Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker Instruction Manual
- June 13, 2024
- Schneider Electric
Table of Contents
PowerPacT™ B 2P/3P/4P
BJL36030LU Power Pact Molded Case Circuit Breaker
Circuit Breakers and Automatic Switcheswww.se.com
DOCA0094EN / DOCA0095EN
http://www .schneider-electric.com/us/en/download/document/GDE55878
Scan the QR code on the product for additional product information.
For information about other products, see our website: https://www.se.com: /
www.se.comsupport >… /
chneider Electric Customer Support
Before starting the installation read and understand all instructions.
Retain instructions for future use.
PLEASE NOTE
- Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
- No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
- All pertinent state, regional, and local safety regulations must be observed when installing and using this product.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
- Apply appropriate personal protective equipment (PPE) and follow safe electricawork practices. See NFPA 70E, CSA Z462NOM 029-STPS or local equivalent.
- This equipment must only be installed and serviced by qualified electrical personnel.
- Turn off all power supplying this equipment before working on or inside equipment.
- Always use a properly rated voltage sensing device to confirm power is off.
- Replace all devices, doors, and covers before turning on power to this equipment
- Beware of potential hazards, and carefully inspect the work area for tools anobjects that may have been left inside theequipment.
Failure to follow these instructions willresult in death or serious injury.
WARNING: This product can expoyou to chemicals including DINP, whis known
to the State of California tcause cancer, and DIDP which is known to the State
of California to cause birth defects or other reproductive harm. For more
information go to:
www.P65Warnings.ca.gov.
Necessary Tools
Before Working on Equipment
- Turn off all power supplying this equipment before working on or inside equipment.
- Turn off or use push-to-trip button to trip circuit breaker.
- Use a properly rated voltage sensing device to confirm power is off.
Safety Clearances
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Install circuit breaker so minimum clearance distance to grounded metal is
maintained.
Failure to follow these instructions wilresult in death or serious injury.
3.1 Minimum Clearances
Standard (80% rated current)
A | B | C |
---|
14.6 in.
371 mm| 8.5 in.
216 mm| 3.16 in.
80 mm
100% rated current
| Painted sheet metal| Bare sheet metal
---|---|---
D| E| F| D| E| D
1| No accessories| 1.18 in.
30 mm| 0.19 in.
5 mm| 0
0| 1.57 in.
40 mm| 0.19 in.
5 mm| 0.19 in.
5mm
2| Interohase barrier:| 0
0| 0
0| 0
0| 0
0| 0
0| 0.19 in.
5mm
3| Long terminal shield
I| 0
0| 0
0| 0
0| 0
0| 0
0| 0.19 in.
5mm
3.2 Compression Lug Safety Clearance
If G < 0.37 in. (<
9.5 mm) : an insulating screen or long terminal shield is required.
3.3 Live Part Minimum Safety Clearances Required
Live parts.
V ≤ 600Y/347 V (UL) 690 V (IEC) | H ≤ 2.36 in. (60 mm) | H > 2.36 in. (60 mm) |
---|---|---|
I | J | I |
7.87 in.
200 mm| 3.94 in.
100 mm| 4.72 in.
120 mm| 2.36 in.
60 mm
Installation
4.2 DIN Rail
PLEASE NOTE
For DIN rail mounting, cable cross-sectional area should noexceed 1/0 AWG (50
mm²).
4.3 Door Cutout
Wiring
5.1 EverLink Lugs Connections
1| | | |
---|---|---|---|---
0.78 in.20 mm| Cu \ Al| 14-8 AWG| 2.5-10 mm²| 44 ± 4.4 lb-in.
<125 A \<100 A| 2.5-10 mm2| 5 ± 0.5 N•m
Cu \ Al| 6-3/0 AWG| 6-2/0 AWG| 80 ± 8 lb-in.
<125 A \<100 A| 16-95 mm²| 16-70 mm²| 9 ± 0.9 N•m
2| 0.47 in.12 mm| 20-10 AWG| 20-10 AWG| 9 ± 1 lb-in.
1.5-6 mm²| 0.5-6 mm²| 1 ± 0.1 N•m
5.2 Mechanical Lug Connections
NOTICE
HAZARD OF OVERHEATING
Do not allow wire strands to get caught in wire binding screw threads.
Failure to follow these instructions can result in equipment
damage.![Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker
- binding](https://manuals.plus/wp-content/uploads/2023/10/Schneider-Electric- BJL36030LU-Power-Pact-Molded-Case-Circuit-Breaker-binding.jpg)
| | | |
---|---|---|---|---
| 0.63 in.
16 mm| Cu/AI
15-125 A| 14-10 AWG
2.5-6 mm2| 35±3.5 lb-in.
4±0.4 N•m| 5/32 in.
4 mm
8-2/0 AWG
10-70 mm2| 50+5 lb-in.
5.6±0.6 N•m
| 0.63 in.
16 mm| Cu
15-125A| 14-10 AWG
2.5-6 mm2| 35±3.5 lb-in.
4±0.4 N•m| 5/32 in.
4 mm
8 AWG
10 mm2| 40±4 lb-in.
4.5±0.5 N•m
6-4 AWG
16-25 mm2| 45±4.5 lb-in.
5.1±0.5 N•m
3-1/0 AWG
35-50 mm2| 50±5 lb-in.
5.6±0.6 N•m
5.3 Compression Lugs/Busbar Connections
5.4 PowerPacT B DC Wiring Diagrams
| Grounded Negative| Grounded Middle Point| Ung rounded
Source
---|---|---|---
Type| | ![Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker
- Load](https://manuals.plus/wp-content/uploads/2023/10/Schneider-Electric-
BJL36030LU-Power-Pact-Molded-Case-Circuit-Breaker-Load.jpg)|
| 125 Vdc| 250 Vdc| ≤ 250 Vdc| ≤ 250 Vdc
1P| | |
2P| | |
3P| | |
4P| | |
Circuit Breaker Removal
- Turn off all power supplying this equipment before working on or inside equipment.
- Turn off or trip circuit breaker before removal. Make sure the circuit breaker is in the open (O) position or in the trip ( ) position.
- Use a properly rated voltage sensing device to confirm power is off.
- Remove circuit breaker in reverse order of installation.
© 2019-2022 Schneider Electric
All Rights Reserved
Schneider Electric, Square D, and PowerPacT are trademarks owned by Schneider
Electric Industries SAS or its affiliated companies. All other trademarks are
the property of their respective owners.
Schneider Electric Limited
Stafford Park 5
Telford TF3 3BL
United Kingdom
www.se.com/uk
Schneider Electric USA, Inc.
800 Federal Street
Andover, MA 01810 USA
888-778-2733
www.se.com/us/en/
GDE55878
References
- P65Warnings.ca.gov
- p65warnings.ca.gov/
- se.cn - This website is for sale! - se Resources and Information.
- Schneider Electric Canada | Global Specialist in Energy Management and Automation
- Schneider Electric Mexico | Servicios de Renovación y Retrofit de Schneider Electric
- Schneider Electric USA | Global Specialist in Energy Management and Automation
- Schneider Electric Global | Global Specialist in Energy Management and Automation
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>