Honeywell FML-E3 Fiber Option Modules User Guide

June 13, 2024
Honeywell

Honeywell FML-E3 Fiber Option Modules User Guide

Description

The Gamewell-FCI E3 Series® (Expandable Emergency Evacuation) and the S3 Series (Small Addressable Fire Alarm Control Panel) use the RPT-E3-UTP (Repeater-E3 Module) to support two types of fiber-option modules to convert wire to fiber. These communication circuits are wired in Class X configuration so the option modules provide Class X outputs.

  • FML-E3 (Fiber-Optic Multi-Mode, Receiver)
  • FSL-E3 (Fiber-Optic Single-Mode, Transmitter)

FML-E3 (Fiber-Optic Multi-Mode, Receiver)

The FML-E3 is a fiber module used as one channel to transmit or receive communications with the RPT-E3-UTP (Repeater-E3 Module). It allows the multi- mode fiber to network between the FML-E3 module boards.

Figure 1 FML-E3 Circuit Board
Circuit Board 

FML-E3 Specifications

  • Type of Connector: Type ST
  • Maximum Attenuation: 8 dB for multi-mode with 62.5/125 micrometer cable @ 200 µm.
  • Standby Current: 0.053 A
  • Alarm Current: 0.053 A
  • Environment Rating: 32° to 120°F (0° to 49°C), 0% to 93%
  • Relative Humidity: Non-condensing at 90°F (30°C)

FSL-E3 (Fiber-Optic Single-Mode, Transmitter)

The FSL-E3 is a fiber module that is used as one channel to transmit or receive communications with the RPT-E3-UTP (Repeater E3 Module). It allows the single-mode fiber to network between the FSL-E3 module boards.

Figure 2 FSL-E3 Circuit Board
Circuit Board 

FSL-E3 Specifications

  • Type of Connector: Type LC
  • Maximum Attenuation: 30 dB for multi-mode with 9/125 micrometer cable @ 1,310 nm.
  • Standby Current: 0.079 A
  • Alarm Current: 0.079 A
  • Environment Rating: 32° to 120°F (0° to 49°C), 0% to 93%
  • Relative Humidity: Non-condensing at 90°F (30°C)

Installation

CAUTION: STATIC SENSITIVE COMPONENTS
THE CIRCUIT BOARD CONTAINS STATIC-SENSITIVE COMPONENTS. ALWAYS GROUND YOURSELF WITH A PROPER WRIST STRAP BEFORE HANDLING ANY BOARDS SO THAT STATIC CHARGES ARE REMOVED FROM THE BODY. USE STATIC SUPPRESSIVE PACKAGING TO PROTECT ELECTRONIC ASSEMBLIES.

WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY MODULES OR WIRING.

The following guidelines must be followed when installing the FSL-E3 and FML-E3 modules.

  • Installations are to be indoors only, in dry locations, protected from rain, water, and rapid changes in temperature that could cause condensation. Equipment must be securely mounted on rigid, permanent walls.
  • Operating temperature shall not exceed the range of 32°-120° F (0-49° C).
  • Operating humidity not to exceed 93% non-condensing at 90° F (32° C).
  • There should be adequate space around the installation to allow easy access for operation and servicing.
  • All sub-assemblies and components are to be located in compliance with the local, the national codes and the manufacturer’s recommendations.
  • All installation field wiring shall be in compliance with the local code, the national code and the manufacturer’s recommendations.
  • Use the Architects and Engineering Specifications for detailed information on your Facility’s Configuration.

FML-E3/FSL-E3 Installation

Install a maximum of two boards per installation. Fiber modules can be mixed in the configuration.

  1. Remove the unit from its static-shield bag, observing proper static protection measures.
  2. Visually inspect the unit for damage. If any components are damaged, notify the shipping carrier immediately. Report missing components to Gamewell-FCI Customer Service.
  3. Install three standoffs from the hardware kit into the holes shown in Figure 3 below.
  4. Plug the fiber module onto the connector of the RPT-E3-UTP.
  5. Secure with three supplied #4-40 x 1/4” screws.

Figure 3 RPT-E3-UTP Installation
Installation

Wiring and Configuration

FML-3

Use DIP switches 1-3 to set the output power for the transmitting fiber. DIP switch 4 is not used. Refer to Table 1 below. Use standard ST connector fiber- optic cable, multi-mode, up to 200 µm (optimized for 62.5/125 µm). There is a signal loss of up to 8dB maximum between nodes.

Table 1 FML-3 Switch Settings/Drive Currents

SW1-1 SW1-2 SW1-3 Drive Current
OFF OFF OFF 10 mA
OFF OFF ON 20 mA
OFF ON OFF 32 mA
OFF ON ON 42 mA
ON OFF OFF 54 mA
ON OFF ON 64 mA
ON ON OFF 76 mA
ON ON ON 86 mA

FSL-3

Use LC connector fiber-optic cable, single mode, up to 1310 nm (optimized for 9/125 µm). There is a signal loss of up to 30dB maximum between nodes. There are two LED indicators on the FSL-3. Refer to the table below.

Table 2 FSL-3 LED Functions

LED # Name Color Description
1 TX Green Lights when data is transmitted on the Repeater.When activity is

detected, the TX light flickers and turns ON. If no activity is detected, the TX light turns OFF.
2| RX| Green| Lights when data is received on the Repeater.When activity is detected, the RX light flickers and turns ON. When no activity is detected, the RX light turns OFF.

Reference Documentation

If you require detailed installation instructions on cabinetry, wiring, and specifications, you can download the following UL Controlled documentation from the Gamewell-FCI website, www.gamewellfcimanuals.com

  • S3 Series UL Listing Document: LS10005-051GF-E
  • E3 Series UL Listing Document: LS10080
  • E3 Series Broadband Installation/Operation Manual: 9000-0575
  • E3 Series Classic Installation/Operation Manual: 9000-0577