Sensorworx SWX-222-1 Ceiling Mount Occupancy Sensor Instruction Manual

June 13, 2024
SENSORWORX

Sensorworx SWX-222-1 Ceiling Mount Occupancy Sensor

Product Information

The Low Voltage Ceiling Mount Sensors are designed for installation in ceilings and provide occupancy detection for lighting control. The sensors are available in various models, including PIR (Passive Infrared) and Acoustic Photocell. They are suitable for both small motion and large motion applications, such as high bay environments.
The sensors come with additional unit options, including Daylight Harvesting, Isolated Auxiliary Relay, and High Humidity Environment. The SWX-299-JP accessory is available for mounting the sensor to a single gang mudring, handy box, or 4 octagon box.
The sensors operate at a voltage range of 12-24 VAC/VDC and have a low current draw. The output is a logic high voltage in the occupied mode. The sensors are compatible with 0-10 VDC ballasts or drivers for dimming control. They comply with IEC 60929 Annex E.2 for dimming compatibility.
The isolated relay rating allows for 1A at 30 VDC/VAC. The sensors can be used to meet energy code requirements, such as ASHRAE 90.1, IECC, and Title 24. They are suitable for indoor use with a relative humidity range of 0-95% non- condensing.
The physical dimensions of the sensor are 4.00″ diameter x 1.25″ height, and it weighs 4.75 oz. The color of the sensor is white.

Product Usage Instructions

Sensor Placement
When installing the sensor, it is recommended to position it in a way that adequately covers all entrances to the room or space. The coverage beams of the sensor should be perpendicular to the door, ensuring immediate detection upon entry. Care should be taken to avoid extending the coverage pattern through an open door, as this may result in false detections.
If line of sight between the sensor and occupants is blocked, such as by a cubicle wall or stall, dual technology sensors or additional PIR sensors should be used until line of sight is restored. Dual technology sensors are recommended for spaces where= occupants are sitting or motion is limited, such as private offices, open offices, restrooms with stalls, and libraries. However, they are not recommended for hallways or warehouses.

Coverage
The sensors provide coverage using passive infrared (PIR) and dual technology (PIR/acoustic). The coverage patterns can vary depending on the mounting height. Top view and side view diagrams are provided in the user manual to assist with selecting the appropriate sensor placement based on the desired coverage area.

Wiring
The sensors support both standard wiring and Class 2 wiring options. Refer to the user manual for detailed wiring instructions based on the specific installation requirements.

MODELS

MODEL # PIR ACOUSTIC PHOTOCELL LENS TYPE
SWX-201-1 SMALL MOTION
SWX-211-1 SMALL MOTION
SWX-221-1 SMALL MOTION
SWX-231-1 SMALL MOTION
SWX-202-1 LARGE MOTION
SWX-212-1 LARGE MOTION
SWX-222-1 LARGE MOTION
SWX-232-1 LARGE MOTION
SWX-203-1 HIGH BAY
SWX-213-1 HIGH BAY

ADDITIONAL UNIT OPTIONS

  • D: Daylight Harvesting
  • AR : Isolated Auxiliary Relay
  • HE: High Humidity Environment

ACCESSORIES SWX-299-JP
Ceiling Sensor Trim Ring for Mounting to Single Gang Mudring, Handy Box, or 4” Octagon Box

OVERVIEW
SENSORWORX sensors detect movement in the infrared energy that radiates from occupants as they move within the device’s field-of-view. Once occupancy is identified, the sensor signals a power/relay pack to switch on the connected lighting. If equipped with passive dual technology (PIR/Acoustic), the unit’s microphone is then enabled to further enhance detection while the lights are on. This overlapping passive acoustic occupancy detection is important for rooms with obstructions or where occupant motion will be limited. An internal timer is set to keep lights on during brief periods of inactivity, and is reset every time occupancy is signaled by either the passive infrared or acoustic detection technologies. Additionally, units equipped with ambient daylight detection
(photocells) or daylight harvesting are capable of overriding lights off and/or dimming during periods of occupancy.

SPECIFICATIONS

ELECTRICAL
OPERATING VOLTAGE

  • 12-24 VAC/VDC

CURRENT DRAW

  • 4mA (PIR models)
  • 16mA (Dual Tech. models)
  • 18mA (Dual Tech. w/ Photocell units)

OUTPUT

  • Logic High VDC (Occupied Mode)

RECOMMENDED POWER PACK

  • SWX-900 Series (SENSORWORX)

DIMMING CAPACITY (-D OPTION) 50mA

  • DIMMING COMPATIBILITY
  • 0-10 VDC Ballasts or Drivers
  • Compliant with IEC 60929 Annex E.2

ISOLATED RELAY RATING (-AR)

  • 1A @ 30 VDC/ VAC

CODE COMPLIANCE

  • Sensors can be used to meet ASHRAE 90.1, IECC, & Title 24 energy code requirements

ENVIRONMENTAL

OPERATING TEMP

  • 32°F to 122°F (0°C to 50°C) – Standard
  • -40° F/C (with -HE Option)

RELATIVE HUMIDITY

  • 0-95% Non-Condensing, Indoor Use Only

PHYSICAL

SIZE & WEIGHT

  • 4.00” Diameter x 1.25” H (10.16 x 3.17 cm) 4.75 oz

COLOR
White

OPERATION

TIME DELAYS

  • 30 sec to 30 min (Typical) 10 Minute Default
  • 5 sec Time Delay Expires After 10 min

Sensorworx-SWX-222-1-Ceiling-Mount-Occupancy-Sensor
\(1\)

FEATURES

  • Digital Passive Infrared (PIR) Detection
  • Passive Acoustic Detection (Optional)
  • 360° Coverage Pattern
  • Compact Size and Matte Finish
  • Four Contractor Friendly Mounting Methods
  • Mounting Nipple Attachment with Integrated Hole Saw
  • Convenient Test Mode and Adjustable Time Delays

Diagram 1 – Recommended Sensor Placement in a Private Office PAGE 1

COVERAGE

PASSIVE INFRARED (PIR)

  • 8 to 15 ft (2.44 to 4.57 m) mounting height recommended for small and large motion lenses. For 15 to 40 ft (2.44 to 12.20 m) mounting heights use high bay lens. Ã Detection range improves when walking across beams as compared to into beams.
  • Lenses can be swapped in field if necessary, contact technical support for assistance.

DUAL TECHNOLOGY (PIR/ACOUSTIC)

  • Units with dual technology (SWX-221-1 and SWX-222-1) have overlapping acoustic detection of the complete PIR coverage area.
  • PIR event is required to initially enable acoustic detection.
  • Sounds indicating occupancy reset the sensor’s time delay while non-occupant noises are filtered out.
  • Occupant sounds alone will not keep lights on indefinitely, PIR motion must be periodically detected for lights to remain on for an extended time.
  • After sensor time out expires, acoustic detection remains enabled for 15 seconds to enable voice reactivation of lights for additional convenience and safety.

SMALL MOTION 360°

  • Best choice for detection of small motions from sitting occupants (e.g., hand motion)
  • 500 ft2 of coverage

LARGE MOTION 360°

  • Best choice for detection of larger motion (e.g., walking). Ã ~2000 ft2 of coverage.
  • One of the longer segments of the coverage pattern aligns with the screw hole axis on the sensor (shown as dotted line on Top View diagram below).

Sensorworx-SWX-222-1-Ceiling-Mount-Occupancy-Sensor
\(4\)

HIGH BAY 360°

  • Best choice for mounting heights above 15ft.

  • Recommended for gyms, warehouses, and other high
    ceiling areas where multiple sensor coverage is required. Ã Not recommended for areas where occupants are sitting. Ã Gaps between outer segments get larger as mounting height increases.

  • Not available with acoustic (dual technology).

Sensorworx-SWX-222-1-Ceiling-Mount-Occupancy-Sensor
\(5\)

WIRING

  • Apply power to connected power packs only after low voltage sensor connections have been made.
  • Wiring sensors to a live power pack is not recommended, although in cases where required, it is recommended that the red wire be connected last.

STANDARD WIRING Sensorworx-SWX-222-1-Ceiling-Mount-Occupancy-Sensor
\(6\)

WIRING CONT.

MULTIPLE SENSOR WIRING Sensorworx-SWX-222-1-Ceiling-Mount-Occupancy-
Sensor \(7\)OCCUPANCY + DAYLIGHT HARVESTING

  • Lights will gradually dim in order to maximize energy savings while maintaining desired overall lighting level.
  • Lights will dim only to low trim if white wire is connected to power pack. Connect blue wire to power pack to go completely off from daylight.

Sensorworx-SWX-222-1-Ceiling-Mount-Occupancy-Sensor
\(8\)

SEPARATE OCCUPANCY ZONE & OCCUPANCY + ON/OFF PHOTOCELL ZONE

  • During occupied state, photocell output (blue wire) will turn lights off if ambient light level surpasses threshold and back on if level drops.
  • Also configurable to prevent lights from initially turning on, but not to turn them off once lights are on.

Sensorworx-SWX-222-1-Ceiling-Mount-Occupancy-Sensor
\(9\) SENSOR AUXILIARY RELAY OUPUT (-AR OPTION)

  • The auxiliary output relay (model option -AR) is designed to interface with many types of building management systems (i.e. BMS), VAV units, and relay panels.
  • Operation of relay (brown wires) is configurable
  • By default the relay latches closed when occupancy is detected (white wire goes high).
  • Relay can be configured to alternatively follow the occupancy + photocell (blue wire) output.
  • Relay polarity (open vs closed) can also be reversed.

Sensorworx-SWX-222-1-Ceiling-Mount-Occupancy-Sensor
\(10\)

INSTALLATION INSTRUCTIONS

MOUNTING OPTIONS

  • Chase nipple & lock nut (included) for mounting unit to ceiling tile or 1/2” knockout in junction box. See Side Diagram below.
  • Screw holes for directly mounting to ceiling surface, 3-1/2” (trade size) octagon box, or mud ring with 2-3/4” spaced ears. See Front Diagram below.

INSTALLATION NOTES

  • If mounting to ceiling tile, use the serrated end of the chase nipple to cut a 7/8” hole. Then thread the wires through nipple prior to screwing into rear of sensor. Install and tighten lock nut as needed.
  • To install cover, line up dimples with indents on sensor and turn clockwise.

Sensorworx-SWX-222-1-Ceiling-Mount-Occupancy-Sensor
\(11\)

Note: If mounting to a Single Gang Mudring, Handy Box, or 4” Octagon Box, a trim ring is required. Part Number: SWX-299-JP.

TESTING & TROUBLESHOOTING

TEST MODE
An occupancy test mode with a 5 second time delay is provided in order to efficiently perform walk testing. The sensor will blink white on any detected PIR event and blue on any detected Acoustic event (if equiped), although its time delay will only be reset by a PIR event. In units equipped with a photocell, the test mode will only factor in occupancy. Ambient daylight conditions are ignored.

TO PUT A SENSOR IN TEST MODE FOR 10 MINUTES

  • Press sensor’s pushbutton 2 times, then wait until LED starts blinking back current setting (approx 2 secs).
  • Interupt blinking and press button 1 time to start test mode. After 10 minutes, the sensor’s time delay will revert to previous setting.

RESET
To restore factory settings, press and release the pushbutton 8 times, wait 2 seconds, then press and release the pushbutton 3 times again.

GENERAL CONFIGURATION SETTINGS

FUNCTION #2 – TIME DELAY CONFIGURATION
The length of time after the last occupancy event that the sensor will stay in the occupied state.

CHANGING TIME DELAY SETTINGS

  1. Read through the Time Delay Settings list on the right and note the number of the desired time delay setting (e.g., default is 4 = 10 minutes).

  2. Press and release the unit’s pushbutton twice, then wait 2 seconds.
    The white LED will blink back the number of the current setting.

  3. At any time after blink back starts, enter number of new setting (from Time Delay Settings tables on right).

  4. New setting is saved after white LED blinks new number back 3 times.

If blue LED double flashes at any time, start process over.

FUNCTION #2 – TIME DELAY SETTINGS

SETTING # DESCRIPTION
1 Test Mode *****
2 30 sec
3 5 min
4 10 min      (default)
5 15 min
6 20 min
7 30 min
  • 5 SEC TIME DELAY, EXPIRES AFTER 10 MIN

EXTENDED TIME DELAYS

8 1 hr
9 2 hr
10 4 hr
11 8 hr

** EXTENDED TIME DELAYS GREATLY REDUCE ENERGY SAVINGS

FUNCTION #6 – MICROPHONE (ACOUSTIC DETECTION)
Dual technology sensors prevent non-occupant sounds from resetting the time delay by dynamically reducing the microphones sensitivity at specific frequencies. In some environments, decreasing the sensitivity across all frequencies so that lights go off sooner, may be preferred. A unit’s microphone can also be disabled (effectively changing sensor to a PIR only version).

CHANGING MICROPHONE SETTINGS

  1. Press unit’s pushbutton 6 times, then wait two seconds. The white LED will blink back the number of current setting (from table on right).
  2. At any time after blink back starts, enter number of new setting by pressing the button equal times to choice from table.
  3. New setting will be saved after white LED blinks back new number 3 times. If blue LED double flashes at any time, start process over.

FUNCTION #6 – MICROPHONE (ACOUSTIC DETECTION) SETTINGS

SETTING # DESCRIPTION
2 Normal Operation

(default)
3| Reduced Sensitivity
4| Disabled

FUNCTION #7 – LED INDICATION
By default, the sensor blinks its white LED whenever it detects PIR motion. A unit with dual technology will also blink the LED white when it acoustically detects occupancy. Alternatively, the LED can be enabled to blink white for only PIR events and blue for an acoustic event.

CHANGING LED INDICATION SETTINGS

  1. Press unit’s pushbutton 7 times, then wait two seconds. The white LED will blink back the number of current setting (from table on right).
  2. At any time after blink back starts, enter new setting by pressing the button equal times to numbered choices.
  3. New setting will be saved after white LED blinks back new number 3 times. If blue LED double flashes at any time, start process over.

FUNCTION #7 – LED INDICATION SETTINGS

2| White LED for all occupancy, normal brightness (default)
---|---
3| NA
4| Disable LED
5| White LED for PIR, blue for Acoustic, normal brightness
6| NA

FUNCTION #14 – AUXILIARY RELAY OPERATION (-AR OPTION)
By default, the auxiliary relay provided on sensors with the -AR option will follow the state of the sensor’s white occupancy output wire (i.e. when the white wire is high indicating occupancy, the auxiliary relay is closed).

CHANGING THE AUXILIARY RELAY OPERATION

  1. Press unit’s pushbutton 14 times, then wait two seconds. The LED will blink back white the number of current setting (from table on right).
  2. At any time after blink back starts, enter new setting by pressing the button equal times to numbered choices.
  3. New setting will be saved after white LED blinks back new number 3 times. If blue LED double flashes at any time, start process over.

FUNCTION #14 – AUXILIARY RELAY OPERATION

2 Disabled
3 Relay closed when occupied (state follows white wire).

(default)
4| Relay closed when occupied and insufficient ambient light (state follows Blue wire). Available for SWX-21x-1-AR and SWX-23x-1-AR models.
5| Relay open when occupied (state opposite white wire)
6| Relay open when occupied and insufficient ambient light (state opposite blue wire). Available for SWX-21x-1-AR and SWX-23x-1-AR models.

DAYLIGHT HARVESTING & PHOTOCELL CONFIGURATION
Along with occupancy based control, units with an integrated photocell can provide on/off or inhibit-only control of lighting based on the amount of ambient light present. Units with the daylight harvesting option can also directly dim 0-10V lighting. See the model number table on page 1 for details on included features for each unit. Descriptions of modes are below.

DAYLIGHT HARVESTING

  • Recommend for spaces where it is important to not distract occupants (e.g., offices, classrooms).
  • Lights will gradually dim in order to maximize energy savings while maintaining desired overall lighting level. Ã Option to dim to low trim or turn lighting off.

ON/OFF PHOTOCELL CONTROL

  • Recommended for public spaces (hallways, entryways, etc) where fully switching of lighting off and on will not cause distraction of occupants.
  • Lights are switched off if ambient light level surpasses threshold and back on if level drops.

INITIAL INHIBIT ONLY PHOTOCELL CONTROL

  • Lighting is held off if sufficient ambient light level is present upon initial occupancy.
  • Lighting will turn on if light level drops below setpoint. Ã Once on, lighting will only turn off from vacancy or a manual switch, never from daylight.

FUNCTION #3 – PHOTOCELL OPERATIONAL MODE
To enable/disable the operation of the photocell (in equipped units), use the following procedure

CHANGING THE PHOTOCELL OPERATIONAL MODE

  1. Press and release the unit’s pushbutton 3 times, then wait 2 seconds. The white LED will blink back the number of the current setting (repeats 3 times before exiting).
  2. At any time after blink back starts, enter number of new setting from table on right (e.g., 3 for Occupancy + Daylight Harvesting).
  3. New setting is saved after white LED blinks back new number 3 times. If blue LED double flashes at any time, new setting was not saved and process must be repeated.

FUNCTION #3 – PHOTOCELL OPERATIONAL MODES

SETTING # DESCRIPTION MODEL # NOTES
2 Occupancy + On/Off Photocell Control (Photocell Enabled) Default for SWX-

21x-1 & SWX-23x-1
3| Occupancy + Daylight Harvesting to Off Photocell Control (Photocell Enabled)| Default for SWX-21x-1-D

SWX-23x-1-D

4| Occupancy + Initial Inhibit Photocell Control (Photocell Enabled)|
5| Occupancy only (Photocell Disabled)|
6| Occupancy + Daylight Harvesting to Low Trim (Photocell Enabled)|

PHOTOCELL OPERATION NOTES
During periods of occupancy, all sensors with an integrated photocell (models SWX-21x-1, SWX-23x-1) will signal power packs connected to its blue wire output to turn lighting off when the measured light level is high enough for 5 min. such that turning the lights off will not drop the level below the selected setpoint. During this 5 min. transition time the LED will blink blue at 0.5 second intervals. After lights are turned off, the sensor’s LED double blinks blue every 15 seconds as an indication that sufficient ambient light is the reason the lights are being held off. If the ambient light level falls below the setpoint for more than 45 seconds, lights will switch back on. During this transition time the LED also will blink blue at 0.5 second intervals.

FUNCTION #4 – PHOTOCELL SETPOINT
The minimum overall light level that is to be maintained in a space by the sensor is referred to as the “setpoint”. This value is user selectable or can be chosen by the Auto-Setpoint function that is built into the sensor.

SETPOINT CONFIGURATION

  1. Read through the below setpoint values list and note the number of the desired setpoint (e.g., default is 7 = 25 fc).
  2. Press and release the unit’s pushbutton 4 times, then wait 2 seconds. The LED will blink back the value of the current setting in two alternating digits
    • Blue LED = 10’s digit (1-12 blinks or rapid blink for 0)
    • White LED = 1’s digit (1-9 blinks or rapid blink for 0)
  3. At any time after blinking starts, enter number of new setting (see table below).
  4. New setting is saved after white LED blinks new setting back 3 times. If blue LED double flashes at any time, an error condition exists and process must be repeated.

FUNCTION #4 – SETPOINT VALUE TABLE

Sensorworx-SWX-222-1-Ceiling-Mount-Occupancy-Sensor
\(12\)

*AUTO-SETPOINT SELECTION DETAILS

  • Once setting 2 “Run Auto-Setpoint” has been selected (by following steps 1-4 on left), the sensor’s LED will alternate blue and white for 30 seconds. During this time user should move away from sensor.

  • Lights will then be cycled in order for sensor to calculate the controlled (artificial) light level. This is done by subtracting the light level with the lights off (relay open) from the light level with the lights on (relay closed).

  • A setpoint will then be chosen using the following conditions

  • If controlled level is less than 3 fc, the application is considered open loop and the setpoint will be set to 25 fc.

  • If controlled level is between 3 and 100 fc, setpoint will be set to that level times 1.25.

  • If controlled level is greater than 100 fc the setpoint will be set to 125 fc.

  • Unit will immediately start operating with new setpoint (i.e. blue LED may begin flashing indicating it will transition lights soon)

  • To check auto selected setpoint, press and release button 4 times. Setpoint will be blinked back in two alternating digits

    • Blue LE D = 10’s digit (1-9 blinks or rapid blink for 0)
    • White LED = 1’s digit (1-9 blinks or rapid blink for 0)

DIMMING CONFIGURATION SETTINGS

CHANGING DETAILED DIMMING SETTINGS
The settings listed in the below function tables can be adjusted using the following programming procedure.

  1. From the below tables of detailed functions, note the number (#) of the function to be modified. For example, the HIGH TRIM setting is #9.
  2. To access a particular function, press and release the programming button the number of time of the chosen function. For example, press the button 9 times to access the HIGH TRIM function.
  3. The LED will flash back white the setting number of the current value as it appears in each function’s detailed table below. For example, the default HIGH TRIM is setting #2 (10V)
  4. To change the setting number, press and release the button the number of times equal to the new setting #. For example, 3 times (for 9V).
  5. The LED will flash back white the new setting number as confirmation and will be saved after three confirmations. If LED double flashes blue at any time, start process over.

DETAILED DIMMING FUNCTION TABLES

FUNCTION #5 – TURN OFF SCHEME
The method by which a sensor with daylight harvesting (dimming) turns off connected lighting.

SETTING # VALUES NOTES
2 Drop to Off Dimming output drops to low trim level & connected power

pack’s relay is signaled to open (i.e. blue wire goes low).
3| Fade to Off (defautl)| Dimming output fades to low trim and connected power pack’s relay is signaled to open (i.e. blue wire goes low).
4|

Fade to 0V

| Dimming output fades to low trim level and then drops to 0 volts (e.g. below a connected driver’s electronic off level). The connected power packs’s relay is signaled to remain closed (i.e. blue wire stays high).
5|

Fade to Low Trim

| Dimming output fades down to low trim level and the connected power packs’s relay is signaled to remain closed (i.e. blue wire stays high).
6|

Drop to Low Trim

| Dimming output drops down to low trim level and the connected power packs’s relay is signaled to remain closed (i.e. blue wire stays high).
7| Drop to OV| Dimming output drops to 0 volts (e.g. below a connected driver’s electronic off level and the connected power packs’s relay is signaled to remain closed (i.e. blue wire stays high).

FUNCTION #9 – HIGH TRIM
The maximum voltage to which the daylight harvesting sensor is allowed to raise its dimming output when measuring a low level of ambient light.

SETTING # VALUES NOTES
2 ~10 VDC                          (default)
3 ~9 VDC

Light output at each voltage level depends on driver/ballast and luminaire.

4| ~8 VDC
5| ~7 VDC
6| ~6 VDC
7| ~5 VDC

FUNCTION #10 – LOW TRIM
The minimum voltage to which the daylight harvesting sensor is allowed to reduce its dimming output when measuring high levels of ambient light.

SETTING # VALUES NOTES
2 ~0 VDC
3 ~1 VDC

Light output at each voltage level depends on driver/ballast and luminaire.

4| ~2 VDC
5| ~3 VDC                          (default)
6| ~4 VDC
7| ~5 VDC
8| ~6 VDC

FUNCTION #11 – FADE OFF TIME
Adjustable time interval for lights to ramp down to off. Note that the signal on the blue output wire will wait until the Fade Off Time has completed before transitioning from high to low.

SETTING # VALUES
2 0.75 Sec
3 1.5 Sec                           (default)
4 3 Sec
5 5 Sec
6 15 Sec
7 Disabled

FUNCTION #12 – FADE ON TIME
Adjustable time interval for lights to ramp up when connected occupancy sensors signal an occupied state.

SETTING # VALUES
2 0.75 Sec
3 1.5 Sec                          (default)
4 3 Sec
5 5 Sec
6 15 Sec
7 Disabled

SENSORWORX | 2a Research Parkway, Wallingford, CT 06492 203.678.4224 | www.sensorworx.com
© 2022 BLP Technologies, Inc. All rights reserved.