Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker Instruction Manual

June 13, 2024
Schneider Electric

Schneider Electric LogoSchneider Electric Logo
1 PowerPacT™ B 2P/3P/4P

BJL36030LU Power Pact Molded Case Circuit Breaker

Circuit Breakers and Automatic Switcheswww.se.com
DOCA0094EN / DOCA0095EN

Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker - QR
Cordhttp://www .schneider-electric.com/us/en/download/document/GDE55878

Scan the QR code on the product for additional product information.
For information about other products, see our website: https://www.se.com: /
www.se.comsupport >… /
chneider Electric Customer Support
Before starting the installation read and understand all instructions.
Retain instructions for future use.
PLEASE NOTE

  • Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
  • No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
  • All pertinent state, regional, and local safety regulations must be observed when installing and using this product.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electricawork practices. See NFPA 70E, CSA Z462NOM 029-STPS or local equivalent.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Replace all devices, doors, and covers before turning on power to this equipment
  • Beware of potential hazards, and carefully inspect the work area for tools anobjects that may have been left inside theequipment.

Failure to follow these instructions willresult in death or serious injury.
WARNING: This product can expoyou to chemicals including DINP, whis known to the State of California tcause cancer, and DIDP which is known to the State of California to cause birth defects or other reproductive harm. For more information go to:
www.P65Warnings.ca.gov.

Necessary Tools

Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker -
Tools

Before Working on Equipment

Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker -
Trip

  1. Turn off all power supplying this equipment before working on or inside equipment.
  2. Turn off or use push-to-trip button to trip circuit breaker.
  3. Use a properly rated voltage sensing device to confirm power is off.

Safety Clearances

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Install circuit breaker so minimum clearance distance to grounded metal is maintained.
Failure to follow these instructions wilresult in death or serious injury.
3.1 Minimum Clearances

Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker -
Clearances

Standard (80% rated current)

A B C

14.6 in.
371 mm| 8.5 in.
216 mm| 3.16 in.
80 mm

100% rated current

| Painted sheet metal| Bare sheet metal
---|---|---
D| E| F| D| E| D
1| No accessories| 1.18 in.
30 mm| 0.19 in.
5 mm| 0
0| 1.57 in.
40 mm| 0.19 in.
5 mm| 0.19 in.
5mm
2| Interohase barrier:| 0
0| 0
0| 0
0| 0
0| 0
0| 0.19 in.
5mm
3| Long terminal shield
I| 0
0| 0
0| 0
0| 0
0| 0
0| 0.19 in.
5mm

3.2 Compression Lug Safety Clearance

Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker -
cableIf G < 0.37 in. (< 9.5 mm) : an insulating screen or long terminal shield is required.
3.3 Live Part Minimum Safety Clearances Required

Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker - Live
parts Live parts.

V ≤ 600Y/347 V (UL) 690 V (IEC) H ≤ 2.36 in. (60 mm) H > 2.36 in. (60 mm)
I J I

7.87 in.
200 mm| 3.94 in.
100 mm| 4.72 in.
120 mm| 2.36 in.
60 mm

Installation

Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker -
Installation

4.2 DIN Rail

Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker -
Dismounting

PLEASE NOTE
For DIN rail mounting, cable cross-sectional area should noexceed 1/0 AWG (50 mm²).
4.3 Door Cutout

Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker - Door
Cutout

Wiring

5.1 EverLink Lugs Connections

Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker -
EverLink

1| | | |
---|---|---|---|---
0.78 in.20 mm| Cu \ Al| 14-8 AWG| 2.5-10 mm²| 44 ± 4.4 lb-in.
<125 A \<100 A| 2.5-10 mm2| 5 ± 0.5 N•m
Cu \ Al| 6-3/0 AWG| 6-2/0 AWG| 80 ± 8 lb-in.
<125 A \<100 A| 16-95 mm²| 16-70 mm²| 9 ± 0.9 N•m
2| 0.47 in.12 mm| 20-10 AWG| 20-10 AWG| 9 ± 1 lb-in.
1.5-6 mm²| 0.5-6 mm²| 1 ± 0.1 N•m

5.2 Mechanical Lug Connections
NOTICE
HAZARD OF OVERHEATING

Do not allow wire strands to get caught in wire binding screw threads.
Failure to follow these instructions can result in equipment damage.![Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker

| | | |
---|---|---|---|---
| 0.63 in.
16 mm| Cu/AI
15-125 A| 14-10 AWG
2.5-6 mm2| 35±3.5 lb-in.
4±0.4 N•m| 5/32 in.
4 mm
8-2/0 AWG
10-70 mm2| 50+5 lb-in.
5.6±0.6 N•m
| 0.63 in.
16 mm| Cu
15-125A| 14-10 AWG
2.5-6 mm2| 35±3.5 lb-in.
4±0.4 N•m| 5/32 in.
4 mm
8 AWG
10 mm2| 40±4 lb-in.
4.5±0.5 N•m
6-4 AWG
16-25 mm2| 45±4.5 lb-in.
5.1±0.5 N•m
3-1/0 AWG
35-50 mm2| 50±5 lb-in.
5.6±0.6 N•m

5.3 Compression Lugs/Busbar Connections

Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker -
Busbar

5.4 PowerPacT B DC Wiring Diagrams

| Grounded Negative| Grounded Middle Point| Ung rounded Source
---|---|---|---
Type| | ![Schneider Electric BJL36030LU Power Pact Molded Case Circuit Breaker

Circuit Breaker Removal

  1. Turn off all power supplying this equipment before working on or inside equipment.
  2. Turn off or trip circuit breaker before removal. Make sure the circuit breaker is in the open (O) position or in the trip ( ) position.
  3. Use a properly rated voltage sensing device to confirm power is off.
  4. Remove circuit breaker in reverse order of installation.

© 2019-2022 Schneider Electric
All Rights Reserved
Schneider Electric, Square D, and PowerPacT are trademarks owned by Schneider Electric Industries SAS or its affiliated companies. All other trademarks are the property of their respective owners.

Schneider Electric LogoSchneider Electric Limited
Stafford Park 5
Telford TF3 3BL
United Kingdom
www.se.com/uk
Schneider Electric USA, Inc.
800 Federal Street
Andover, MA 01810 USA
888-778-2733
www.se.com/us/en/
GDE55878

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals