SEIKOM ELECTRONIC RLSW6AR Air Flow Monitor Instruction Manual
- June 13, 2024
- SEIKOM ELECTRONIC
Table of Contents
Air flow monitor
Manual for Air flow monitor
RLSW6 and RLSW6AR Our products correspond to the requirements of the
European guidelines
WEEE 2012/19/EU – RoHS 2011/65/EU ****
Technical Data:
Type | RLSW6 – RLSW6AR | RLSW6 – RLSW6AR |
---|---|---|
Article No. | 77566A – 77566AR | 77567A – 77567AR |
supply voltage | 24VDC/AC | 230VAC |
supply voltage tolerance | +/-5% | +/-5% |
signal, supply voltage | green LED | green LED |
power consumption | 5VA | 5VA |
ambient temperature | -20..+60°C | -20..+60°C |
signal output, flow | changer | changer |
current- and contact load | 250VAC, 8A, 2kVA | 250VAC, 8A, 2kVA |
minimum switching load | 10mA / 5V DC | 10mA / 5V DC |
switch function at flow | relays connects | relays connects |
signal at flow | yellow LED | yellow LED |
start-up delay | 15-120s (potentiometer) | 15-120s (potentiometer) |
display start-up delay | – | – |
break down delay | 2-20s (potentiometer) | 2-20s (potentiometer) |
media temperature | -10..+80°C | -10..+80°C |
temperature gradient | 15K/min | 15K/min |
switch point | potentiometer | potentiometer |
measurement range | 0.1..25m/s | 0.1..25m/s |
sensor | F9 | F9 |
sensor accessory | flange | flange |
electrical connection | 11clamps, 2.5mm² | 11clamps, 2.5mm² |
protection class housing | IP65 | IP65 |
protection class sensor | IP67 | IP67 |
housing dimensions | L= 55mm; W = 165 mm; H=85mm | L= 55mm; W=165mm; H=85mm |
mark of conformity | CE | CE |
Installation Instruction (F9):
- The sensor should be mounted in such a way that the air flow passes through the lateral opening. The marking is intended as an assembly aid.
- Installation where there is low turbulence, if possible.
- Do not install directly behind bends (distance approx 10x bend radius).
- Install the probe in the middle of the duct where possible (distance at least 1/3 of the duct diameter from the wall).
- Do not install directly behind the heating register (rapid changes in temperature may lead to the measured values being falsified).
Cleaning (F9):
The airflow sensor contains a sensor element which is sensitivity to
mechanical loading and which must not be touched with hard and pointed
objects. Any cleaning that may be necessary is possible in water (also with
addition of detergents). Let the unit drip off and dry renewed start-up.
Value table relays-contacts:
| relays “Alarm”| relays “flow”
---|---|---
| clamps 3/4| clamps 4/5| clamps 6/7| clamps 7/8
no flow| open| connected| open| connected
work flow| connected| open| connected| open
Electrical connection (voltage off):
supply: green LED
alarm: yellow LED, left relay on PCB
flow: yellow LED, right relay on PCB
The RLSW6 has on failure of airflow an error memory that can only be resettled
by pressing the button inside the unit or disconnecting the power supply.
The RLSW6AR features instead of the error memory an automatic reset, which
sets the device back to monitoring function after an interruption of airflow.
Attention!!
Connection and commissioning must be performed by properly authorized and
qualified personnel!
Connection to mains supply (L, N) must be made by means of a protected
isolating switch with the usual fuses. As a matter of principle, the General
VDE Regulations must be complied with (VDE 0100, VDE 0113, VDE 0160).
He air flow monitor RLSW6 is used to watch ventilators or regulating flaps,
flow depending humidifiers and electrical heating registers regarding to
DIN57100 part 420 or DDC-installations.
More installation areas: Exhaust and supply air.
Function:
After connecting supply voltage to the device (green LED enlightens) and the work flow being switched on (red LED enlightens), the relays connects and the applied aggregate will be released. Harmful heating or humidifying is safely prevented. If the work flow is not reached within the start-up delay the relays will connect to “Alarm” on clamps 4/5. The flow will drop after the break down delay is elapsed. Clamps 6/7 open (heater off) and the clamps 4/5 will be closed at the same time. This condition will be saved. With pushing “Reset” the device will be set to initial state and the start-up delay will run down again.
Devices with start-up delay:
There are applications in which the ventilators take some time to generate
work flow. In order to prevent false alarms in this case, the RLSW6 has a
start-up delay (15-120s). In this time the relay “Strömung” connects and the
red LED “flow” enlightens. We suggest to switch on the ventilators as well as
the flow monitor at the same time.
Frequently asked questions:
Problem | Cause | Solution |
---|---|---|
RLSW does not operate | wrong or none supply voltage | check the supply voltage |
RLSW does not react on flow | sensor is installed wrongly | check the sensor’s |
installation
RLSW shows unusual response| sensor is highly polluted| clean the sensor,
refer to the regarding page in this manual
RLSW does not react on flow| no flow| press reset button
Mistakes and misprints are not to be excluded. All information „without
guarantee“.
03/2022