Winterwarm WWH-LT Unit Air Heater Instruction Manual
- June 13, 2024
- Winterwarm
Table of Contents
Winterwarm WWH-LT Unit Air Heater Instruction Manual
Unit air heater
TYPE WWH-EC; WWH-LT
THIS DOCUMENTATION MUST ABSOLUTELY BE READ BEFORE STARTING THE INSTALLATION. INSTRUCT USER AND LEAVE THIS DOCUMENT WITH HEATER FOR REFERENCE.
General
This user’s guide is meant for the installer and if necessary for the user. It’s a reference to operation and installation of the WWH-EC and WWHLT. For a safe and effective function of this appliance it is strictly necessary that this manual is applied correctly.
Description
The WWH is an effective in-direct fired heater.
The heat exchanger consists of copper tubes and aluminium fins. This is an
approved design for an optimal heat exchange.
The grill has been designed to accomplish an optimal air displacement at the lowest possible sound level.
With a (stepless) regulator or external voltage source is it possible to reduce the air output and noise level.
Function
The WWH is in fact a radiator with a fan on the back. When hot water is pumped
through the radiator, and the fan is on, the heater will blow hot air. The
heater will give no heat when the fan is off, no matter there is hot water
running through the radiator or not.
The heater requires a control (thermostat) to arrange the supply of hot water and to switch the fan on/off.
There are several options for control, this will be described later in this manual.
For a better air distribution it’s always better to choose 2 or more heaters instead of 1 heater. For example, it’s better to select two 30kW heaters, instead of one 60kW heater.
Matching capacity hot water boiler and WWH
In case the capacity of the boiler is higher than that of the WWH, the boiler
won’t be able to release all the heat produced. This will cause the boiler to
go on and off (commute). As a consequence of this the installation won’t be
able to reach the temperature demanded. For small installations it is
advisable to select a WWH which has an higher output than the boiler itself.
Guarantee
Operation and /or installation of appliances not according to this manual can
imply invalidation of guarantee.
Technical feature
Table with data
The WWH-EC is available in 8 models with capacities that differ from 10 to 80
kW. The range of 10-80 kW heaters is subdivided in 3 basic sizes. The type
number of the appliance starts with the housing model (1,2 and 3). See table
below for exact dimensions.
Type| 115EC| 120EC| 235EC| 245EC| 350EC|
365EC| 380EC
---|---|---|---|---|---|---|---
Model size| 1| 1| 2| 2| 3| 3| 3
A| 510,5| 510,5| 692,5| 692,5| 863,5| 863,5| 863,5
B| 509| 509| 693| 693| 864| 864| 864
C| 46,5| 44| 34| 42| 33| 33| 34
D| 435,5| 435,5| 585| 585| 756| 756| 756
E| 435| 435| 585| 585| 756| 756| 756
F| ¾”| ¾”| ¾”| 1”| 1”| 1”| 1”
G| 91,75| 72,75| 93,5| 82,75| 107,25| 107,25| 93,75
H| 327| 346| 504,5| 515,5| 652| 652| 666,5
I| 91,75| 91,75| 94,5| 94,25| 104,25| 104,25| 103,25
J| 320| 320| 363| 363| 357,5| 357,5| 357,5
K| 45| 45| 83| 83| 66,8| 66,8| 66,8
L| 70| 69| 86| 86| 93| 93| 86,5
M| 39| 44| 43,5| 45| 35| 35| 45,5
N| 54,5| 54,5| 76,5| 76,5| 87| 87| 87
O| 160| 160| 160| 160| 160| 160| 160
P| 80| 80| 101| 101| 78| 78| 78
Q| 254,5| 254,5| 346,5| 346,5| 432| 432| 432
R| 160| 160| 181| 181| 158| 158| 158
Heating capacity (*)| kW| 14.7| 19.7| 27.8| 42.4| 46.4| 54.4| 76.7
Air output| m3/h| 2200| 1950| 3900| 3500| 6150| 8500| 7600
Throw horizontally| m| 16| 14| 22| 19| 21| 25| 21
Throw vertical| m| 5| 5| 7| 6| 7| 8| 7
Electrical supply| V| 230| 230| 230| 230| 230| 230| 230
Consumed current| A| 1.0| 1.1| 0.9| 1.1| 1.5| 1.8| 1.4
Power consumption| W| 111| 123| 200| 250| 320| 400| 308
Weight (incl. water)| kg| 20| 21| 31| 32| 44| 61| 65
Water connection (ext.)| G| ¾| ¾| ¾| 1| 1| 1| 1
Water sided pressure loss| kPa| 3| 3| 4| 5| 4| 7| 9
Recommended susp. height| m| 2.5| 2.5| 2.5| 2.5| 2.5| 2.5| 2.5
Noise level (5m)| dB(A)| 35-54| 35-54| 35-59| 35-57| 35-60| 35-56| 35-54
(*) at water temperature of 90°/70° and environmental temperature of 15°C.
Table with data WWH-LT
The WWH-LT is available in 4 models. Besides heating through a boiler, the
WWH-LT has specially been developed for use in a low-temperature installation.
In addition the WWH-LT model can be used for cooling through a heat pump or a
cooling pump.
Type | 110LT | 220LT | 330LT | 340LT |
---|---|---|---|---|
Model size | 1 | 2 | 3 | 3 |
A | 510,5 | 692,5 | 863,5 | 863,5 |
B | 508 | 693 | 864 | 864 |
C | 46,5 | 35 | 28,5 | 28,5 |
D | 435,5 | 585 | 756 | 756 |
E | 435 | 585 | 756 | 756 |
F | ¾” | 1” | 1” | 1” |
G | 102,75 | 111,25 | 121,5 | 121,5 |
H | 330 | 495 | 647 | 647 |
I | 77,75 | 86,25 | 95 | 95 |
J | 320 | 363 | 357 | 357 |
K | 45 | 83 | 65,5 | 65,5 |
L | 124 | 142 | 144 | 144 |
M | 60,5 | 60 | 65,5 | 65,5 |
N | 54,5 | 76,5 | 87 | 87 |
O | 160 | 160 | 160 | 160 |
P | 80 | 95,5 | 78 | 78 |
Q | 254,5 | 364,5 | 432 | 432 |
R | 160 | 175,5 | 158 | 158 |
Type | 110 LT | 220 LT | 330 LT | 340 LT |
---|---|---|---|---|
A | 37,75 | 40,75 | 51,75 | 51,75 |
B | 190 | 214 | 208,75 | 208,75 |
C | 19 | 19 | 19 | 19 |
D | 23,75 | 20,25 | 24,25 | 24,25 |
E | 42,5 | 42,5 | 42,5 | 42,5 |
(*) at water temperature 90°C/70°C and ambient temperature of 15°C
(**) at ambient temperature 28°C
Type | Unit | 110LT | 220LT | 330LT | 340LT |
---|---|---|---|---|---|
Capacity * 45°/35°C | kW | 8.3 | 19.4 | 28.6 | 37.9 |
Cool capacity ** at 7°/12°C | kW | 6.6 | 16.5 | 19.2 | 32.1 |
Cool capacity ** at 15°/18°C | kW | 3.8 | 8.8 | 12.8 | 17.8 |
Cool capacity ** at 16°/19°C | kW | 3.4 | 7.9 | 11.7 | 16.1 |
Air output | m3/hr | 1850 | 4150 | 5450 | 8850 |
Throw horizontally | m | 14 | 21 | 20 | 25 |
Throw vertical | m | 5 | 7 | 7 | 8 |
Electrical supply | V | 230 | 230 | 230 | 230 |
Consumed current | A | 1.1 | 2.3 | 1.5 | 3.2 |
Power consumption | W | 118 | 515 | 320 | 718 |
Weight (incl. water) | kg | 22 | 34 | 66 | 68 |
Water connection (ext.) | G | ¾ | 1 | 1 | 1 |
Water sided pressure loss | kPa | 4 | 11 | 30 | 30 |
Recommended susp. height | m | 2.5 | 2.5 | 2.5 | 2.5 |
Noise level (5m) | dB(A) | 35-54 | 35-64 | 35-60 | 35-62 |
User’s restrictions
- Work pressure: max. 5 bar.
- Water temperature: max. 100°C; min 4°C. (freezing danger!)
- Environment temp.: max. 40°C; min 4°C. (freezing danger!)
- Protection grade : IP00B
Note : frost can cause the internal copper tubes in the exchanger to burst, the exchanger will leak. No warranty on this!
Pre-check
Before installing the heater, please check if the heater is in accordance with the order, and whether it suites the local and present provisions (electrical supply etc.). The heater also has to meet local and national legislations.
After installation ensure that the appliance is no hazard for persons or can cause damage in terms of moisture, dust, inflammable or corrosive gases, smoke and/or combustible materials.
The competent installer must make sure that the heater functions correctly and must instruct the user about safe operation of the heater.
Installation
Suspension
The WWH is provided with eight M10 suspension points on the side panels.
Use preferably the specially designed cantilever brackets or the ceiling
mounting-set.
Take care that the heater is placed stable and that there is no tension on the
water sided connections.
In case de WWH-LT is used for cooling, make sure that the condensate discharge
pipe is on the bottom and that the air heater has been placed upright,
enabling condensate to run out of the discharge system.
Condensation drain WWH-LT
Wall setup : The pipe connections for water should always be horizontal, with a view to venting of the internal pipes. The heater can be turned over slightly, but the heater may absolutely not hang askew.
Place the heater in such manner that, the return connection (cold water) is at the lowest point. It’s important to place the venting in the duct near the heater.
Ceilling set up: Again the pipe connections to the heater should be horizontal, to enable venting of the internal tubes.. Place the heater high enough (minimally 2,5m) to avoid draught. If necessary use our outlet cone or the 4-way down flow plenum. Application of a plenum will decrease the throw with factor 4.
The WWH-LT can’t be installed in a celling setup in case it is also used for cooling. This will cause condensate dripping down from the air heater.
Hanging options WWH
Water connections
Connections for hot water supply and return (two times ¾ inch or two times 1 inch) are marked with a red and a blue sticker. Red is water supply and blue is water return. Do not twist these connections, the heater will not give the desired output.
The WWH is not provided with a standard venting. There is the possibility to place one when it is desired.
Prevent mechanical tension on the connections, this will cause leakage.
Warning: Prevent damage to the heater, hold the connections with pliers to avoid twisting of welded parts of the connections. Do not put excessive force! Internal welds may break and cause leakage.
Water pipe installation
Blow-out options
Type | 1 | 2 | 3 |
---|---|---|---|
A | 516 | 693 | 864 |
B | 163 | 183 | 222 |
The discharge grille, 4-sided discharge plenum and the vertical blades can be easily removed and directed to the desired discharge direction. When using a plenum, the throw decreases by a factor of 4! Make sure that the exchanger is not damaged at all times.
Ensure free intake and discharge options.
Make sure that there is a good air exchange in the room (enough fans), but that people present are not bothered by annoying air currents. Always have the heaters in a wall arrangement blow on the cold surfaces.
Electrical connection
230Vac supply
The installation must comply with all applicable local and/or national
standards.
There should be a suitable electrical group with a main fuse. There is an
electrical diagram further on in this guide.
The supply is 230Vac (50 Hz) with earth.
Isolation switch or power plug
The heater has to be equipped with a 230 Volt isolation switch or power plug.
This switch should disconnect phase and neutral (not earth) and have a 3mm
contact opening at least. Switches or powerplugs must be accessible at all
times.
General functioning of the unit
The WWH is simply described as a radiator with a ventilator at the back. If there is hot water flowing through the radiator, and the heater is on, the heater will blow hot air. But when hot water is flowing through the radiator and the heater is off, the heater will not discharge hot air. If the fan is turned on, but the boiler water is cold, there could be draught. This must be prevented.
The installation should have some kind of control to make turning on/off the hot water boiler and the fan of the WWH separately, possible. The WWH and the boiler are 2 separate systems. Both systems need to be controlled. There are several ways to do this. It depends on the situation and needs of the user, what combination of controls will work best.
Connecting options
Variants
WWH with EC motor is available in several variants.
Alternative 1, motor with internal connectors
Alternative 2, motor without connectors:
Combinations with a stepless switch.
To reduce the noise level of the WWH, it is possible to install a stepless fan
switch. This switch regulates the fan speed of the WWH. Please note that if
the fan speed is lower, the heat output from the heater will also be lower.
There are 3 alternatives for speed control:
- Maximum speed only (factory setting)
- With speed regulation
- External via 0-10V
Only maximum speed (factory setting):
This can be achieved with a cable jumper on the motor between [10V] and [E1]
or between [T2] and [S3] on the 6-pin connector. This will cause the fan to
run at maximum speed permanently. This bridge has been connected by default.
With a speed control (potential meter)
A 3-wire speed control (GA3955) or other potential meter can be connected to:
- plug [10V] [GND] and [E1] in the fan motor
- or to GND[T1], 10V[T2] and 0-10V IN[S3] in the 6-pin connector.
Make sure the potentiometer has a resistive value of 10kΩ.
0-10V External control
An external 0-10V current can be set:
- on connectors [GND] and [E1] in the fan motor
- or on GND[T1] and 0-10V IN[S3] on the 6-pin connector
Multiple WWHs on one control
Eight WWHs can be connected to 1 speed controller.
The 10V[T2] power supply must only be required from 1 WWH, the others must not
be connected!
Connection with only one room thermostat
This setting is only possible when there is a continuous hot water supply. The
hot water boiler must have its own control.
Operation:
The on/off room thermostat turns on the WWH’s fan when there is a need for
heat. The fan will blow air over the heat exchanger. If the water is hot, the
heater will emit hot air. If the water is cold, the heater will blow cold air,
which can be experienced as a draft.
The boiler must be switched on/off separately. Therefore, a second room
thermostat is needed. The thermostat IW3961 is a special thermostat with gold-
plated contacts that controls the low steam in 0- 10V circuit can switch.
Connection with contact thermostat.
This setting is used if the boiler’s thermostat is in the same room as the
WWH.
Operation:
The contact thermostat closes if the water has reached the preset temperature.
In this situation, the WWH will only discharge warm air.
The boiler thermostat will switch on the boiler. The boiler will pump hot
water around. The contact thermostat on the WWH will close if the water is hot
enough. The fan will blow hot air out into the room. If the boiler is switched
off by the boiler thermostat, the water will cool and the contact thermostat
will open.
Connection with room thermostat combined with contact thermostat
This option is used when the boiler is controlled by its own thermostat and
there is still a hot water supply.
Operation:
The on/off thermostat changes when there is a need for heat. The contact
thermostat will not close (connect) until the water has reached the preset
temperature. In this situation, WWH’s fan will transport hot air. This will
prevent drafts.
The boiler must be switched on and off separately.
Maintenance and operation
Caution:
Make sure that you have turned off the power group that you are working on.
The heater must be earthed.
Maintenance
Especially in dusty spaces, it’s important to clean the heater regularly. If
the heat exchanger is heavily covered by dust-traps it will not displace the
heat sufficiently. Use a vacuum cleaner or compressed air.
Avoid damage to the fins. Clean also the fan and the fan grill
Safe operation
The heater is controlled by the room thermostat and/or the fan (speed)
control. There are no controls on the heater itself. Depending on the
installation, the user can make following settings:
- Control main or isolation switch
- Turn up and down room thermostat
- Turn up and down contact thermostat
- Change fan speed with voltage regulator or externa;0-10V signal
Adjusting direction of the air outlet is normally no user’s action, this is done by the installer.
Frost damage
ATTENTION: frost damage!
Do not set the room thermostat lower than 5°C. Freezing of the exchanger or
the tubes will cause irrevocable damage to the installation. A constant supply
of hot water from the boiler must be ensured. Frost damage is excluded from
warranty claims!
Water temperatures/ air volumes
The conversion diagram shows heater capacities in KW under different conditions. These conditions may be:
- Water temperature, for example 90/70°C (Regime)
- Air temperature sucked by the fan (Air temp)
WWH-EC capacities at several water temperatures
In situations where other inlet- and return water temperatures are applied,
the original (registered) heater capacity should be multiplied with the value
in the table below. The WWH-EC is not classified for steam applications.
| Air temperature
---|---
Water temperature| 0°C| 5°C| 10°C| 15°C| 18°C| 20°C
90/70°C| 1.30| 1.19| 1.10| 1.00| 0.94| 0.91
80/60°C| 1.11| 1.01| 0.91| 0.82| 0.76| 0.73
70/50°C| 0.92| 0.82| 0.73| 0.64| 0.56| 0.55
60/40°C| 0.73| 0.64| 0.54| 0.45| 0.40| 0.37
50/30°C| 0.54| 0.45| 0.37| 0.27| 0.22| 0.18
WWH-LT capacities at several water temperatures
In situations where other inlet- and return water temperatures are applied,
the registered heater capacity should be multiplied with the value in the
table below. The WWH-LT is not classified for steam applications.
| Air temperature
---|---
Water temperature| 0°C| 5°C| 10°C| 15°C| 18°C| 20°C
45/35°C| 1.76| 1.51| 1.25| 1.00| 0.81| 0.74
50/30°C| 1.56| 1.30| 1.07| 0.78| 0.64| 0.52
60/40°C| 2.11| 1.85| 1.56| 1.30| 1.16| 1.07
70/50°C| 2.66| 2.37| 2.11| 1.85| 1.62| 1.59
Example
What is the output of a WWH 235-EC with a water supply (regime) of 80/60 °C,
in a room with a environment temperature of 10 °C?
The table in paragraph 2.1 states the power of the WWH 235-EC at a regime of 90/70 degrees and an environmental temperature of 15°C. This is 27. kW. With a regime of 80/60 degrees and 10 degrees room temperature, the conversion factor according to the table above in paragraph 9.1 is 0.91. De capacity will therefore become 0.91×27.8kW = 25.3 kW
Type| Unit| 115EC| 120EC| 235EC| 245EC|
350EC| 365EC| 380EC
---|---|---|---|---|---|---|---|---
Heating capacity (*)| kW| 14.7| 19.7| 27.8| 42.4| 46.4| 54.4| 76.7
Air output| m3/h| 2200| 1950| 3900| 3500| 6150| 8500| 7600
Throw horizontally| m| 16| 14| 22| 19| 21| 25| 21
Throw vertical| m| 5| 5| 7| 6| 7| 8| 7
Electrical supply| V| 230| 230| 230| 230| 230| 230| 230
Consumed current| A| 1.0| 1.1| 0.9| 1.1| 1.5| 1.8| 1.4
Power consumption| W| 111| 123| 200| 250| 320| 400| 308
Weight (incl. water)| kg| 20| 21| 31| 32| 44| 61| 65
Water connection (ext.)| G| ¾| ¾| ¾| 1| 1| 1| 1
Water sided pressure loss| kPa| 3| 3| 4| 5| 4| 7| 9
Recommended susp. height| m| 2.5| 2.5| 2.5| 2.5| 2.5| 2.5| 2.5
Noise level (5m)| dB(A)| 35-54| 35-54| 35-59| 35-57| 35-60| 35-56| 35-54
At a regime of 80/60 degrees and a room temperature of 10 degrees, the conversion factor according to the table above in section 9.1 is 0.91.
| Air temperature
---|---
Water temperature| 0°C| 5°C| 10°C| 15°C| 18°C| 20°C
90/70°C| 1.30| 1.19| 1.10| 1.00| 0.94| 0.91
80/60°C| 1.11| 1.01| 0.91| 0.82| 0.76| 0.73
70/50°C| 0.92| 0.82| 0.73| 0.64| 0.56| 0.55
60/40°C| 0.73| 0.64| 0.54| 0.45| 0.40| 0.37
50/30°C| 0.54| 0.45| 0.37| 0.27| 0.22| 0.18
The capacity therefore becomes 0.91×27.8 kW = 25.3 kW.
Disposal & recycling
Waste treatment
The symbol on the material, accessory or packaging indicates that this product
must not be treated as household waste. Dispose of the device via the
collection point for the recycling of waste electrical and electronic
equipment within the EU and in other European countries that have separate
collection systems for used electrical and electronic equipment. By disposing
of the device correctly, you help prevent potential environmental and health
hazards that could otherwise be caused by improper handling of the waste
device. Recycling of materials contributes to the conservation of natural
resources. Therefore, do not dispose of your old electrical and electronic
equipment with the household waste.