Important Information

The JC-30D2-EZ Light Source and Light Detector are mounted on opposite sides of the smoke duct. Smoke passing through the light beam reduces the light Intensity sensed at the Detector. The intensity signal is transmitted to the JC-30D2 Monitor where it is converted into Opacity for display and alarming.

Light Source and Sensor

The 190851S Light Source uses a long life LED Lamp. The 190851D Detector has a large lens that reduces inaccuracies due to ambient light and misalignment.

Light Source and Sensor

Calibration

Calibration is automated, there are no manual adjustments. During every Calibration, the Lamp brightness is automatically adjusted to suit the soot/dust build-up, alignment changes, and stack width.

Auto-Cal

The JC-30D2-EZ can be configured to automatically do a calibration after the burner fan cycles Off. Calibration cancels out soot build-up on the optics and thus reduces the need to frequently clean the Source window and the Detector lens.
Auto-Cal significantly reduces false alarms and nuisance shutdowns caused by typical burner light-off and shutdown soot deposits.

JC-30D2 Monitor / Alarm

At a glance, the bargraph indicates when maintenance is required… before burner shutdown occurs. Intuitive Menu navigation makes setup and adjustments easy. RS-485 and Ethernet Modbus makes remote monitoring easy.

SAFETY

DANGER

Electric Shock Hazard
Multiple power sources may be present. Disconnect all electric power sources, local and remote, before servicing

**WARNING**

This product is intended for use in Commercial and Industrial installations, it is NOT intended for Residential use. This product is intended to be used by Trained Operators.

Installation, start-up, and troubleshooting is intended to be done by Experienced Technicians familiar with Industrial Safety Codes and all Safety Codes specific to burners and boilers.

This product is NOT perform a Primary Safety Interlock rated device. The Shutdown Relay Output should only be used as an additional auxiliary Operating limit and should not replace or bypass any Primary Safety Interlock devices required by Safety Codes.

Incorrect wiring connections to burner/boiler Flame Safeguard controls can cause Equipment Damage, Injury, or Death

Standard Alarm Sequence

See the SEQUENCE section for additional details on the field selectable sequences: NYC-BAR and WOOD-COAL.

The hash mark to the right of the bargraph indicates the Alarm Setpoint. The Alarm contacts will close and the bargraph will blink if the Opacity has been above the Setpoint continuously for 20 seconds (adjustable from 0-120 sec.).

Press the Silence button to stop the blinking and to de-energize the Alarm Relay (typically wired to an external bell, horn, or strobe).

When the opacity drops below the Setpoint, the bargraph will stop blinking and the Alarm relay will de energize (if it hadn’t already been Silenced).

If the Opacity is continuously above the Alarm Setpoint for more than 120 seconds (adjustable from 0-180 sec.), the Shutdown relay will de-energize and display the message SHUTDOWN. Typically, the Shutdown relay N.O. contacts are wired in series with the burner Operating Limits circuit and this will cause the burner to shutdown.

After the opacity has dropped below the Alarm Setpoint, you must press the RESET button to re-energize the Shutdown before the burner can re-start (assuming the shutdown contacts are wired to shutdown the burner). The Shutdown Relay remains de-energized, the burner will not re-start, and SHUTDOWN is displayed until the JC-30D2 has been RESET.

If the AC power has cycled Off and then ON, the JC-30D2 cannot be RESET until after the Lamp has completed WARM UP.

Operation

Home Screen

The current % Opacity is displayed at the top. The Bargraph height varies in proportion to the Opacity. The line on the right side of the bargraph is the Warning/Shutdown Alarm setpoint.

The lower left button on all screens indicates one of these three words:
Silence or Alarms or History

When a new Alarm occurs, Silence and the bargraph blink, and the Common Alarm Relay Output energizes. Touch Silence to stop the blinking and to de-energize the Alarm Relay. Alarms is displayed after silencing (if an Alarm is still active). History is displayed when there are no active Alarms.

A Shutdown Alarm latches and requires a manual reset after the temperature has dropped below the Shutdown setpoint. The RESET button is only displayed when a reset is required.

Operation

Active Alarms Screen

From any other screen, touch the Alarms button to display the Active Alarms Screen. If there are no active Alarms, Alarms will not be displayed on the Home or Menu screens.

All active Alarms are displayed on this screen: Warning Alarm, Shutdown Alarm, Hardware Faults, etc….

The Alarm Opacity and time/date shown occurred when the Alarm time delay expired and the Alarm triggered.

When the Alarms screen is displayed, History and Back are displayed.
Touch History to display the History screen.
Touch Home return to the Home screen.

History Screen

Touch History to display the History screen.

The History screen displays the Time/Date of the most recent 50 Alarms and Events. Events include: peak Opacity, when an Alarm Clears, a Shutdown Reset, JC-30D2 power-up, etc..

Touch the Up or Down arrow to advance to the next page of History. Touch Date to enter a time/date and then to jump to the nearest History records.

The Hide Events and Show Events removes or displays Events.

The History memory is retained when powered down. The History can be extracted via the USB port using the free JC_TG_Edit Windows App.

Menu Screens

To set clock, Alarm Setpoints, and other initial Setup…..See pages 9 and 10

Window-Lens Cleaning

  • The Light Source window, Light Detector lens, and any Purge Cap windows should be cleaned periodically. Use a soft, lint free cloth dampened with “Windex”.
  • Re-calibrate after every cleaning (from the CALIBRATE Menu) .
  • If cleaning the windows/lens and re-calibrating doesn’t clear the “LENS IS DIRTY” message, then the Source and Detector might need to be re-aligned.
    Window-Lens Cleaning

The message “LENS IS DIRTY” is displayed after a calibration when: 0% Opacity mA is less than 15 and Detector Gain = High and Lamp Brightness =17. Re- calibration fails when 0% Opacity (“0 mA”) is less than 8.

The Calibration History screen (Menu/Calibrate Opacity/Calibration History) shows the results of the last 60 calibrations. The trend of increasing Lamp values, then decreasing 0 mA values, allows you to anticipate a nuisance Opacity shutdown.

“Before” is the Opacity (due to dirt/soot) just before a calibration.. If these values are consistently near the Alarm setpoint, increase Purge air flow or service the burner or re-calibrate more frequently, to prevent nuisance shutdowns.

“Fan Starts” is the number of starts since the last calibration. If a small number of starts increases “Before” opacity, consider cleaning the oil nozzles or changing the burner light-off settings to reduce the initial puff of soot.

If the AutoCal is enabled (see page 10), the time interval between Lens cleanings will be much longer because AutoCal calibrates out the normal dust build-up on the optical surfaces. AutoCal can prevent nuisance Lockouts due to soot buildup.

Calibration

Calibration is required After Installing; After cleaning the windows & Lens; After Source or Detector re alignment; or After the LED Lamp has been replaced.

How to Start a Calibration:

  • The burner fans must be OFF during the entire calibration.

  • Once started by the User, Calibration is fully automated and takes approximately 3 minutes.

  • From the Home screen, touch Menu, then Calibrate Opacity, then Calibrate Now

  • Wait: For Stack to Clear displays and counts down to 0 after the burner Fan stops to allow dust to settle.

  • Wait: Lamp Warming Up displays and counts down to 0 when initially powered up, or whenever the Lamp has been Off.

  • When both Waits are done, the Start button appears. Press Start to begin the Calibration. Press Back, Home, Silence, Alarms, or History on any of the Calibration screens to abort the Calibration process.

  • During the first phase of calibration, the 190851x Light Source “Auto Ranging” occurs, as follows:. The Lamp brightness (2-17) and Detector Gain (Low/High) are  automatically varied to find the maximum Detector mA signal. The Wait timer counts down from 180 seconds, but can complete Auto Ranging in as short as 120 sec. (depending on distance, alignment, etc…)
    Calibration

  • After a successful Auto Ranging is completed, Opacity Calibration begins with ON to find the 0% Opacity mA signal.

  • 10 second Wait for the mA signal to start to settle down.

  • After that, every 5 seconds the Detector mA signal is checked.

  • When two successive mA vales are within 0.3% of each other, the Opacity value is saved.

  • Then the Lamp is turned OFF to find the 100% Opacity mA signal.

  • When two successive mA vales are within 0.3% of each other, the 100% value is saved.

  • After a successful Calibration is completed, the Auto Ranging and Calibration displayed and is also stored in the Calibration History Log.

  • The Lamp turns back ON and the Warm Up delay counts down

  • If an Error occurs during Auto Ranging or Opacity Calibration, this screen will  with the Error Message (see Trouble Shooting section)

  • This screen will continue to be displayed (forever) until the Back, Home, Alarms, or History button is touched.

  • If CLEAN LENSE is displayed on the Status line, the Detector mA signal is very weak. Opacity has been successfully Calibrated. However, if the Optics aren’t cleaned and/or re-aligned, the next Calibration might not be successful.

AutoCal After Burner Shutdown

The main reason for Opacity drift and/or nuisance burner trips is soot/dust build-up on the windows or the Detector lens. A calibration cycle cancels out the normal dust/soot build-up on the optical surfaces.
The JC-30D2-EZ can initiate an unattended fully Automated Calibration (AutoCal) cycle after the burner fan stops running.

The calibration screens above are not displayed during AutoCal. The normal bargraph screen is displayed with the status message Auto Calibration in Progress. After a successful AutoCal has completed Calibration Successful is displayed and the data is saved in the Calibration Log. If AutoCal is not successful, the last successful calibration data will continue to be used.

To enable this feature: In the Configure/Setup menu, enable the AutoCal Option, and Wire terminal 8 to the 120 Vac fan starter coil as shown in the Wiring section.
See the Menu section (page 10) for additional AutoCal settings.

Installation

JC-30D2 Indicator Mounting:

The JC-30D2 Indicator is designed for flush mounting in an enclosure located in an indoor NEMA 12 environment.

The JC-30D2 should not be subjected to excessive vibration. Continuous operation is guaranteed over the 32-131 F (0-55C) ambient operating range.

See Full Size Cutout Template on the last page

Installation

Light Source & Detector Mounting 

The Light Source and Detector are designed for mounting in an indoor NEMA 1 environment, with 32-149F (0-65C) ambient, and without excessive vibration

  • See last page for Full Size Cutout Template.
  • Locate such that the light beam passes through the complete smoke profile at all flow rates. See the sketch at right for locations after an Elbow, T, Fan, Damper, or other uneven flow profile.
  • Do NOT locate the Light Source and Detector near any sources of bright light (outside windows, light fixtures, …). If this is not possible, 190713 Light Shields may be required.
  • Do NOT locate the Light Source and Detector upstream from an Oxygen Analyzer. Air entering the duct would give a false stack Oxygen indication.
  • Locate the Source and Detector where it is accessible for routine cleaning.
  • The distance from the face of the Light Source to the face of the Light Detector must be greater than 3 ft. and less than 10 ft.
  • The ¾” mounting pipe should be horizontal.
  • The ¾” mounting pipe maintains the optical alignment from the Source to the Detector. The flue gas heat expands and contracts the pipe length. One end of the mounting pipe should be welded, or clamped, to the duct. The other end of the mounting pipe must be free to move. Do NOT connect BOTH ends of the mounting pipe to the duct. Do NOT use 2 stubs on opposite sides of the duct to mount the Source and Detector because the alignment will shift as the duct heats and cools.
  • For positive pressure ducts, install a pressure cap (ie, window) to prevent flue gas and dust from exiting the duct. The 107226P pressure caps can be used without purge air for low soot installations. For high soot applications, clean dry compressed air should be connected to 107226P pressure caps. See SDI-107226P instructions for further details.
  • If Clean, dry compressed air is not available, the 190275A Blower Caps are suitable for duct pressures less than +1.0″ wc.
    See the 190275A instructions for further details.

Light Source and Light Detector Dimensions

Light Source and Light Detector Dimensions

Light Source and Light Detector Dimensions

Wiring

  Warning

Disconnect all sources of power before installing or servicing this equipment. Multiple Disconnects may be required. Burner interface wiring must be performed by an experienced burner service technician.

All wiring must comply with all local and national electrical codes. Tighten all terminals to 4.4 in-lb. Wire must be stranded copper, 12-24 ga., 150V / 75 C insulation minimum. AC and DC wiring must be separated and must not be run in the same conduit to prevent electrical noise coupling. Use shielded cables where shown, connect shields only where shown, insulate all other shields to prevent accidental grounding. Ignition transformer and motor VFD wiring are particularly noisy and should be kept away from all Opacity Monitor AC and DC wiring.

  • The Light Source and Light Detector final connection wiring must be installed with flexible conduit to allow the light beam to be aimed/aligned and for cleaning.
  • Inside the Light Source, insulate the bare shield wires so that they do not short to the enclosure or to any of the components on the circuit board.
  • Relay contacts are shown with power removed from the JC-30D2. In normal operation Relay 2 is energized. Relay 2 de-energizes to shutdown the burner.
  • Relay contacts are rated: 10 A resistive, 9 FLA / ½ Hp / 120 Vac
  • If the 4-20 mA output will not be used, jumper terminal 39 to 40 to prevent the OUTPUT FAILURE error message.
  • RS485 is electrically Isolated from all other DC and AC wiring.
  • All DC wiring and shields must be isolated from Ground.
  • All DC wiring ‘-‘, shield, and ‘Common’ terminals are connected together internally.
  • Terminals 1-9 are Line Voltage AC. Terminals 31-50 are low voltage DC.
  • An external Line Voltage supply switch or circuit breaker, marked as the disconnect for this instrument, suitably located and easily reached, and complying with IEC 60947-1 and -3 must be provided.

Fuse: 3.15 amp Slo-Blo, 250 V, 5x20mm (Littlefuse 02393.15HXP, Belfuse 5TT 3.15-R, Preferred Utilities 16740-3.15S)
Caution: To reduce the risk of fire, only replace fuse with the same type.

Wiring

Parameters / Menu Map

From the Home screen, touch Menu to display the Main Menu.

Parameters / Menu Map

Screen Settings

Parameter Default Max. Min. Go to: Menu > Utilities > Screen Settings
1 Disable Enable Disable Touch Buzzer Enable: Activates faceplate

Tone when a screen item is touched
2| Disable| Enable| Disable| Alarm Buzzer Enable: Activates faceplate Tone when an Alarm is triggered.

Opacity Alarms

Parameter Default Max. Min. Go to: Menu > Opacity Alarms
20 20 50 5 Alarm Setpoint (% Opacity)

This Setpoint is used for the Warning Alarm logic.

Note: In the NYC-BAR Sequence, the Setpoint can be greater than 20%.

21| 20| 120| 0| Warning Delay (seconds)

The Common Alarm relay energizes when the Opacity has been above the Alarm Setpoint for more than ‘Warning Delay’ seconds.

Once the Warning Alarm has been triggered, the Opacity must drop 1% below the Setpoint before the Warning Alarm de-activates.

Note: In the NYC-BAR Sequence, this Delay is forced to 0 seconds.

22| 120| 180| 0| Shutdown Delay (seconds)

The Shutdown relay de-energizes when the Opacity has been above the Shutdown Setpoint for more than ‘Shutdown Delay’ seconds.

The Opacity must drop 1% below the Shutdown Setpoint and the Operator must press the RESET button in order to re-energize the Shutdown relay.

Note: In the NYC-BAR Sequence, this Delay can be greater than 120 seconds.

23| Std.| Wood| Std.| Alarm Sequence (Standard, NYC-BAR, Wood-Coal)

See Alarm Sequence descriptions on page 2 and 11

24| 12| 50| 1| Overfire Start Setpoint (% Opacity)

Only used in the Wood/Coal Sequence, see Sequence description on page 11

25| 10| 120| 1| Overfire Start Delay (seconds)

Only used in the Wood/Coal Sequence, see Sequence description on page 11

26| 180| 600| 1| Overfire Stop Delay (seconds)

Only used in the Wood/Coal Sequence, see Sequence description on page 11

Configure/Setup

AutoCal

Parameter Default Max. Min. Goto: Menu > Configure / Setup > AutoCal
27 Enable Enable Disable AutoCal Option Enable

See description on pages 4-5

If the fan starter energizes when an AutoCal is in progress, the AutoCal aborts.

28| 30| 600| 30| Clear Stack Delay (seconds)

Seconds from Fan Starter de-energizing and start of Auto-Cal. Allows time for fan to coast down, Dampers to close, and for dust in ducts to settle in order to provide an accurate 0% Opacity Calibration.

29| 24| 168| 0| Min Hours Between AutoCal’s (hours)

0-168 hours. 0 hrs means an AutoCal attempt will occur every time the burner fan starter de-energizes. 1 hr means an AutoCal will occur at most once per hour.

However, if after the clear stack delay, the Opacity (soot) is greater than 1/2 of the Alarm Setpoint value, an AutoCal (if enabled) will occur regardless of the “Min Hours

Between AutoCal’s setting”. This avoid nuisance Opacity Alarms and Shutdowns.

Bargraph Range

Parameter Default Max. Min. Goto: Menu > Configure / Setup > Bargraph
30 40 100 20 Top of Bargraph (% Opacity)

This is the % Opacity value at the top of the bargraph.

Other Alarm Sequences

STANDARD Sequence

This sequence is described in the Operation section, see above.

NYC-BAR Sequence

The NYC-BAR Sequence is the same as the STANDARD Sequence described above with two differences:
The Alarm Time Delay is fixed at 0 seconds and cannot be adjusted. This means that the Alarm Relay will activate as soon as the Opacity is greater than the Alarm Setpoint. The Shutdown Time Delay is fixed at 120 seconds and cannot be adjusted.

A 30% Opacity Test Filter is attached to the Light Source. You can clean the windows/Lens and then hang the filter on the screw to verify that the Alarm Setpoint is set correctly and that the calibration is reasonable. The 30% Opacity value of the filter is approximate.

WOOD-COAL Sequence

The WOOD-COAL sequence is intended for use on solid fuel stoker fired furnaces. The Alarm Relay and Alarm Silence operation is the same as the STANDARD Sequence described above.

The JC-30D2 WOOD-COAL logic for Relay 2 can be used to add Overfire Air (above the stoker) to reduce smoke caused by clinkers and other stoker problems. Relay 2 is typically wired to an Overfire Air fan starter, or motorized damper. The WOOD-COAL Sequence does not include any burner Shutdown logic.

The Overfire Start Setpoint controls Relay 2, and is independent from the Alarm Setpoint. Typically, the Overfire Alarm Setpoint is set to a lower Opacity level than the Alarm Setpoint. If the Opacity is above the Overfire Start Setpoint for more than the 10 second Overfire Start Delay (adjustable 10-120 sec.), Relay 2 energizes and OVERFIRE ON is displayed on the message line. The Overfire Start Delay prevents nuisance starts due to momentary smoke puffs.

Once Relay 2 is energized, the Opacity must be below the Overfire Start Setpoint for more than the 120 second Overfire Stop Delay (adjustable 0-600 sec) before Relay 2 will de-energize. The Stop Delay helps prevent re occurrence due to incomplete burn-out.

Troubleshooting

Normal Operation:

Lamp is ON, and NOT blinking

190851S Light Source power input, terminals 10(+) to 12(-): 17 – 26 Vdc range

190851S Lamp On/Off command input, terminal 23(+) to 12(-):
Lamp ON command: approx. 1.5 Vdc. Lamp OFF command: Greater than 2.7 Vdc

Detector to Light Source 4-20mA, terminal 28, meter in-series: 3.8 – 22 mA 3.8-4.3 mA with Detector lens totally blocked.

Light Source to JC-30D2 Monitor mA, Terminal 38 meter in series 3.8 – 22 mA Should exactly match mA signal into Light Source Terminal 28

Light Source Lamp is Blinking

These following errors are detected by the Light Source processor during the Auto Ranging portion of the Calibration cycle. Correct the problem and then start another Calibration cycle to stop the Lamp Blinking.

1 Blink

Detector output (terminal 28) is near 0 mA, should be approx. 4 mA when Lamp is Off. Check Light Source to Light Detector Wiring, Terminals 27 and 28. Wires might be swapped.

2 Blinks

Detector output (terminal 28) is greater than 20 mA, should be approx. 4 mA when Lamp is Off.
Check Light Source to Light Detector Wiring, Terminals 28 and 29. Wires might be swapped.

3 Blinks

The AutoRanging data in the Light Source is invalid. Do a Calibration to correct the data.
Either this light source has never been AutoRanged/calibrated before or Electrical noise corrupted the data.

4 Blinks

The Lamp Brightness command is Out of Range. Do a Calibration to correct the data.
Electrical noise could cause this.

5 Blinks

The Detector Gain setting is invalid. Do a Calibration to correct the data.
Electrical noise could cause this.

Light Source Auto Ranging Error Messages

Wiring Detector Plus: See 1 blink above

Wiring Gain: See 2 blinks above

Bad CRC: See 3, 4, 5 blinks above

Source Too Close: With the Lamp at the lowest Brightness setting, the Detector Intensity was higher than 22.6 mA. The Light Source is too close to the Light Detector or the Detector is seeing Ambient Light.

Gain Relay: The Light Source changed the Detector Gain relay command (term. 29), but Detector mA didn’t change. Terminal 29 wire is open circuit, or the Detector is defective, or the Source is defective.

Bad Monitor: The Lamp Brightness sensor signal is too low when the Lamp is at max brightness. Could be a dim LED Lamp, a dirty sensor, or a bad Light Source.

Low Detector: With max Lamp brightness and High Det. Gain, the Detector signal is below 8.1 mA. Windows/lens are very dirty, or bad alignment, or Detector is too far from Source.

Timeout: Auto Ranging did not complete in less than 3 minutes

Opacity Calibration Error Messages

Calibration Aborted by Fan: The burner fan energized during Calibration.
Clear Stack Failed to Settle: With the Lamp ON, Detector mA signal never stabilized. Fan running without starter wired to JC-30D2, Soot/dust in optical path, vibration shaking Source/Detector, or Electrical Noise.
Clear Stack Over 23 mA Too Much Light: Ambient light sensed by the Detector drove the Detector too high. A 190713 Light Shield over the Detector might be needed to block nearby bright lights or bright sun light.
Clear Stack Under 8 mA Not Enough Light: Detector signal was very low. Very dirty windows or lens or Source/Detector got knocked out of alignment.
Opaque Stack Failed to Settle: With the Lamp OFF, Detector mA signal never stabilized. A 190713 Light Shield over the Detector might be needed to block nearby bright lights or bright sun light or Electrical Noise.
Opaque Over 4.7 mA Too Much Light: Lamp is OFF. A 190713 Light Shield over the Detector might be needed to block nearby bright lights or bright sun light.
Opaque Under 3.3 mA: Wiring Error, or possible bad Detector.

Other

If Pressure Caps are installed; Warming up a Natural Gas fired boiler can cause nuisance alarms due to condensate on the window. Use purge air that is below the dew point to prevent this nuisance alarm.

LED Lamp Replacement

  • Remove 120 Vac power from the JC-30D2 (Note: This will cause the burner Shutdown relay to de energize).
  • Remove the 190851S Light Source rear cover plate.
  • Remove the 4 screws the hold the 190799 Lamp PC Board in place.
  • Un-plug the old Lamp board, plug-in the new190799 Lamp, and re-install the 4 screws and the read cover.
  • Apply 120 Vac power to the JC-30D2.
  • Wait for Lamp Warmup to complete.
  • The new LED Lamp will not have the same optical alignment, or brightness, as the old LED Lamp.
  • Re-calibrate the JC-30D2 from the CALIBRATE Menu as described above in the Calibration section

Parts List

JC-30D2
190851S
190851D
190799
16740-3.15S
92794
92791
92795| Opacity Monitor/Indicator
Light Source
Light Detector
LED Lamp
3.15 A slow-blow fuse
5 pt Term. Block
8 pt Term. Block
10 pt Term. Block| 96059
90434
90437-KIT
107226P
190275A
SDA-VB
SDA-B6| RC Noise Snubber
Mounting Gasket
Panel Mounting Clips (2)
Pressure Caps (2) with Purge Air Ports
Pressure Caps (2)
with 1” wc 120V Blowers
Audible/Visual Ext. Alarm
6” Alarm Bell, 120V, 85 db
---|---|---|---

Specifications

Mechanical

Enclosure: Nema 12 Faceplate, Indoor Locations
Bezel: 3 7/8 w x 8 h x 1 d
Rear Case: 3 1/2 w x 7 9/16 h x 4 7/8 d
Panel Cutout: 3.61 w x 7.65 h
Weight: 2 lbs
Ambient: 32-131 F (0-55 C)
Altitude: 6560 feet (2000 meters)

Electrical:

Input Power: 120Vac +/-15%, 50/60 Hz, 26 VA
Output Power: 24 Vdc, 300mA max combined load
Terminals: 31,35,37,40,42

Inputs

Light Intensity: 3.7 – 23 mAdc
Remote Silence (2): Dry Contact, 24 Vdc / 1 mA 120Vac, 10 mA, opto isolated
Burner Fan Running: 120Vac, 10 mA, opto isolated

Outputs

Opacity (0-100%): 4-20 mA, 650 ohm load
Relay Outputs: 10 A Resistive, 8 FLA, ½ Hp, 120
Vac

Light Source and Detector

Calibration: Automatic, Off-Line
Spectral: Photopic, peak and mean within 500-600 nm
Response Time: < 10 seconds for 95% change
Sighting Distance: 3 – 10 ft optical path length
Wiring Distance: 500 ft max.
Ambient Temp.: +32° to 149° F Enclosure NEMA 1
Size: 6w x 5d x 8.5h
Mounting: ¾” pipe, 3.5” centers

Communications

USB: JC_TG_Edit config & Firmware Flashing
RS485: Isolated, 4.8 – 57.6k baud, Modbus RTU
Ethernet: 10/100 Mb/s, Modbus/TCP

Modbus Communications

RS485: Baud: 4800, 9600, 19200, 38400, 57600 Parity: Odd, Even, None Stop Bits: 1, 2
Ethernet: 10/100 Mb/s
Protocol: RTU, TCP/IP
Address: 1-247
Register Formats: 16 bit Signed Integer 32 bit Floating Point (register below = High bytes (exponent), register+1 = Low bytes (mantissa)
Modbus Commands: 01 Read Coils, 03 Read Registers, 05 Write Single Coil, 06 Write Single Register, 16 Write Multiple Registers (2 registers max)
Max Poll Size: 120 coils or registers (except Code 16)

Coil 0 = 1 = Description
98 WO Alarm Silence Remote Alarm Silence
99 RO No Alarm Alarm Common Alarm
102 RO No Alarm Alarm High Opacity Alarm
103 RO No Alarm Alarm High Opacity Shutdown
104 RO Not Dirty Dirty Lens is Dirty
105 RO Stray Light Stray Light
106 RO Offline Measurement Offline
107 RO Cal. Inactive Cal. Active Calibration In Progress
108 RO Overfire Inactive Overfire Active Opacity Overfire Air
109 RO Fan OFF Fan ON Burner Fan Starter
Register F / I Description
--- --- --- ---
40116 F RO Opacity
40118 S16 RO Alarm Setpoint

F = Floating Point, S32 =Signed Integer 32 bit, S16=Signed Integer 16 bit
STR=String, RW*=Tech. Password Required

Full Size Cutout Templates