (.13m)

driveway located on public property

M = Clearance under veranda, porch, deck or balcony

1″ (30cm)

1″ (30cm)

N = Clearance above a roof shall extend a minimum of 4″ (610mm) above the highest point when it passes through the roof surface, and any other obstruction within a horizontal distance of 18″ (450mm).

1 In accordance with the current CSA-B149 Installation Codes In accordance with the current ANSI Z3.1/NFPA 54 National Fuel Gas Codes A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings only permitted if veranda, porch, deck or balcony is fully open on a minimum sides beneath the floor: NOTE: 1. Local codes or regulations may require different clearances.
. The special venting system used on Direct Vent Fireplaces are certified as part of the appliance, with clearances tested and approved by the listing agency. 3. Vermont Castings Group assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements.

Fig. 11 Vent termination locations. 1

10007317

LDVR Series Direct Vent Gas Fireplace

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

Inside Corner

Outside Corner

Alcove Applications*

G V

G = Combustible
6″ (152 mm)
Noncombustible 2″ (51 mm)

V F

F = Combustible
6″ (152 mm)
Noncombustible 2″ (51 mm)

D

C

C

V

O

E

Balcony with no side wall

Balcony with perpendicular side wall

E = Min. 2″ (51 mm) for non-vinyl sidewalls Min. 12″ (305 mm) for vinyl sidewalls O = 8′ (2.4 m) Min.

M V
M = Combustible & Noncombustible
12″ (305 mm)

M
V P
Combustible & Noncombustible M = 12″ (305 mm) P = 6″ (152 mm)

No. of Caps
1 3 4

DMin. 3′ (914 mm) 6′ (1.8 m) 9′ (.7 m) 1′ (3.7 m)

CMax. x DActual 1 x DActual /3 x DActual 1/ x DActual

DMin. = # of Termination caps x 3 CMax. = ( / # termination caps) x DActual

584-15

*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3′ (914 mm) minimum between termination caps. . All mechanical air intakes within 10′ (1 m) of a termination cap must be a minimum of 3′ (914 mm) below the termination cap. 3. All gravity air intakes within 3′ (914 mm) of a termination cap must be a minimum of 1′ (305 mm) below the termination cap.

Fig. 12 Termination clearances.

General Information Assembling Vent Pipes

Canadian Installations:
Venting system must be installed in accordance with the current CSA-B149.1 installation code.
USA Installations:
The venting system must conform with local codes and/or the current National Fuel Gas code ANSI Z3.1/NFPA 54.
Only venting components manufactured by Vermont Castings Group can be used in Direct Vent systems.

  • Be sure the vent is actually crushed before proceeding. Apply a tug to be sure the vent will not slip off the collars. Repeat process with 7″ flex vent pipe. The same procedure must be performed on the vent side.
    Apply High Temperature Sealant

Flex Vent Pipes

Before joining the flex vent pipe to the unit, apply a bead of high temperature sealant* (provided) to the 4″ pipe exiting the fireplace. Secure flex vent piep in place with a hose clamp (provided).

*Be sure the flex pipe overlaps at least 1″ (5mm) onto the collars of the fireplace and termination. If the termination has an internal bead, be sure to overlap and secure 1″ (5mm) past the bead.

Hose Clamp FP1471
Fig. 13 Apply high temperature sealant to 4″ and 7″ pipes.

10007317

13

LDVR Series Direct Vent Gas Fireplace

Twist Lock Pipes
When using Vermont Castings Group twist-lock pipe it is not necessary to use sealant on the joints. The only areas of the venting system that need to be sealed with high temperature silicone sealant are the sliding joints of any telescopic vent section used in the system.
To join the twist lock pipes together, simply align the beads of the male end with the grooves of the female end, then while bringing the pipe together, twist the pipe until the flange on the female end contacts the external flange on the male end. It is recommended that you secure the joints with three (3) sheet metal screws, however this is not mandatory with twist lock pipe.
To make it easier to assemble the joints we suggest putting a lubricant (Vaseline or similar) on the male end of the twist lock pipe prior to assembly.

Male End

Female End

Screw Holes Fig. 14 Twist-lock pipe joints.

TWL100

How to Use the Vent Graph
The vent chart should be read in conjunction with the following vent installation instructions to determine the relationship of the vertical and horizontal dimensions of the vent system.
1. Determine the height of the center of the horizontal vent pipe exiting through the outer wall. Using this dimension on the Sidewall Vent Graph (Fig. 15) locate the point intersecting with slanted graph line.
. From the point of this intersection, draw a vertical line to the bottom of the graph.
3. Select the indicated dimension, and position the fireplace in accordance with same.
Example A: If the vertical dimension from the floor of the fireplace is 11′ (3.4 m) the horizontal run to the face of the outer wall must not exceed 14′ (4.3 m).
Example B: If the vertical dimension from the floor of the unit is 7′ (.14 m), the horizontal run to the face of the outer wall must not exceed 8¹/’ (.6 m).

Vertical dimension from the floor of the unit to the center of the horizontal vent pipe

30

29

28

27

26

25

24

23

22

21

20

19

18

17

16

15

14

13

12

eg: A

11

10

9

8

7

eg: B

6

5

4

3

3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Horizontal dimension from the outside face of the wall to the center of the fireplace vent flange
Sidewall vent graph showing the relationship between vertical and horizontal dimensions for a Direct Vent flue system.
Fig. 15 Sidewall venting graph. (Dimensions in feet)

Rear Wall Venting Applications

When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind the appliance.
· Only Vermont Castings Group venting components
are approved to be used in these applications. (Refer to “Venting Components” listed for different installation requirements)
· The maximum horizontal distance between the rear of
the appliance (or end of the transition elbow in a corner application) and the outside face of the rear wall is 0″ (508mm). (Fig. 16)
· Only one 45° elbow is allowed in these installations. · Minimum clearances between vent pipe and combus-
tible materials are as follows:
Top – ” (51 mm) Sides – 1″ (5 mm) Bottom – 1″ (5 mm)

14

10007317

20″ (508mm)

LDVR Series Direct Vent Gas Fireplace

Vent Opening for Combustible Wall 9³/”
(40mm)

10³/” (64mm)

Framing Detail

Top View Straight Venting

20″ (508mm)
Max.

20″ (508mm)
Max.

Fireplace Hearth Opening for Noncombustible Wall
7¹/” (190mm)

VO584-100

45°

45°

Fig. 17 Locate vent opening on wall.

Adjustable Zero Clearance Sleeve

Max. Length 1″ (305mm) #8 Screws ()

Top View Rear Vent Corner Installation Fig. 16 Rear vent applications, one 45° elbow.
Rear Wall Installation Twist Lock Pipe
STEP 1 Locate vent opening on the wall. To locate hole center consult with appropriate fireplace dimensions, Page 4. Frame as shown below. NOTE: When using flex vent, the opening will have to be measured according to the 1/” (13 mm) rise in 1″ (305 mm) vertical run. Combustible Walls (Fig. 17): Cut a 10³/”H x 9³/” W (64 x 40 mm) hole through the exterior wall and frame as shown. Noncombustible Walls (Fig. 17): Hole opening must be 7¹/” (190 mm) in diameter. STEP 2 Measure wall thickness and cut zero clearance sleeve parts to proper length (MAXIMUM 1″/305 mm). Assemble sleeve and attach to firestop with

8 sheet metal screws (supplied). (Fig. 18)

10007317

8 Screws ()

Firestop

8 Screws ()

Adjustable Zero Clearance Sleeve Fig. 18 Adjustable zero clearance sleeve.

ZCS101

STEP 3
Measure from the fireplace collar or elbow face to face of outside wall (add ” for vent pipe overlap). Mark pipes and cut to length. It is very important that the two pipes are flush with the outside wall once the fireplace is in its final location. (Fig. 19)

STEP 4

Slip 4″ and 7″ pipes onto respective flue collars. Make sure to fix to the fireplace collar the 4″ pipe with three (3) screws before fixing the 7″ pipe on the 7″ collar. Both pipes must be on a level plane. (Fig 0)

STEP 5

Guide the vent termination 4″ collar into the 4″ pipe then the 7″ collar into the 7″ pipe. Do not force the venting into position. If the pipes do not line up with the termination collars, disassemble pipes and reattach to the fireplace collar. (Fig. 1)

STEP 6

Secure fireplace to floor through floor holes and adjustable frame drywall strip (nailing flange) to frame. (Refer to Framing & Finishing Section).

15

LDVR Series Direct Vent Gas Fireplace
Zero Clearance Sleeve
Firestop

Termination
Flex Section Appliance Collars

CFM133
Fig. 19 Firestop and zero clearance sleeve in place.

Finished Wall

Vent Termination

FP1473
Fig. 21 Grasp the vent pipe close to the collar and bend to 45° angle. Do not exceed 45°.

Rise

FP1005
Fig. 20 Side view of final unit location.
Rear Wall Vent Installations Flex Vent Pipe
Follow Steps 1 and on Page 15.
Step 3
Install the 4″ (10 mm) flex vent pipe to the appliance collars described in “General Information Assembling Vent Pipes”, Page 11. If the installation requires a 45° angle, grasp the vent pipe close to the appliance collar and bend to 45°. DO NOT exceed 45°. (Fig. 1) Install the 7″ vent pipe in the same manner as Step . NOTE: There must be a 1″ (5 mm) rise in a 4″ (610mm) length of flex vent.
Step 4
Assemble the flex vent to the collars on the termination as you did on the appliance.

Fig. 22 There must be a 1/” rise per foot length.

FP147

Vertical Sidewall Applications

Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.
The Vent Graph shows the relationship between vertical and horizontal side wall venting and will help to determine the various dimensions allowable.
Minimum clearance between vent pipes and combustible materials is 1″(25 mm) on top, bottom and sides unless otherwise noted.
When vent termination exits through foundations less than 0″ below siding outcrop, the vent pipe must flush up with the siding. It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace to the face of the outer wall.
Horizontal plane means no vertical rise exists on this portion of the vent assembly.

16

10007317

· The maximum horizontal vent run is 0 ft. (6.1 m) when
the vertical vent rise is 7¹/ ft. (.3 m). (Fig. 3)
· The maximum number of 90° elbows per side wall
installation is three (3).

Vertical Dimension 7¹/’ Minimum When Horizontal Run is 0′

Maximum 20 ft. (6.1m)
12″ (305mm)
15 ft. (4572mm)

48″ (1.2m)

7 ft. 6 in. (2286 mm)

LDVR Series Direct Vent Gas Fireplace

10 ft. (3048 mm)

7 ft. (2134 mm)
90° Elbow = 3 ft.

A + B = 17 ft. (Max.)

7.5′ (2.3m)

CFM141

7TDVRT90 Elbow

Fig. 23 Maximum number of 90° elbows is three (3).
· If a 90° elbow is used in the horizontal vent run (level
height maintained) the maximum horizontal vent length is reduced by 36″ (914 mm). (Fig. 4) This does not apply if the 90° elbows are used to increase or redirect a vertical rise. (Fig. 5)

Maximum 3′ (914mm)

Fig. 25 Maximum vent run with elbows.

CFM147

· The maximum number of elbow degrees in a system is
70°. (Fig. 6)

Example:

Elbow 1 = 90°

Elbow = 45°

4

Elbow 3 = 45°

Elbow 4 = 90°

Total angular variation = 70°

1 + 2 + 3 + 4 = 270o

3
2 1

7TDVRT90 Elbow
CFM14
Fig. 24 Maximum horizontal vent run. Example: According to the chart the maximum horizontal vent length in a system with a 7.5′ (.3 m) vertical rise is 0′ (6 m) and if a 90° elbow is required in the horizontal vent it must be reduced to 17′ (5. m). In Figure 5 Dimension A plus B must not be greater than 17′ (5. m).
· The maximum number of 45° elbows permitted per side
wall installation is six (6). These elbows can be installed in either the vertical or horizontal run.
· For each 45° elbow installed in the horizontal run, the
length of the horizontal run MUST be reduced by 18″ (45cm). This does not apply if the 45° elbows are installed on the vertical part of the vent system.
10007317

CFM13
Fig. 26 Maximum number of elbows.
·IMPORTANT· Minimum clearance between vent pipes and combustible materials is one (1″) inch (5 mm) on bottom, sides and top. Twist Lock Vent Starter Kit 7TDVSK, plus Transition Elbow 7TDVRT90 must be used in Vertical Sidewall installations. The 4″ pipe must be centered inside the 7″ pipe coming off the transition elbow. Canadian & USA Installations: The venting system must conform with local codes, or in the absence of local codes, with National Fuel Gas Code, ANSI Z3.1/NFPA 54 – latest edition, or CSA B149.1 Installation Code.
Only Vermont Castings Group venting components specifically approved and labelled for this fireplace may be used.
17

LDVR Series Direct Vent Gas Fireplace

Vertical Sidewall Installation
STEP 1 Locate vent opening on the wall. It may be necessary to first position the fireplace and measure to obtain hole location. Depending on whether the wall is combustible or noncombustible, cut opening to size. (Fig. 7) For combustible walls first frame in opening. Combustible Walls (Fig. 7): Cut a 9³/”H x 9³/” W (40 x 40 mm) hole through the exterior wall and frame. Noncombustible Walls (Fig. 7): Hole opening must be 7.5″ (190 mm) in diameter.
Vent Opening for Combustible Wall 9³/”
(40mm)
9³/” (40mm)

Adjustable Zero Clearance Sleeve

Maximum Length 1″ (305mm) #8 Screws ()

8 Screws () #8 Screws ()

Wall Exterior

Adjustable Zero Clearance Sleeve

Wood Framing Firestop

Firestop Zero Clearance Sleeve Flush with Wall Exterior

Vent Pipe Drywall
Fig. 28 Locate vent opening on wall.

CFM135

Framing Detail
Fireplace Hearth Opening for Noncombustible Wall

Ensure Pipes are Concentric
8

7¹/” (190mm) Fig. 27 Locate vent opening on wall.

VO584-100

STEP 2
Measure wall thickness and cut adjustable zero clearance sleeve parts to proper length (MAXIMUM 1″/305 mm). (Fig. 8) Adjust sleeve to minimum (9³/” x 9³/” and attach to firestop with #8 sheet metal screws (supplied). Assemble sleeve and attach to firestop with #8 sheet metal screws (supplied). Install firestop assembly.
Zero clearance sleeve is only required for combustible walls.
STEP 3
Attach the appropriate venting component(s) to the inner and outer flue collars of the fireplace using three (3) screws. (Fig. 9) Follow with the installation of the inner and outer elbow. Again secure joints with three (3) sheet metal screws.

Ç/6,/ä
CFM143
Fig. 29 Apply sealant to inner and outer pipe.
STEP 4 Measure the horizontal length requirement including a ” (51 mm) overlap, i.e. from the elbow to the outside wall finish plus “, or the distance required if installing a second 90° elbow. (Fig. 30) STEP 5 Use appropriate length of pipe section – telescopic or fixed – and install the horizontal vent sections. The 0″ (508 mm) section of pipe which goes through the wall is packaged with the 7TDVSK starter kit, and can be cut to suit if necessary. (Fig. 31)
Sealing vent pipe and firestop gaps with high temperature sealant will restrict cold air being drawn in around fireplace.

18

10007317

X
Always install horizontal venting on a level plane.

LDVR Series Direct Vent Gas Fireplace

X

X

CFM136
Fig. 30 Measure horizontal length including ” overlap. X
High Temperature Sealant
CFM137
Fig. 31 Apply high temperature sealant. STEP 6 Guide the vent termination’s 4″ (10 mm) and 7″ (178 mm) collars into their respective vent pipes. Double check that the vent pipes overlap the collars by ” (51 mm). Secure the termination to the wall with screws provided and caulk around the wall plate to weatherproof. (Fig. 3) STEP 7 Support the horizontal pipes every 36″ (914 mm) with metal pipe straps. Make sure that the horizontal vent pipe is installed on a level horizontal plane. STEP 8 Re-check the fireplace to make sure that it is levelled, properly positioned, and nailed or screwed to the floor. If applied, the fireplaces adjustable frame drywall strips (nailing flanges) should be fastened. Refer to “Framing & Finishing”.

CFM138
Fig. 32 Horizontal length requirement.
Below Grade Installations
When it is not possible to meet the required vent terminal clearances of 1″ (305 mm) above grade level a snorkel vent kit #7TDVSNORK is required. It allows installation depth of down to 7″ (178 mm) below grade level. The 7″ is measured from the center of the horizontal vent pipe as it penetrates through the wall.
If venting system is installed below ground, we recommend a window well with adequate and proper drainage.
Ensure sidewall venting clearances are observed.
The maximum horizontal run with 24″ vertical rise is 36″ (914 mm) from the back of the fireplace to the face of the exterior wall. See vent graph (Page 14) for extended horizontal run if the vertical rise exceeds 24″ (610 mm).
1. Establish vent hole through the wall. (Fig. 7) . Remove soil to a depth of approximately 16″ (406mm)
below base of snorkel. Install window well (not supplied). Refill hole with 1″ (305 mm) of coarse gravel leaving a clearance of approximately 4″ (10 mm) below snorkel. (Fig. 33) 3. Install vent system. See Page 15, Steps through 5. 4. Ensure a watertight seal is made around the vent pipe coming through the wall. 5. Apply high temperature sealant caulking (supplied) around the 4″ and 7″ snorkel collars. 6. Slide into the vent pipe and secure to the wall. 7. Level the soil to maintain a 4″ (10 mm) clearance below snorkel. (Fig. 33)

10007317

19

LDVR Series Direct Vent Gas Fireplace

Zero Clearance Sleeve (if required)
Firestop 7″ Pipe
24″ (610mm) Minimum*

7TDVSNORK (Snorkel) 4″ (10mm) Clearance Min.
Window Well Gravel Drain

Foundation Wall *A minimum of 4″ (608mm) vertical pipe must be installed when using 7TDVSNORK Kit.

BG400
Fig. 33 Below grade installation. Do not back fill around snorkel. A clearance of at least 4″ (102mm) must be maintained between the snorkel and the soil.

Snorkel

Foundation Recess Recess Brackets
Watertight Seal Around Pipe

Wall Screws Sheet Metal Screws

BG401
Fig. 34 Snorkel installation, recessed foundation.
If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fasten brackets to wall first, then secure to snorkel with self drilling #8 x 1/ sheet metal screws. It will be necessary to extend vent pipes out as far as protruding wall face. (Fig. 34)

Vertical Through-the-Roof Applications
This Gas Fireplace has been approved for: 1. Vertical installations up to 40′ (1 m) in height. Up to
10′ (3 m) horizontal vent run can be installed within the vent system using a maximum of three 90° elbows.

Minimum 8′ (.4 m) / Maximum 40′ (1 m) Vertical
Rise

Maximum 10′
(3 m) Pipe Straps Every 3′ (914 mm)

Fig. 35 Support straps for horizontal runs.

CFM148

This Gas Fireplace has been approved for: 1. Vertical installations up to 40′ (1 m) in height. Up to
10′ (3 m) horizontal vent run can be installed within the vent system using a maximum of three 90° elbows.
. Up to two 45° elbows may be used within the horizontal run. For each 45° elbow used on the horizontal level the maximum horizontal length must be reduced by 18″ (457 mm).
Example: Maximum horizontal length
0 x 45° elbows = 10′ (3 m) 1 x 45° elbows = 8¹/’ (.6 m) x 45° elbows = 7′ (.1 m)
3. A minimum of an 8′ vertical rise.
4. Two sets of 45° elbows offsets within these vertical installations. From 0 to a maximum of 8′ (.4 m) of vent pipe can be used between elbows. (Fig. 36)
5. 7DVCS must be used to support offsets. (Fig. 36) This application will require that you first determine the roof pitch and use the appropriate 7DVSKV (A, B or F). (Refer to Venting Components List, Page 3)

0

10007317

LDVR Series Direct Vent Gas Fireplace

Max. 8′
(.4m)

45° Max.
8′ (.4m)

40′ (1m) 45°

Attic Insulation Shield

Typical Ceil-

Joist

ing Support

Application

Ceiling Instal-

lation

11″

11″

Upper Floor

Joist

Typical Roof Support Ap-
plication

Firestop Spacer

Typical Offset Installation Fig. 36 Typical vertical roof applications.

FP101

Vertical Through-the-Roof Installation
1. Locate your fireplace.
. Plumb to center of the (4″) flue collar from ceiling above and mark position.
3. Cut opening equal to 9³/” x 9³/” (40 x 40mm).
4. Proceed to plumb for additional openings through the roof. In all cases, the opening must provide a minimum of 1 inch clearance to the vent pipe, i.e., the hole must be at least 9³/” x 9³/” (40 x 40 mm).
5. Place fireplace into position.
6. Place firestop(s) #7DVFS or Attic Insulation Shield #7DVAIS into position and secure. (Fig. 37)
7. Install roof support (Fig. 38 & 39) and roof flashing making sure upper flange is below the shingles. (Fig. 38)
8. Install appropriate pipe sections until the venting is above the flashing. (Fig. 38)
9. Install storm collar and seal around the pipe.
10. Add additional vent lengths for proper height. (Fig 40)
11. Install vertical vent termination.

Nails (4)

CFM100

Fig. 37 Place firestop spacer(s) and secure.

If there is room above ceiling level, firestop spacer must be installed on both the bottom and the top side of the ceiling joists. If an attic is above ceiling level a 7DVAIS (Attic Insulation Shield) must be installed. (Fig. 37)

The enlarged ends of the vent section always face downward. (Fig. 38)

3 #5 Sheet Metal Screws per Joint
Sealant Storm Collar

Fig. 38 Roof flashing.

TWL101a

10007317

1

LDVR Series Direct Vent Gas Fireplace

Roof

‘ Min.

Roof Support

Attic Insulation

40′

Shield

(1 m) Attic

Insulation

Joists

Vent Termination
Storm Collar Roof Flashing
Joists

Min. 2′ (610 mm)

Fig. 40 Minimum termination to roof clearance.

FP1185

Fig. 39 Typical straight-up installation.

FP10

10007317

10007317

LDVR Series Direct Vent Gas Fireplace
Venting Components
7TDVRVT – Through the wall Rear Vent Termination

Starter Kit Model 7TDVSK – Sidewall Venting (Twist Lock Pipe) Model 7FDVSK – Sidewall Venting (Flex Vent Pipe) Models 7TDVTK/TV – Hot Touch Termination Kits Model 7TDVTVTK/TV – Cool Touch Termination Kit
Starter Kit – Model 7TDVSKV – Vertical Venting for 7TDVSKV-A order 1/1 to 6/1 roof pitch for 7TDVSKV-B order 7/1 to 1/1 roof pitch for 7TDVSKV-F order flat roof
Starter Kit for Below Grade Installation Model 7TDVSKS -Snorkel Kit (Twist Lock Pipe) Model 7FDVSKS -Snorkel Kit (Flex Vent Pipe)
Starter Pipe Model 7TDVP 0/8 – 4″ Starter Pipe Bulk Model 7FDVP 30/8 – 30″ Flex Pipe Bulk

45o Elbow 7TDV45 for Rear Vent to Vertical Vent or Vertical/Horizontal Offsets

90o Transition Elbow 7TDVRT90 for Rear Vent to Vertical Vent
90° Elbow 7TDV90 Vertical/Horizontal Offset
Telescopic vent sections 7TDVP1117 -11″ to 17″ adjustable length 7TDVP3567 -35″ to 67″ adjustable length

Pipe sections for vertical or horizontal venting

Model 7TDVP8″ –

4 per box

Model 7TDVP1″ –

4 per box

Model 7TDVP4″ –

4 per box

Model 7TDVP36″

Model 7TDVP48″

Firestop Spacer Model 7DVFS

Attic Insulation Shield Model 7DVAIS

Vertical/Horizontal Combination Offset Support Model 7DVCS
3

LDVR Series Direct Vent Gas Fireplace

Operating Instructions

Glass Information
Only glass approved by Vermont Castings Group should be used on this fireplace.

6. Tilt the window frame assembly out slightly at the bottom, lift the window frame assembly up and away from the fireplace.
7. To replace the window frame assembly reverse the procedure.

· The use of any non-approved replacement glass will
void all product warranties.
· Care must be taken to avoid breakage of the glass.
· Do not operate appliance with glass front removed,
cracked or broken.
· Replacement glass (complete with frame window)
is available through your Vermont Castings Group dealer and should only be installed by a licensed qualified service person.

Lower Clamps

Louvre Removal

The top louvre panel is

removed by lifting the

panel vertically and pulling

it away from the appliance.

(Fig. 41) The lower access

door is hinged along the

bottom edge and is folded

down to allow access.

Louvre

Glass Panel FP17
Fig. 41 Remove top louvre assembly.
Window Frame Assembly Removal
1. Turn the fireplace OFF (including the pilot) . If the unit has been operating allow time for the
components to cool. 3. Remove the top louvre assembly. 4. Open the lower louvre panel. 5. Release the two clamps securing the lower edge of the
window frame assembly by pulling down on the handles. (Fig. 4)

Window Frame Assembly

Window Frame Assembly

Pull Clamp

Push Hook

Clamp

Handle

FP18

Fig. 42 Window frame assembly removal.

Glass Cleaning
It is necessary to periodically clean glass. During startup condensation, which is normal, forms on the inside of the glass. This condensation causes lint, dust and other airborne particles to cling to glass surface.
Also initial paint curing may deposit a slight film on the glass. It is therefore recommended the glass be cleaned two or three times with a non- ammonia based household cleaner and warm water (We recommend gas fireplace glass cleaner) within the first few weeks of operation.
After the initial cleaning process the glass should be cleaned two or three times during each operating season depending on the environment in the house.

Clean glass after first two weeks of operation.
Do not clean glass when hot.
Do not use abrasive cleaners.
Do not strike or slam the glass.

4

10007317

LDVR Series Direct Vent Gas Fireplace

Installation of Logs, Lava Rock & Ember Material

The logs are fragile and should be handled with care. Keep the packaging material out of the reach of children and dispose of the material in a safe manner.

The individual logs can be easily identified by the numbers cast on the underside of each log.

Log Identification Chart

Location Front Left Front Right Front Center
Rear Rear Left Rear Right Top Center

33LDVR A43 —A41 A4 A44

36LDVR B160 B159 B161 B158 —-

39LDVR BC15 BC16 B138 BC14 —-

43LDVR BD16 BD17 B138 BD15 –BD18

Log Installation
1. Remove the top louvre assembly. . Open the bottom louvre. 3. Remove the window frame assembly. 4. Remove log box from inside firebox. 5. Unpack the logs from packaging and remove each log
from its wrapping material. Set aside the ember and the lava rock bags.
As with all plastic bags – these are not toys and should be kept away from children and infants.

33LDVR
1. Place rear log left (A41) on rear bracket (ensure the notch on the left end locates against the bend up on the left side of rear bracket.)
. Place rear log right (A4) on rear bracket (ensure the notch on the right end locates against the bend up on the right side of rear bracket) and just rest the cut out from front log onto the front support.
3. Place front log left (A43). Use the log’s bottom hole to locate it onto rear log left (A41) and just rest bottom cut out log onto the front support.
4. Place top log center (A44). Use the log’s bottom hole to locate it onto the knob on the rear log right (A4) and the top log center rest onto rear log left.
5. Place ember material on top of burner. Scatter the ember material over the tiles on the front area of the burner housing. (Fig. 50) Do not pack the ember material. Separate it when unpacked and keep it in a fluffy and loose condition for a more realistic ember effect.
6. Scatter the lava rock material around the firebox base.
Do not place any of the lava rock material on the burner housing assembly.

Figure 43 33LDVR

Rear Left (A41)

Top Center (A44)

Rear Right (A4)

10007317

Front Left (A43)

LG38
5

LDVR Series Direct Vent Gas Fireplace

36LDVR

1. Place rear log (B158) on rear bracket (ensure log is

seated properly to the bracket and located to the two

pins), so it will not move from side to side and is firmly positioned on the bracket.

Figure 44 36LDVR

. Place front left log (B160). Use the log’s bottom

hole to locate it onto the front support and just rest

on top of the rear log.

3. Place front right log (B159). Use the log’s bottom hole to locate it onto the front support and the top hole to the knob onto the rear log.

4. Place front center log (B161) on top of the two small shelves at the front log support and between the left and right logs.

5. Place ember material on top of burner. Scatter the ember material over the tiles on the front area of the burner housing. (Fig. 50) Do not pack the ember material. Separate it when unpacked and keep it in a fluffy and loose condition for a more realistic ember effect.

6. Scatter the lava rock material around

the firebox base.

LG481

Front Left (B160)

Do not place any of the lava rock material on the burner housing assembly.

Rear (B158)
Front Center (B161 )

Front Right (B159)

39LDVR

1. Place rear log (BC14) on rear bracket (ensure log is

centered and seated properly to the log sup-

port).

.

Place

front

left

log

(BC15).

Use

log’s

bottom

Front Left (BC15)

hole to locate it onto the front support and just

rest on top of the rear log.

3. Place front right log (BC16). Use log’s bottom hole to locate it onto the front support and the top hole to the knob on the rear log.

4. Place front center log (B138) on top of the two small shelves at the front log support, and between the left and right logs.

5. Place ember material on top of burner. Scatter the ember material over the tiles on the front area of the burner housing. (Fig. 50) Separate it when unpacked and keep it in a fluffy and loose condition for a more realistic ember effect.

Do not place any of the lava rock material on the burner housing assembly.

Figure 45 39LDVR

Front Right (BC16)
Rear (BC14)

Front Center (B138)

LG414

6

10007317

LDVR Series Direct Vent Gas Fireplace

43LDVR

1. Place rear log (BD15) on rear bracket (ensure log is centered and seated properly to the log support).

. Place front left log (BD16). Use log’s bottom notch to

locate it onto the front support and just rest on top of the burner housing tile.

Rear (BD15)

3. Place front right log (BD17). Use log’s bottom

notch to locate it onto the front support and

just rest on top of the burner housing.

Front

4. Place ember material on top of burner.

Left (BD16)

5. Scatter the ember material over the tiles on

the front area of the burner housing. (Fig. 46)

Do not pack the ember material. Separate it

when unpacked and keep it in a fluffy and

loose condition for a more realistic ember ef-

fect.

Figure 46 43LDVR
Top Center (BBD18)

Front Right (BD17)

6. Place front center log (B138) on top of the two small shelves at the front log support, and between the left and right logs.
7. Place top center log (BD18) on top of the rear log using the hole locator under the log and on top of front right log.
8. Scatter lava rock material round the firebox base.

Lava Rock

Front Center (B138)

Lava Rock

LG434

Ember Material

Do not place any of the lava rock material on the burner housing assembly.

Flame Characteristics

Flame & Temperature Adjustment
RN/RP & EN/EP Models

It is important to periodically perform a visual check of the
pilot and burner flames. Compare them to the illustrations. (Figs. 48 & 49)

For units equipped with “HI/LO” valves the flame adjustment is accomplished by rotating the “HI/LO” adjustment knob located near the center of the gas control valve. (Fig. 47)

If the flame patterns appear abnormal contact a qualified service provider for service and adjustment.

SIT 820 Valve
Turn counterclockwise
to increase flame height

LO

H I

Turn clockwise to decrease flame height

SIT RN/RP

Fig. 47 Flame adjustment knob for SIT valve.

SIT EN/EP, IN/IP

10007317

Fig. 48 Correct pilot flame appearance.

FP1541
7

LDVR Series Direct Vent Gas Fireplace

LG384
LG415
Figure 49 8

33LDVR

Glowing Embers
36LDVR

LG48 Glowing Embers

39LDVR

Glowing Embers
43LDVR
LG435

Glowing Embers
10007317

LDVR Series Direct Vent Gas Fireplace

Lighting and Operating Instructions
For Fireplaces Equipped with the SIT820 Valve
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING:If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

A. This heater has a pilot which must be lit manually. When lighting the pilot follow these instructions exactly.
B. BEFORE LIGHTING smell all around the heater area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
· Do not try to light any fireplace · Do not touch any electric switch · Do not use any phone in your building · Immediately call your gas supplier from a
neighbor’s phone.

Follow the gas supplier’s instructions.
· If you cannot reach your gas supplier, call the Fire
Department C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or turn by hand, do not try to repair it, call a qualified service technician. Applying force or any attempted repair may result in a fire or explosion. D. Do not use this fireplace if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.

Lighting Instructions

1. STOP! Read the safety information above. . Turn off all electrical power to the fireplace. 3. Turn the ON/OFF switch to “OFF” position. 4. Open control access panel. 5. Push in gas control knob slightly and turn clockwise
to “OFF”.

PILOT

*”/

10. Push the control knob all the way in and hold. Immediately light the pilot by repeatedly depressing the piezo spark ignitor until a flame appears. Continue to hold the control knob in for about one (1) minute after the pilot is lit. Release knob and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through 8.
3/8″ – 1/2″

OFF

OFF

SIT NOVA Honeywell

6. Wait five (5) minutes to clear out any gas. Then smell

for gas, including near the floor. If you smell gas,

STOP! Follow “B” in the safety information above. If

you do not smell gas, go to the next step.

7. Remove glass door before lighting pilot. (See Glass

Frame Removal section).

8. Visibly locate pilot by the main burner.

9. Turn knob on gas control counterclockwise

to

“PILOT”.

· If knob does not pop up when released, stop and
immediately call your service technician or gas supplier.
· If after several tries, the pilot will not stay lit, turn
the gas control knob to “OFF” and call your service technician or gas supplier.
11. Replace glass door.
1. Turn gas control knob to “ON” position.
13. Turn the ON/OFF switch to “ON” position or set thermostat to desired setting.
14. Turn on all electrical power to the fireplace.

To Turn Off Gas To Heater

1. Turn the ON/OFF switch to Off position. . Turn off all electric power to the fireplace if service
is to be performed. 3. Open control access panel.

4. Push in gas control knob slightly and turn clockwise to “OFF”. Do not force.
5. Close control access panel.

10007317

9

LDVR Series Direct Vent Gas Fireplace

Lighting and Operating Instructions
For Fireplaces equipped with SIT822 Gas Valve (EN or EP) WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury and loss of life.

FOR YOUR SAFETY READ THE FOLLOWING WARNINGS BEFORE LIGHTING THE APPLIANCE

A. This fireplace is equipped with an ignition device which automatically lights the pilot. DO NOT try to light the pilot by hand.
B. BEFORE OPERATING, smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than the air and will settle on the floor. What to do if you smell gas
· Do not try to light any appliance · Do not operate any electrical switch. · Do not use any phone in your building. · Immediately call your gas supplier from a
neighbor’s phone.

Follow the gas suppliers instructions.
· If you cannot contact your gas supplier call the
Fire Department C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or turn by hand do not try to repair it, call a qualified service technician. Force or attempting repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and replace any part of the control system and any gas control that has been under water.

Lighting Instructions

1. STOP! Read the safety information above before continuing.
. Turn off all electrical power to the appliance.
3. This appliance is equipped with an ignition device which automatically lights the pilot. DO NOT try to light the pilot by hand.
4. Access the gas control by lowering the lower access door (louvre assembly).

5. Turn the remote switch, if used, OFF. Turn the wireless remote, if used, OFF.

6. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas STOP. Follow instructions B in the safety warnings above. If you do not smell gas go onto the next step.

7. Close the access door.

8. Turn ON all electrical power to the appliance.

9. Turn remote switch or wireless remote to “ON”.

10. If the appliance will not operate, follow the instructions

TURNING OFF THE GAS TO THE APPLIANCEand

call your service technician or

gas supplier.

LO

HI

Turning Off the Gas to the Appliance

1. Turn the remote switch to the “OFF” position. . Turn OFF all electrical power to the fireplace if
service is required. 3 Open the lower access panel. 4. Turn the shut-off valve on the flexible gas line to
the “OFF” position.

1/” Gas Supply

1/” NPT x 1/” Flare Shut-Off Valve
3/8″ Flex Line (From Valve)

Valve in the on position

FP97A

30

10007317

LDVR Series Direct Vent Gas Fireplace

Lighting & Operating Instructions

For Fireplaces equipped with AF4000 Gas Valve

WARNING
If you do not follow these instructions exactly, a fire or explosion may result, causing property damage, personal injury and loss of life.

For Your Safety, Read the Following Warnings before Lighting the Appliance

A. This fireplace is equipped with an ignition device which automatically lights the pilot. DO NOT try to light the pilot by hand.
B. BEFORE OPERATING, smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than the air and will settle on the floor.
What to do if you smell gas
· Do not try to light any appliance. · Do not operate any electrical switch.

· Do not use any phone in your building. · Immediately call your gas supplier from a neighbor’s
phone. Follow the gas suppliers instructions.
· If you cannot contact your gas supplier call the
Fire Department C. Do not use this appliance if any part has been under
water. Immediately call a qualified service technician to inspect the appliance and replace any part of the control system and any gas control that has been under water.

Lighting Instructions

1. STOP! Read the safety information above before

continuing. . This appliance is equipped with an ignition device

Spark to Pilot Pilot Assembly

which automatically lights the pilot. DO NOT try to light the pilot by hand.
3. Turn the remote switch, if used, OFF. Turn the

“S” Connection Connect to Module

wireless remote, if used, OFF.

Pilot Adjustment

4. Wait five (5) minutes to clear out any gas. Then Screw

smell for gas, including near the floor. If you smell gas, STOP. Follow instruction B in the

Inlet Pressure Tap

Main Valve Internal Solenoid Connection Green & White Wires

safety warnings above. If you do not smell

Pilot Gas Connection Side or Back

gas, go on to the next step.

“I” Connection Connect to Module

5. Turn on electrical power to the appliance.
6. Turn remote switch or wireless remote to ON.

Flame Control Knob

7. If the appliance will not operate, follow the instructions TURNING OFF THE GAS TO THE APPLIANCE, and call your service technician or gas supplier.

Minimum Rate Screw

Outlet

Black Plastic Cap

Pressure Tap

Pilot Internal Solenoid Connection Orange & White Wires

Turning Off the Gas to the Appliance

1. Turn the remote switch to the OFF position.
. Turn OFF all electrical power to the fireplace if service is required.
3. Open the lower access panel.
4. Turn the shut-off valve on the flexible gas line to the OFF position.

1/” Gas Supply

1/” NPT x 3/8″ Flare Shut-Off Valve
3/8″ Flex Line (From Valve)

Valve in the “ON” position

10007317

31

LDVR Series Direct Vent Gas Fireplace

Troubleshooting the Gas Control System

SIT NOVA 820 Millivolt Valve
NOTE: Before trouble shooting the gas control system, be sure external gas shut off is in the “On” position.

WARNING: Before doing any gas control service work, remove glass front.

SYMPTOM 1. Spark ignitor will not light

POSSIBLE CAUSES A. Defective or misaligned
electrode at pilot.

CORRECTIVE ACTION Using a match, light pilot. If pilot lights, turn off pilot and push the red button again. If pilot will not light – check gap at electrode and pilotshould be 1/8″ to have a strong spark.

B. Defective ignitor (Push button)

Push Piezo Ignitor Button. Check for spark at electrode and pilot. If no spark to pilot, and electrode wire is properly connected, replace ignitor.

. Pilot will not stay lit after carefully following lighting instructions.

A. Defective pilot generator Check pilot flame. Must impinge on thermo-

(thermocouple), remote wall couple/thermopile. Note: this pilot burner

switch

assembly utilizes both-a thermocouple and a ther-

mopile. The thermocouple operates the main valve

operation (On and Off). Clean and or adjust pilot for

maximum flame impingement on thermopile and

thermocouple.

B. Defective automatic valve

Turn valve knob to “Pilot”. Maintain flow to pilot; milivolt meter should read greater than 10 mV. If the reading is okay and the pilot does not stay on, replace the gas valve. Note: An interrupter block (not supplied) must be used to conduct this test.

3. Pilot burning, no gas to main burner

A. Wall switch or wires defective

Check wall switch and wires for proper connections Jumper wire accross terminals at wall switch, if burner comes on, replace defective wall switch. If okay, jumper wires across wall switch wires at valve, if burner comes on, wires are faulty or connections are bad.

B. Thermopile may not be generating sufficient millivoltage
C. Plugged burner orifice.

1. Be sure wire connections from thermopile at gas valve terminals are tight and thermopile is fully inserted into pilot bracket.
. One of the wall switch wires may be grounded. Remove wall switch wires from valve terminals if pilot now stays lit, trace wall switch wiring for ground. May be grounded to fireplace or gas supply.
3. Check thermopile with millivolt meter. Take reading at thermopile terminals of gas valve. Should read 50-300 millivolts (minimum 150) while holding valve knob depressed in pilot position and wall switch “Off”. Replace faulty thermopile if reading is below specified minimum.
Check burner orifices for debris and remove.

D. Defective automatic valve operator.

Turn valve knob to “On”, place wall switch to “On” millivolt meter should read greater than 100 mV. If the reading is okay and the burner does not come on, replace the gas valve.

4. Frequent pilot outage problem.

A. Pilot flame may be too low Clean and/or adjust pilot flame for maximum flame or blowing (high) causing the impingement on thermopile and thermocouple. pilot safety to drop out.

B. Possible blockage of the vent terminal.

Check the vent terminal for blockage (recycling the flue gases)

3

10007317

LDVR Series Direct Vent Gas Fireplace

Troubleshooting the Gas Control System

SIT 8 Valve with Synetek Electronic Control

Operating Diagram

Normal Operation

Abnormal Operation

ON/OFF Switch Closed? YES

Safe Start Check On?

NO

YES

0 Sec Purge

Ignition Trial: 30 sec Spark ON

Pilot Valve ON. Has Flame

NO

been Detected within 30 sec?

Spark Off. Main Valve ON. Pilot Flame Continuously Monitored

Pilot Flame Sense OK?

NO

ON/OFF Switch Opened? YES
Pilot and Main Valve OFF? YES

5 sec Inter-Trial Delay

LED: Steady Flash? Lockout: Flame detected out of sequence Reset by interrupting ON/OFF switch or power for 10 sec

LED: 5 Flashes? Reverse power cord polarity

LED: Flashes? Reset by interrupting ON/OFF switch for power for 10 sec

YES

Pilot, Valve OFF, Spark OFF Have three ignition trials been completed?

NO

LED: 3 Flashes? Lockout: Flame Loss Reset by interrupting ON/OFF switch or power for 10 sec

YES Main Valve OFF, Spark ON Has flame been detected within 30 sec?

NO

Have three pilot flame losses been detected?

YES

0 sec Post Purge?

Heating Cycle Complete LED: OFF

10007317

33

LDVR Series Direct Vent Gas Fireplace

Troubleshooting
American Flame Gas Control System
If erratic system behavior is observed that cannot be resolved by the methods outlined below, ensure that there is not a transmitter with batteries installed that may be interfering. If a transmitter is packed with batteries installed, its buttons may be depressed sending a constant signal which can interfere with the transmission of desired signals. A transmitter with new batteries can have a range of over 100′ (30.4 m). (Page 10, Fig. 10)

Fireplace will not light Pilot will not light/stay lit
Pilot flame is always on/ will not extinguish Main flame will not light

· Ensure the REMOTE/OFF switch on the side of the module (Fig. 50) is set to OFF.
· Make sure the leads from the AC power adapter are securely connected to the POWER terminals on the control module and 10V AC power is available. (Fig. 51)
· Make sure the remote wall switch is wired correctly.
· Verify the gas supply is turned on.
· Ensure the orange lead from the pilot assembly igniter is securely connected to the terminal labeled “I” and the white lead from the flame rectification sensor is securely connected to the terminal labeled “S” on the control module. (Fig. 50)
· Make sure the orange and white leads from the module are securely connected to the terminals labeled “PILOT” on the valve body. (Fig. 5)
· Ensure the black GROUND wire is securely connected to an appropriate metal portion of the valve or pilot assembly. A proper ground is essential to spark igniter operation.
· Make certain the pilot flame is in contact with the flame rectification sensor on the pilot assembly. This valve is equipped with a pilot flame adjustment screw. (Fig. 5) If the pilot flame is too small it will not contact the flame rectification sensor and will not complete the safety circuit.
· Check continuity of pilot coil on valve. Remove wire connector. If there is no continuity on pin terminals, replace valve.
· Ensure the CONTINUOUS PILOT switch on the control module (Fig. 50) is set to OFF.
· Verify the gas supply is turned on.
· Ensure the pilot flame will ignite. If not, see pilot flame troubleshooting above.
· Make sure the green and white leads from the module are securely connected to the terminals labeled “MAIN: on the valve body. (Fig. 5)
· Make certain the pilot flame is in contact with the flame rectification sensor on the pilot assembly. This valve is equipped with a pilot flame adjustment screw. (Fig. 5) If the pilot flame is too small it will not contact the flame rectification sensor and will not complete the safety circuit.
· Ensure the pilot flame is properly located to ignite the main flame.
· Check continuity of main burner coil in gas valve. Remove wire connector. If there is no continuity, replace valve.

34

10007317

LDVR Series Direct Vent Gas Fireplace Troubleshooting American Flame Gas Control System (continued)

Figure 50: AF4000 MOD Module Right Side

Continuous PIlot Off/On Switch

Remote/Off Switch

Adjustment

“S” Pilot Connection

“I” Pilot

FP176

Connection

Figure 51: AF4000 MOD Module End

6 Volt DC Adapter Power Connection

8CoPninneIPctIion

Figure 52: AF4000 Valve Face

Main Connection

Inlet

MAIN

Pilot Adj.

PILOT

Outlet

Pilot Connection

FP1764

FP1769

10007317

35

LDVR Series Direct Vent Gas Fireplace
American Flame Gas Control System Error Codes
Ignition Safety: Protection for Ignition System Error Code: One beep every one second Description of Fault: Warn users if the pilot is not successfully ignited in 60 seconds. How to Clear: Switch OFF then ON to re-attempt ignition. What to Check:
· Ensure gas supply is turned on. · Ensure orange/white leads from module are plugged into the “PILOT” connection on the valve body. · Verify the lead from igniter on pilot assembly is connected to the “I” terminal on the module. · Verify lead from flame sensor on pilot assembly is connected to the “S” terminal on the module. · Verify that the black ground lead form the module is connected to a proper ground on the fireplace. · Ensure there is no blockage in the pilot line.
Sensor Safety: Protection for Flame Sensor Error Code: 4 beeps every one second Description of Fault: Warn users the pilot flame sensor detects a pilot flame already present when ignition sequence is initiated. This fault will also occur if pilot flame sensor is shorted to ground. How to Clear: Switch OFF then ON to re-attempt normal ignition. What to Check:
· Check if pilot flame is actually present when valve is turned OFF (valve replacement necessary if yes). · Replace pilot assembly. · Replace module.
Thermal Safety: Overheat Protection Error Code: 4 beeps every two seconds. Description of Fault: Warn users that the module’s internal temperature has exceeded 170° F (77° C). How to Clear: Turn off fireplace. The module’s internal temperature must cool to below 160° F (71° C). Then switch to ON. What to Check:
· Is module located in unapproved location, too close to burner? · Move to cooler location.

36

10007317

LDVR Series Direct Vent Gas Fireplace

Fuel Conversion Instructions
The conversion of this appliance from one gas to another must be carried out by an authorized service provider.
The procedure for converting from one gas to another is the same regardless of the initial gas used. The only variation is in the orifice sizes and component part numbers. Your authorized service provider will ensure the correct parts are used.
1. Disconnect power to the unit and shut off the gas supply.
. Remove window frame assembly.
3. Carefully remove the logs & lava rock material.
4. Remove the screws holding the burner housing in place.
5. Remove the burner housing assembly. Depending on the model of the appliance you may have to loosen the pilot bracket retaining screw/nut to allow the pilot and bracket assembly to tilt and give enough clearance to remove the burner housing assembly.
6. For Model 36LDVR ONLY: Remove the rear log support and relocate the two () screws that locate the rear log as shown in Figure 53.

PSE Pilot Using a suitable wrench on the hexagonal body unscrew the pilot hood assembly from the pilot, do not twist the hood itself. Remove the orifice and replace it with the new orifice supplied in the kit. Refit the pilot hood assembly. Do not over-tighten the pilot hood. The hood must return to its original alignment. Take care not to damage the thermocouple, thermopile or igniter.
Valve Conversion
SIT 820 NOVA Gas Control Valve (Fig. 54)
1. Using a Torx T0 or slotted screwdriver, remove and save the three pressure regulator mounting screws (A), pressure regulator tower (B) and diaphram (C).
A
E
B

F PIL F PIL

C
OF

OT O

OF
D

OT O

Natural Gas

F

Log Locator Pin Propane Gas

Log Locator Pin

KT615

Fig. 53 Move log locator pins to new locations on rear log support.

7. Remove the main burner orifice and replace it with the orifice supplied in the conversion kit.
Pilot Orifice Conversion

SIT Top Convertible Gently lift off the pilot

Pilot hood

from

the

pilot.

(Do

not

remove

the spring clip holding the hood in place). Using a 5/3″ Al-

len key, unscrew the exposed orifice. Insert the new orifice

supplied in the kit, do not over tighten the orifice. Replace

the pilot hood ensuring the index tab aligns with the notch

on the hood.

FC107/108
Fig. 54 Nova SIT80 Gas Valve.
. Ensure the rubber gasket (D) is properly positioned and install the new HI/LO pressure regulator to the valve using the new screws (E) supplied with the kit. Tighten screws securely. (Reference torque – 5 in.LB)
3. Install the enclosed identification label (F) to the valve body where it can be easily seen.
AF4000 Gas Control Valve The AF4000 electronic control valve is convertible from natural gas to propane gas by changing the minimum rate screw in the valve and by rotating a plastic knob located under a black cap on the top face of the valve.
1. Remove the black cap by pulling the cap straight off. Note the position of the marker on the top of the rotary knob. This marker will point to NAT or LP. (Fig. 55)
. To convert the valve from NG to LP, push in the knob and rotate 90° (1/4 turn). NOTE: The shaft should point to LP and the shaft will remain pushed in.
3. Remove the minimum rate screw, using a small screwdriver, located in the valve next to the motor drive. (Fig. 55)
4. Replace the minimum rate screw with the new minimum rate screw supplied in the conversion kit. Ensure the screw is fully installed. Replace plug.

10007317

37

LDVR Series Direct Vent Gas Fireplace

Main Connection
MAIN Inlet

Pilot Adj.

PILOT

Outlet

Gas Type Marker

Rubber Cap

Minimum (LP Position Shown)

FP1769a

Rate Screw

CO137

Fig. 55 Remove rubber cap and adjust gas type marker.

5. Turn on gas supply and check that plugs are tight and leak free.

6. Install the enclosed identification label to the valve body where it can easily be seen.

Conversion is complete.
1. Reassemble the fireplace in the revers e orde r, except
for the window frame assembly. Leave this off until after
the unit has been checked for leaks and the gas supply
has been bled.

. After bleeding the gas line and checking for leaks with a soap solution, replace the window frame assembly. Fire up the unit, check for flame impingement on the logs, adjusting them if necessary. Check the manifold and supply pressures against the appliance specifications.

38

10007317

LDVR Series Direct Vent Gas Fireplace

Maintenance

Burner and Burner Compartment
It is important to keep the burner and the burner compartment clean. At least once per year the logs and lava rock/ember material should be removed and the burner compartment vacuumed and wiped out. Remove and refit the logs as per the instructions in this manual.
Always handle the logs with care as they are fragile and may also be hot if the fireplace has been in use.
FK24/FK12 Fan Assembly
The fan unit requires periodic cleaning. At least once per month in the operating season open the lower louvre panels and wipe or vacuum the area around the fan to remove any build up of dust or lint.
Brass Trim

Most of these components may require only an occasional checkup and cleaning and some may require adjustment. If repair is necessary, it should be performed by a qualified technician.
1. Turn off pilot light at gas valve.
. Allow fireplace to cool if it has been operating.
3. Remove window frame assembly. (Refer to Window Frame Assembly Removal section.)
4. Remove logs.
5. Vacuum burner compartment especially around orifice primary air openings.
6. Visually inspect pilot. Brush or blow away any dust or lint accumulation.
7. Reinstall logs.
8. Ignite pilot – Refer to Lighting Instructions.
9. Reinstall window frame assembly.

Clean the brass trim pieces using a soft cloth lightly dampened with lemon oil. Do not use water or household cleaners on any brass components.

To obtain proper operation, it is imperative that the pilot and burner’s flame characteristics are steady, not lifting or floating.

Cleaning the Standing Pilot Control System

The burner and control system consist of:

· burner

· gas orifice

· pilot assembly · thermopile

· millivolt gas valve

Typically, the top 3/8″ to 1/” of the thermopile should be engulfed in the pilot flame. (Refer to Page 7, Figure 48)
To adjust pilot burner: (by qualified service technician)
1. Remove pilot adjustment cap . Adjust pilot screw to provide properly sized flame. 3. Replace pilot adjustment cap.
The primary air shutter is set at factory and should only be adjusted, if necessary, by a qualified service technician.

10007317

39

LDVR Series Direct Vent Gas Fireplace

1 1e 1a 1h
17 21
22 34
42

33LDVR
1g 1i

1 1d
1f 1a

36LDVR

1

39LDVR

1d

1b 1a
1c 2
3

1b 1c
12 6a,b

43LDVR 1d

1g 1a
1c
14 11 7a,b

1b
9 16

18a,b

19a,b

15 13

LO

HI

23

24

8 26
20
29
30

31 25 33
45

35 37

32 46
44

39 40 43

48 47

ON H/L

OFF/CONTINUOUS

PILOT BUTTON

41

Vermont Castings Group reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time, without notice.
33/36/39/43LDVR

40

10007317

LDVR Series Direct Vent Gas Fireplace

LDVR (continued)

Ref. Description 1. Log Set (complete)
1a. Front Left Log 1b. Front Right Log 1c. Front Center Log 1d. Rear Log 1e. Rear Left Log 1f. Rear Right Log 1g. Top Center Log 1h. Lava Rock Package 1i. Ember (Package) a. Burner Housing Assy – Natural b. Burner Housing Assy – LP
3. Ceramic Tile (Single) 4a. Orifice Burner – Natural 4b. Orifice Burner – Propane 5a. Orifice Pilot – Natural 5b. Orifice Pilot – Propane 6a. Pilot Assy SIT – RN 6b. PIlot Assy SIT – RP 7a. PIlot Assy SIT – EN 7b. Pilot Assy SIT – EP
8. Pilot Tubing w/Fittings SIT 9. Pilot Hood 10. Manifold Tubing w/Fittings 11. Thermocouple – RN/RP 1. Thermopile – RN/RP 13. Electrode Ignitor w/Cable – RN/RP 14. Electrode Ignitor – EN/EP 15. Cable Ignitor – EN/EP 16. Sensing Electrode – EN/EP 17. Ignitor Piezo SIT80 Valve 18a. Valve SIT 80 – RN 18b. Valve SIT 80 – RP 19a. Valve SIT 8 – EN 19b. Valve SIT 8 – EP 0. Flexible Gas Line w/ON/OFF Shut-Off Valve 1. Fan Assy w/Bracket (FK4 Option) . Fan Assy (FK1 Option) 3. Electrical Cord (6ft) 4. Fan Temperature Sensor (FK4) 5. Speed Control (FK4) 6. Speed Control Knob (FK4) 9. Frame Window w/Glass 30. Clamp Frame Window 31. Top Louvre Assy 3. Bottom Louvre Assy 33a. Support Rear Log 33b. Support Rear Log – LP 10007317

33LDVR

36LDVR

39LDVR

10007567

10010113

1000814

A43

B160

BC15

B159

BC16

B161

B138

B158

BC14

A41

A4

A44

10001454

10001454

10001454

51915

51915

51915

10007558

1000717

1000818

10007558

1000804

10008586

57803

57803

57803

Refer to Rating Plate for Orifice Size

Refer to Rating Plate for Orifice Size

100068

100068

100068

100069

100069

100069

100064

100064

100064

100065

100065

100065

1000387

1000387

1000387

1000388

1000388

1000388

1000196

1000196

1000196

1000385

1000385

1000385

57318

57318

57318

53373

53373

53373

5187

5187

5187

1000197

1000197

1000197

5465

5465

5465

10000696

10000696

10000696

57885

57885

57885

5464

5464

5464

5677

5677

5677

5678

5678

5678

57884

57884

57884

57883

57883

57883

000500

000500

000500

ZA1100

ZA1100

ZA1100

ZA1110

ZA1110

ZA1110

51865

51865

51865

51704

51704

51704

51738

51738

51738

5188

5188

5188

10009693

10009694

10009695

54174

54174

54174

10007400

10007090

10007984

10007397

1000709

10007986

10007561

1000716

1000811

10007561

10008045

1000811

43LDVR 10008314
BD16 BD17 B138 BD15
–BD18 10001454 51915 10008464 10008587 57803
100068 100069 100064 100065 1000387 1000388 1000196 1000385
57318 53373 5187 1000197 5465 10000696 57885 5464 5677 5678 57884 57883 000500 ZA1100 ZA1110 51865 51704 51738 5188 10008535 54174 10008311 10008307 10008480 10008480
41

LDVR Series Direct Vent Gas Fireplace

LDVR (continued)

Ref. Description

33LDVR

34. Support Front Log

1000756

35. ON/OFF Switch

5184

37. Relief Plate Assy (Burner Base)

1000419

38. Remote Switch Kit (Not shown)

53875

39. Ignition Control from Synetek (EN)

10007939

40. Wire Harness (EN) Synetek (low voltage) 10008139

41. Wire Harness (EN) Synetek (high voltage) 10008140

4. Clevis Pin

10008615

43. Clip Pin Hitch

10008616

44. Main Module (IN)

0011895

45. AC Adaptor (IN)

0011900

46. 4″ Wire Harness (IN)

00158

47. Remote Control (IN)

0011904

48. American Flame Valve AF-4010-IN Assy 0013151

36LDVR 1000711
5184 1000419
53875 10007939 10008139 10008140 10008615 10008616 0011895 0011900 00158 0011904 0013151

39LDVR 10008416
5184 1000419
53875 10007939 10008139 10008140 10008615 10008616 0011895 0011900 00158 0011904 0013151

43LDVR 10008469
5184 1000419
53875 10007939 10008139 10008140 10008615 10008616
n/a n/a n/a n/a n/a

Fuel Conversion Kits Conversion Kit, NG to LP
33LDVRRN/EN 33LDVRIN 36LDVRRN/EN 36LDVRIN 39LDVRRN/EN 39LDVRIN 43LDVRRN/EN Conversion Kit, LP to NG 33LDVRRP/EP 33LDVRIP 36LDVRRP/EP 36LDVRIP 39LDVRRP/EP 39LDVRIP 43LDVRRP/EP

Kit # 1000833 Kit # 001431 Kit # 1000835 Kit # 0014313 Kit # 1000837 Kit # 0014314 Kit # 1000839
Kit # 1000834 Kit # 0014315 Kit # 1000836 Kit # 0014316 Kit # 1000838 Kit # 0014317 Kit # 1000840

4

10007317

LDVR Series Direct Vent Gas Fireplace

Optional Accessories Available

Fan Kits
FK24 Fan Assembly
This auxiliary fan system increases the efficiency of the circulation of the heated air.
The FK4 fan kit allows variable speed control of the circulation fan and also incorporates a heat sensor in the circuit.
Specifications
115 Volt / 60Hz / 56 Watts
Maintenance
The fan itself does not require regular maintenance, however periodic cleaning of the fan and the surrounding area is required.
Check the area under the control door (lower louvre assembly) and in front of the fan and wipe or vacuum this area at least once a month during the operating season.
Installation
The fan assembly and other components are supplied fully wired, eliminating the need for a licensed electrician to carry out the installation.
If hard wiring the fan using Method B (following) we strongly recommend the use of a licensed electrician.
1. Open the lower louvre assembly. Move the fan & bracket assembly around the gas valve and lines to locate the unit onto the screw studs on the back of the fireplace.
. Install the thermal sensor under the bottom of the of the firebox, locating it over the two 10mm studs and secure it with nuts.
3. Locate the fan speed control unit. This can be fitted behind the lower louvre assembly as in Figure 56 or located remotely in a conveniently located wall mounted electrical box. Remote location of the speed control will require suitable extension of the component wiring.
4. The power supply may be connected in two ways:
Method A Route the 6′ lead fitted to the unit to a conveniently located wall socket.
Method B (Using EB-1 Receptacle Box) The EB-1 receptacle box (Pt. # ZA100) may be hard wired into the house supply. The fan lead is then plugged into the EB-1 box. For instruction on wiring the EB-1 receptacle box see the earlier chapter in the Installation section of this manual.

Thermal

Sensor

Fan

Valve

Fan Speed FP130 Switch

Gas Lines

Fig. 56 FK4 fan placement.

EB-1 Receptacle Box

FK12

This auxiliary fan system increases the efficiency of the circulation of the heating air.

The FK1 Fan Assembly is a fixed speed fan system and does not allow for variable speed control. It does not use the speed control unit or the heat sensor used in the FK4 Kit.

Specifications

115 Volts / 60 Hz / 56 Watts.

Maintenance

The fan itself does not require regular maintenance, however periodic cleaning of the fan and the surrounding area is required.

Check the area under the control door (lower louvre assembly) and in front of the fan and wipe or vacuum this area at least once a month during the operating season.

Installation

The fan assembly is supplied fully wired eliminating the need for a licensed electrician to carry out the installation.

1. Open the lower Louvre assembly. Move the fan & bracket

assembly around the gas valve and lines to locate the

unit against the back wall of the

appliance, resting

on the base.

. With the protective cover removed from the self-adhesive `Velcro’ strips apply mild pressure to the fan & bracket unit to secure the strips to the metal panels. No further securing is required.

3. Power to the fan can be supplied by plugging the supplied lead into a conveniently located wall socket or by using a hard-wired EB-1 receptacle box.

10007317

43

LDVR Series Direct Vent Gas Fireplace

Wiring Instructions
The fireplace, when installed, must be electrically connected and grounded in accordance with local codes or, in the absence of local codes, with the current CSA C22.1 Canadian Electric Code.
For USA installations follow the local codes and the national electrical code ANSI/NFPA No. 70.
Should this fan require servicing or repair the power supply must be disconnected. For rewiring of any replacement parts refer to Figure 57.
Any electrical rewiring of this fan must be done by a licensed electrician.

Speed Control
Black White Ground

Fan Temperature Sensor
FP105

Fig. 57 FK4 fan wiring.

Ceramic Refractory Panels

Ceramic refractory panels are available in kit form for the LDV series appliances

Kit Model and Finish

Unit 33LDVR 36LDVR 39LDVR 43LDVR

Sandstone Red 33LDVRCR GAHC3J0 GAFC3J0 39LDVCR 43LDVCR

Black

Grey

GABC3J0 GAGC3J0

Take care when handling the refractory panels as they are fragile until held in place and supported.
Installation Refer to Figures 58 & 59
1. Remove the front window frame assembly. . Remove the logs. 3. Place the rear refractory panel in place. Locate the lower
edge of the panel in the ledge formed by the top of the rear log support bracket.
4. Slide the side refractory panels into place to hold the rear panel secure. Repeat the procedure on the other side.
5. Replace the logs and window frame assembly.
For aesthetic purposes we recommend aligning the horizontal mortar lines.

44

Side Panel

Back Panel
Log Support Burner Tray

Side Panel

FP131
Fig. 58 Ceramic panel installation. Rear Refractory Panel
Rear Panel Support Brackets

Firebox Back Panel

Rear Log Support Fig. 59 Rear refractory panel installation.

FP13

Remote Controls

Optional remote control units are available to control different

functions of the appliances

Model

Function/s Controlled

RCI

ON/OFF

RC

ON/OFF and Temperature

IMTFK

Wall mounted thermostat control

(must be used in bedroom installations)

10007317

Optional Trim Kits

Louvre Accent Trim

Appliance Model Polished Brass
36LDVR 39LDVR Rustic Bronze 33LDVR 36LDVR Pewter 33LDVR 36LDVR 39LDVR 43LDVR

Main Louvre Kit
36DVLMP 39DVLMP
33DVLMR 36DVLMR
33DVLMS 36DVLMS 39DVLMS 43DVLMS

Regular Trim Kit
Appliance Model 33LDVR
33LDVR

Trim Kit 33DVRRKS
33DVRTKR

Adjustable Regular Trim Kit

Appliance Model

Trim Kit

36LDVR

ADVRRKS

36LDVR

ADVRTKR

39LDVR

ADVRRKS

39LDVR

ADVRTKR

Medium Trim Kit
Appliance Model 33LDVR
33LDVR

Trim Kit 33DVMTKS
33DVMTKB

Adjustable Medium Trim Kit

Appliance Model

Trim Kit

36LDVR

ADVMTKP

36LDVR

ADVMTKS

36LDVR

ADVMTKB

39LDVR

ADVMTKP

39LDVR

ADVMTKS

39LDVR

ADVMTKB

Additional Louvre
36DVLAP 39DVLAP
33DVLAR 36DVLAR
33DVLAS 36DVLAS 39DVLAS 43DVLAS
Pewter Rustic Bronze
Pewter Rustic Bronze
Pewter Rustic Bronze
Pewter Black
Polished Brass Pewter Black
Polished Brass Pewter Black

LDVR Series Direct Vent Gas Fireplace

Screen Door Kit

Appliance Model 33LDVR 36LDVR 33LDVR 36LDVR 39LDVR 36LDVR

Kit Model 33DVSDKS 36DVSDKS 33DVSDKB 36DVSDKB 39DVSDKB 36DVSDKR

Pewter Pewter Black Black Black Rustic Bronze

Filigree Louvre Kit

Appliance Model 33LDVR 36LDVR 36LDVR 36LDVR

Kit Model 33DVFKB 36DVFKB 36DVFKS 36DVFKR

Black Black Pewter Rustic Bronze

Arch/Square Face Kit

for the 36LDVR Romanesque – Arch 36DVARFKB 36DVARFKR 36DVARFKS Romanesque – Square 36DVSRFKB 36DVSRFKR 36DVSRFKS Marquette – Arch 36DVAMTKB 36DVAMTKR 36DVAMTKS Marquette – Square 36DVSMTKB 36DVSMTKR 36DVSMTKS

Black Rustic Bronze
Pewter
Black Rustic Bronze
Pewter
Black Rustic Bronze
Pewter
Black Rustic Bronze
Pewter

10007317

45

LDVR Series Direct Vent Gas Fireplace

46

10007317

LDVR Series Direct Vent Gas Fireplace
LIMITED LIFETIME WARRANTY
Lifetime Warranty
The following components are warranted for life to the original owner, subject to proof of purchase: Firebox, Combustion Chamber, Heat Exchanger, Grate and Stainless Steel Burners.
Five Year Warranty
The following components are warranted for five (5) years to the original owner, subject to proof of purchase: Ceramic Fiber Logs.
Basic Warranty
Vermont Castings Group warrants the components and materials in your gas appliance to be free from manufacturing and material defects for a period of two () years from date of installation. After installation, if any of the components manufactured by Vermont Castings Group in the appliance are found to be defective in materials or workmanship, Vermont Castings Group will, at its option, replace or repair the defective components at no charge to the original owner. Vermont Castings Group will also pay for reasonable labor costs incurred in replacing or repairing such components for a period of two () years from date of installation. Any products presented for warranty repair must be accompanied by a dated proof of purchase.
This Limited Lifetime Warranty will be void if the appliance is not installed by a qualified installer in accordance with the installation instructions. The Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance, and does not extend to (1) firebox/burner assembly damage by accident, neglect, misuse, abuse, alterations, negligence of others, including the installation thereof by unqualified installer, () the costs of removal, reinstallation or transportation of defective parts on the appliance, or (3) incidental or consequential damage. All service work must be performed by an authorized service representative.
This warranty is expressly in lieu of other warranties, express or implied, including the warranty of merchantability of fitness for purpose and of all other obligations or liabilities. Vermont Castings Group does not assume for it any other obligations or liabilities in connection with sale or use of the appliance. In states that do not allow limitations on how long an implied warranty lasts, or do not allow exclusion of indirect damage, those limitations of exclusions may not apply to you. You may also have additional rights not covered in the Limited Lifetime Warranty.
Vermont Castings Group reserves the right to investigate any and all claims against the Limited Lifetime Warranty and decide upon method of settlement.
For information about this warranty, contact:
Technical Services Vermont Castings Group 149 Cleveland Drive Paris. KY 40361

10007317

47

Model
33LDVRRN 33LDVRRP 33LDVREN 33LDVREP 33LDVRIN 33LDVRIP 36LDVRRN 36LDVRRP 36LDVREN 36LDVREP 36LDVRIN 36LDVRIP 39LDVRRN 39LDVRRP 39LDVREN 39LDVREP 39LDVRIN 39LDVRIP 43LDVRRN 43LDVRRP 43LDVREN 43LDVREP

Efficiency Ratings

EnerGuide Ratings Fireplace Efficiency (%)
6.6 6.6 7.7 7.7 7.7 7.7 57.5 57.5 63.6 63.6 63.6 63.6 50. 50. 54. 54. 54. 54. 54.3 54.3 58.3 58.3

Steady State (%)

Fan-OFF

Fan-ON

81

8

8

83

81

8

8

83

81

8

8

83

81

8

8

83

81

8

8

83

81

8

8

83

76

79

79

80

78

79

79

80

78

79

79

80

77

78

78

79

77

78

78

79

D.O.E. (AFUE%)
59 59 59 59 59 59 58 58 58 58 58 58 63 63 63 63 63 63 63 63 63 63

Vermont Castings Group
149 Cleveland Drive · Paris, Kentucky 40361 www.vermontcastingsgroup.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals