MANROSE FAN7194 Heat Transfer Touch Screen Controller Instruction Manual
- June 13, 2024
- MANROSE
Table of Contents
- MANROSE FAN7194 Heat Transfer Touch Screen Controller
- Warning
- Installation
- Wiring Diagrams
- Home Screen Icons
- Fan and Fan Speed Setting
- Settings Guide
- System Operating Settings
- Modes
- Commissioning and Testing
- Advanced Settings
- Technical Specifications
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
MANROSE FAN7194 Heat Transfer Touch Screen Controller
Definitions
Before use please read and understand these defi nitions.
- WARNING and/or the use of the symbol refers to conditions where the possibility of injury, or death, exists if the procedure is not followed.
- CAUTION indicates the possibility of damage to the equipment, installation or premises if a procedure is not followed.
- NOTE provides additional information intended to clarify points, procedures or instructions.
Warning
- Please read all instructions carefully before commencing installation.
- This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
- Children should be supervised to ensure that they do not play with the appliance.
- Precautions must be taken to avoid the backflow of gases into the room from the open flue of gas or other open-fire appliances when mounted in outside walls or soffits.
- Isolate the mains supply before making any electrical connections. This system should be installed by a registered electrician.
- A means of mains power isolation must be installed in the circuit for the purpose of safe access for any internal cleaning, recalibration or maintenance.
- All electrical, electronic and mechanical parts must be installed, and all ducting secured, before applying mains power.
- There are no isolated (safety extra low voltage) terminals incorporated. Please treat all terminals as being mains live.
Important
- If it is intended to install an air transfer system such as HeatTrans into a room where gas appliances are used for the heat source, the gas fire installation company must be consulted before undertaking installation. Section G4/ 2.2 (Mechanical Ventilation) of the NZ Building Code refers to certain safety criteria which should be considered when installing mechanical ventilation in a room where gas appliances are used. The gas heating installation company can advise on these aspects.
- The system is not designed for use with heat pumps.
- With certain models of solid fuel fires, negative pressure can cause smoke from the fire place to enter the room where the fireplace is operating.
- If you have a fireplace that uses air from the room for combustion, please ensure that make-up air is available to replace the air that is exhausted by the HeatTrans system.
- The use of a door vent can assist in circulating the air throughout the room.
Caution
- All wiring must comply with national wiring rules.
- Any changes or modifications made or attempted to this product, without the prior written approval of the manufacturer, will void any and all stated warranties.
- Take appropriate safety measures when cutting hazardous building materials.
Installation
Heat Transfer Touch Screen Controller
- Install on an inside wall at eye level in the heat source room, preferably opposite the heat source, where the air temperature can be sensed as accurately as possible and not be adversely affected by direct solar radiation or convection currents.
- DO NOT install in wet/damp areas (ie. laundry or bathrooms), on hot surfaces, in convection currents, exposed to direct sunlight or locations which are not generally affected by changes in the room temperature.
- DO NOT install near any localised heat source.
- Cut an opening in the wall for flush box and mount it.
- Run the electrical cable from the roof cavity down to the flush box.
- Wire the cable to the power module of the touch screen controller, located on the back.
- Separate the front screen of the touch screen controller from the back module. Carefully insert a flat head screwdriver into the slot and gently lever the screwdriver handle upwards.
- Mount the power module to the flush box using screws provided.
- CAUTION: Using incorrect screws or not tightening screws sufficiently may cause damage to the product when re-assembling.
- Ensure the circuit board on the back module is centred so the connectors to the front screen can line up.
- CAUTION: Forcing the controller back together without aligning the connectors properly may cause damage.
- Carefully attach the front screen to the back power module. Align the top edge, rock in, and listen for a click.
Wiring Diagrams
Home Screen Icons
- System Fan Speed
- Heat Transfer Mode
- Summer Vent ON
- Heat Transfer ON
- Recycle ON
- Temperature Sensing ON
- Home and Power
- Settings
- Up
- Select
- Down
- Set Temperature
- Current Room Temperature
- Key Lock ON
- Alert
- Time
- Scheduler Period and Day
- Heat Transfer mode selections are AUTO or MAN (manual).
- When an electronic fault in the system occurs, the alert icon will appear and the applicable error code(s) will be displayed instead of the time.
- Time is displayed in a 24 hour clock format.
Button Functions
- ****Power OFF/ON or discard selections and return to Home Screen.
- ****From Home Screen enter setting screen or return to previous setting option.
- ****Scroll through setting options and change setting values.
- ****Save setting selection and go to next setting option.
Screen Highlights
Fan and Fan Speed Setting
All HeatTrans touch screen controllers are set to the three fan speed option by default and the three fan speeds available – HIGH, MEDIUM and LOW. If your fan does not have three speeds, you can follow the guide below to alter the fan speed to fan speed option or fan speed option and as required.
Settings Guide
Auto Operation and Temperature (TEMP) Setting
- On the Home Screen, press SETTINGS and then UP , or DOWN ****, to toggle to ON
- Press SELECT ****to enter VENTILATION mode
- Press UP , or DOWN , to toggle to AUTO operation and follow the guide below to adjust the temperature setting.
- Alternately, if already in ON and on the Home Screen, press SELECT ****to toggle directly to AUTO operation and follow the same guide below to adjust the temperature setting.
Fan speed will adjust automatically based on the indoor air temperature. If system is in BOOST mode, the fan will operate at the speed set for that mode.
Manual (MAN) Operation and System Fan Speed Setting
- On the Home Screen, press SETTINGS and then UP , or DOWN ****, to toggle to ON
- Press SELECT ****to enter VENTILATION mode
- Press UP , or DOWN , to toggle to MAN operation and follow the guide below to change the system fan speed.
Fan speed will remain constant at the speed set. If system is in BOOST mode, the fan will operate at the speed set for that mode.
Fan OFF Setting
- On the Home Screen, press SETTINGS and then UP , or DOWN ****, to toggle to OFF
- Press SELECT ****to save the fan OFF setting.
Key Lock Setting
When Key Lock is ON, system settings cannot be changed
- Press UP and DOWN together for 3 seconds, until the KEY LOCK icon is displayed, to confirm that the system is locked.
- Press UP and DOWN together for 3 seconds, until the KEY LOCK icon is not displayed, to confirm that the system is unlocked.
System Time-Date Settings
System Time-Date Settings must be entered before Scheduler start times for
HEAT TRANSFER can be set.
-
On the Home Screen, press SETTINGS **for 3 seconds to enter Time-Date Settings and follow the guide below to complete.
NOTE:** Settings shown are examples only -
Press HOME ****at any stage to exit and enter Scheduler Settings.
-
Press SETTINGS ****at any stage to return to the previous screen.
System Operating Settings
Scheduler Settings
Setting the Scheduler is only necessary if you want HEAT TRANSFER to operate
for predetermined times during each of the four periods available every 24
hours. Each period of time starts with the scheduled start time for that
period and ends at the start time for the next scheduled period.
-
On the Home Screen, press SETTINGS for 3 seconds then press HOME to enter Scheduler Settings and follow the guide below to complete.
NOTE: Settings shown are examples only. -
Press HOME ****at any stage to exit Scheduler Settings and return to the Home Screen.
-
Press SETTINGS ****at any stage to return to the previous screen.
Period OFF/ON Schedule
Set HEAT TRANSFER mode to AUTO operation (see page 8). Fan speed will adjust
automatically based on the indoor air temperature.
-
On the Home Screen, press SETTINGS **to enter Period OFF/ON Schedule and follow the guide below to complete the fan OFF/ON settings for each of the four periods available in a 24 hour period.
NOTE:** Settings shown are examples only. -
Press HOME ****at any stage to exit Period OFF/ON Schedule and return to the Home Screen
-
Press SETTINGS ****at any stage to return to the previous screen
Period Schedule Log
Record your scheduled start times and OFF/ON status in the Period Schedule Log
below.
Date| Period 1| Period 2| Period 3|
Period 4
---|---|---|---|---
Start| OFF| ON| Start| OFF| ON| Start|
OFF| ON| Start| OFF| ON
| | | | | | | | | | | |
| | | | | | | | | | | |
| | | | | | | | | | | |
| | | | | | | | | | | |
| | | | | | | | | | | |
| | | | | | | | | | | |
Modes
Boost
BOOST enables you to immediately override fan speed settings and boost fan
speed to maximum.
- On the Home Screen, press SELECT ****for 3 seconds and system’s fan will boost to maximum speed.
- In BOOST mode, the time segments will become a count down to the end of the BOOST mode.
- A quick tap of SELECT ****on the Home Screen will exit BOOST mode.
Commissioning and Testing
- Inspection Checklist
- Controller is displaying temperatures correctly.
- Controller is configured to match the number of speeds the fan motor has.
- Fan operates on all speeds. Put fan onto high speed to continue inspection.
- There are no leaks in the ducting.
- Diffusers are open and not whistling.
- System is set to AUTO operation.
Advanced Settings
Advanced Setting Selection
Advanced Settings can be changed at any time using the guide below. This guide
must also be used to enter the password at setting 020 before settings 021 and
above can be changed.
Advanced Setting Menu
SETTING | DESCRIPTION | RANGE | DEFAULT | NOTE |
---|---|---|---|---|
000 | Hardware Version | N/A | 3.1 | |
001 | Firmware Version | N/A | 3.4 | |
002 | Temperature – Room | -10°C – 10°C | -2.5°C | 1 |
003 | Reserved | N/A | N/A | |
004 | Screen Brightness – Maximum | 0 – 100% | 80% | |
005 | Screen Brightness – Minimum | 0 – 100% | 20% | |
006 | Boost Time | 0 min – 60 min | 20 min | |
007 | Reserved | N/A | N/A | |
008 | Reserved | N/A | N/A | |
009 | Reserved | N/A | N/A | |
010 | Reserved | N/A | N/A | |
011 | Reserved | N/A | N/A | |
012 | Heat Transfer Speed Threshold – High | 0°C – 10°C | 5.0°C | |
013 | Heat Transfer Speed Threshold – Low | 0°C – 10°C | 2.0°C | |
014 | Reserved | N/A | N/A | |
015 | Reserved | N/A | N/A | |
016 | Reserved | N/A | N/A | |
017 | Reserved | N/A | N/A | |
018 | Reserved | N/A | N/A | |
019 | Restore 000 – 018 Default Settings | 0 – 1 | 0 | 1 = restore |
020 | Enter Installer Password: | 0 – 100 | 0 | 2 |
021 | Summer Vent Kit Mode | 0 – 1 | 0 | 1 = enabled |
022 | Reserved | N/A | 1 | Do not change |
023 | Reserved | N/A | N/A | |
024 | Reserved | N/A | N/A | |
025 | Fan Type | 0 – 1 | 0 | |
026 | Number of Fan Speeds | 1 – 3 | 3 | |
027 | Reserved | N/A | 1 | Do not change |
028 | Touch Activation Setting – ****Home/Power | 15 – 125 | 55 | 3 |
029 | Touch Activation Setting – ****Settings | 15 – 125 | 55 | 3 |
030 | Touch Activation Setting – ****Up | 15 – 125 | 60 | 3 |
031 | Touch Activation Setting – ****Select | 15 – 125 | 60 | 3 |
032 | Touch Activation Setting – ****Down | 15 – 125 | 60 | 3 |
033 | EC Fan Speed – Low | 0 – Medium | 30% | |
034 | EC Fan Speed – Medium | Low – High | 50% | |
035 | EC Fan Speed – High | Medium – Boost | 70% | |
036 | EC Fan Speed – Boost | Boost – 100 | 100% |
- If your room temperature reading is inaccurate, use this setting to calibrate.
- Settings 021 and above are installer only settings and are only accessible after the installer password (setting 020 = ) has been entered and set.
- CAUTION: It is possible to render buttons inoperable and irrecoverable by adjusting the touch activation settings. Adjust at your own risk. The lower the value the more sensitive the button, the higher the value the less sensitive the button.
Troubleshooting
An ALERT icon and error code will appear on the Home Screen when there is an
electronic fault in the system. Contact Simx, 09 259 1662, for assistance.
Technical Specifications
TOUCH SCREEN CONTROLLER V3.4
Temperature Range| 5-35ºC adjustable
Display Resolution| 0.1ºC
Operating Voltage/Frequency| 220-240V AC, 50Hz
Switching Voltage| 240V AC Max
Switching Current| 3A max resistive load
Operating Temperature| 0 to 40ºC
Operating Humidity| 5-90% non condensing
Live Output Isolation| Relay
Output Control| Relay / 0-10V DC
Display| 3.5” digital LCD touch screen
Approval| All relevant AS/NZS standards
EMC Approval| All relevant AS/NZS standards
Specifications are subject to change without notice
4 Capital Place, Carrum Downs VIC 3201 Australia
p: 1300 665 926
e: info@ventair.com.au
w: https://manrose.com.au