TRIPLETT GSM500 Carbon Dioxide Monitor Controller User Manual
- June 13, 2024
- TRIPLETT
Table of Contents
User Manual
GSM500
Carbon Dioxide Monitor/Controller
Introduction
Thank you for purchasing the Triplett GSM500 CO2 controller. An external CO2
sensing probe is included to help you measure the CO2 level in a closed space.
This GSM500 controller has a 120V US AC line cord plug to get AC power from
wall power outlet, and provide controlling function to other connected
devices, such as CO2 generator and ventilation fan.
To ensure safety, please read this manual carefully before installation and
follow up the instructions. Store this manual in a secure place for future
reference.
Features:
- Accurate & low drift NDIR CO2 measuring
- External CO2 sensor to be used in a closed space
- Display real time CO2 value
- Display CO2 chart with adjustable time scale (week/day/hour/min/auto)
- Auto Max. /Min. Recall on CO2 chart
- Programmable CO2 zone value & CO2 center value to control output power on/off
- Audible alarm warns CO2 concentration
- Target zone indicator on CO2 chart
- Built-in Day/Night auto detection on CO2 probe to override CO2 control
- Backlight to assist operation in dark place
- Monitoring& Controlling CO2 value in
- Green house, residential and commercial building
Included
This package contains:
Meter (controller + monitor)
Operation manual
Screws and tape
Power Supply
The meter is powered by AC120 VAC directly. The power plug is a USA piggyback plug type so you can plug in the device you want to control.
Meter Placement
An external CO2 sensing probe is included to help you measure CO2 level in a
closed space, the cable is 4.5 meter long to extend your measure spot 4.5
meter away from display.
Please make probe and meter away from water spray to extend the life time.
Screws are provided in package. First using the provided wall sticker to
locate the spot where you want to hang the sensing probe and controlling meter
on , drill to fix screw and hang devices.
Safety Fuse
The meter is powered by AC100~240 VAC directly and provide power through piggyback socket or EU/UK/FR/AU type socket to drive CO2 generator or ventilation. To avoid the damage by power overload, a 3kA@300VAC fuse is installed in meter. Contact distributor or shop to purchase new fuse while necessary. See appendix for detail.
Keypad and Function LEDs
| Enter setup mode.
---|---
| Save and finish settings.
| Select mode or increase value in calibration and setup.
| Change time scale. Select mode or decrease value in calibration and setup.
Power: Green on while powered
Day time: Green on while detected light is >60 lux for 10 sec.
Output: Green on while relay is ON
LCD Display
CO2 Chart | CO2 trend in graphic |
---|---|
Max | Max of displayed chart |
MIN | Min of displayed chart |
Buzzer
Beeper alarm on/off indicator
Zone| Zone value for relay control
Center| Center value for relay control
CO2 PPM| Current CO2 value
Time scale| Chart time scale. Includes week, day, hour, min, auto
Target Zone| Controlling zone indicator
ADV| Advanced setting to customize your CO2 controller
RE-CALI| Operate to do CO2 calibration
| Plant mode or Human mode
Operation
Plug the power plug into the wall socket to turn the controller on. While
connect is successful, the device will show full display with a short beep and
then performs 10 sec. countdown to warm up and also displays firmware
information
and “Warm Up” in chart display section.
Unplug the power plug to turn off the meter. While power on the meter again,
the meter will retain the same setting from last operation, except the chart
time will stay as 1 day while re-powered.
Taking Measurements
The meter starts taking measurement after power on and updates readings every
second. If your application is for green house CO2 control, no initial setup
is needed. In the condition of operating environment change (ex. from high
to low temp.), it takes 30 sec to respond for CO2 change. Do not hold the
probe close to face in case that exhalation affects CO2.
He device constantly displays current ambient CO2, set center value and set
zone value.
Trend Chart Zone
Below is a table that shows the available time scale and the duration of each
division for corresponding scale:
Time Span | Time per division |
---|---|
1min | 5sec/div |
1hour | 5 min/div |
1day | 2 hour/div |
1week | 0.5 day/div |
Auto cycle | Cycle above |
Using to toggle the available time you choose auto cycle, you will scale. When
see “ “ on LCD and time scale exchange every 20 sec.
MAX/MIN of displayed chart At the right side of the displayed chart, there are
two numerical indicators: Max and Min. They are the maximum and minimum values
on the displayed chart. While you press down key to change the chart time
scale, these value update as well.
Display Backlight
By pressing any key can activate the backlight for 30 seconds to help you
operate in dark environment.
Auto Detect Day/Night
In greenhouse application, CO2 control is not necessary while light is weak.
The built-in Photo-Cell sensor in CO2 sensing probe can automatically detect
whether it is Day (above 60 Lux) or Night(less than 20Lux). It can override
the CO2 control and shut off the CO2 generator by turning off the output power
during the night. Conversely, if the Photo-Cell detects light (>60Lux) and the
CO2 level is consistently low for 30 seconds, the device will start the CO2
generator by turning on output power.
Above auto detect Day/Night function is ignored while users pick up “ Human”
mode in advanced setting. With auto detection is ignored, the relay output
control is only decided by CO2 value, only. Day or Night has no influence on
it
Output Control
Output power is on when CO2 value is lower Set Center-(1/2) Set zone, and off
when CO2 concentration is above Set Center+(½) Set zone. For example, if the
Set Center is 1200ppm, and the Set zone is 400ppm, the output power will shut
off when CO2 over 1200+ (1/2)(400)=1400ppm, and power on when CO2 below
1200-(½)(400)= 1000ppm.
Above output control pattern is opposite while users pick up “ Human” mode
in advanced setting. You can check from display to know the existing setting
is Human or Plant .
In Human mode, if the Set Center is 1200ppm, and the Set zone is 400ppm, the
output power will turn on when CO2 over 1200+(1/2)(400)=1400ppm, and shut off
when CO2 is below 1200-(½)(400)=1000ppm.
Target Zone indicator
From displayed chart, users can easily know whether the current CO2 reading is
the controlling target zone or not by checking the chart. Target zone is
indicated by triangle icons.
For example, below picture shows the max. & min value of this time scale in
last 85 seconds is 626ppm and 542ppm and it is all in controlling target zone.
Buzzer Alarm
Buzzer alarm default as OFF (icon ) . You may go for setup mode to turn the
buzzer alarm function on (icon ).
While the buzzer is on, it beeps when CO2 value is over Set Center+ Set zone,
and off when CO2 concentration is below Set Center+ Set zone. For example, if
the Set Center is 1200ppm, and the Set zone is 400ppm, the beep will start
when CO2 is over 1200+400=1600ppm, and buzzer off when CO2 is below 1600ppm.
Above high alarm buzzer working pattern is applied to both Plant & Human mode.
Setup
Hold key under normal mode to enter setup mode.
Press key to choose the necessary setup function and then press to enter.
To exit setup, press key four times till it returns to normal mode. “Center”,
“Zone”, “Re-CALI”, “ADV” and then return to normal display is a complete cycle
of setup function.
In setup mode, if none of the keys are pressed within 1 min, the device will
automatically return to normal status.
CENTER
When entering setup mode, press to enter “Center” value setup. The default
value is 1200ppm for general plant. Press or to change the value and it is
50ppm/step. Then, press again to confirm it.
When entering setup mode, press to enter “Zone” value setup. The default value
is 400ppm for general purpose. Press or to change the value and it is
10ppm/step. Then, press again to confirm it.
ZONE
Note: One short cut for users to revert the Center and Zone to 1200&
400ppm : In normal mode, press for 3 secs till an audible beep and LCD should
show“ Back Home Done” .
RE-CALI
While the accuracy of this device is a concern, you may use this function to
calibrate this device with outdoor fresh atmospheric air in ~400ppm condition.
It is suggested to do calibration in sunny day to ensure the fresh air is
closed to 400ppm.
Leave the sensor in outdoor fresh air for 20 mins before you want to start the
calibration. When entering setup mode, press keys to select “Re-CALI”, then
hold for 3 seconds until a beep and the chart will read “Calibration”. Leave
the sensor in outdoor fresh air for 20 mins to complete the calibration.
To escape, press to terminate without saving.
Make sure the device is far away from CO2 source, not in direct sunlight, and
not exposed to water.
Note:
The meter is calibrated at standard 400ppm CO2 concentration in factory.
Note:
Do not calibrate the meter in the air with unknown CO2 level. Otherwise, it
will be taken as 400ppm and leads to inaccurate measurements.
ADV(advance)
The last function in setup mode is called advance setting which allows you to
customize your controller with more flexibility, includes: 1. buzzer alarm
on/off, 2. CO2 altitude (pressure) compensation,3. choose relay output to
Human or 4. Plant mode, 5.restore to factory default status.
Press keys to select “ADV”, then press to enter. In ADV, press or to select
Buzzer, Altitude, Restore or Human/Plant.
To enter Buzzer, press and then use or to turn on/off buzzer alarm. The
default is off.
To enter Altitude, press and then use or to adjust. The range is 50M to to
5000Meter. 50M/step.
To select Plant, you will see plant icon is flashing, press to confirm.
Now, your relay output will be activated while Co2 value is lower than
threshold.
To select Human, you will see human icon is flashing, press to confirm.
Now, your relay output will be activated while CO2 value is too high.
To restore to factory default, press and hold for 3 seconds till an audible
beep.
Now, all Center/Zone/Chart time/ Calibrate/Altitude will all restore to 1200
ppm/400ppm/1Day and 0M.
**Troubleshooting
**
? Can’t power on
Check whether the power is well plugged.
Check whether the fuse is damaged
? Slow response
Check whether the air flow channels on the sensing probe is blocked.
? CO2 reading is “Hi”
Means the measured value is higher than 5000ppm. Remove the sensor to fresh
air to revert it to normal display.
? Error messages
Err4, means IR lamp error.
Please reconnect power adapter
Err5, means Internal parameter error
Please reconnect power adapter.
Err6, means Communication error Please reconnect sensor unit If above
methods to release Err4 ~ 6 are not working,
Specifications
Model: | 7530 |
---|
Measuring range
CO2| 0~5000 ppm
Accuracy
CO2 below 3000ppm
Co2 above 3000ppm| ±50ppm or ±5% of reading, whichever is greater
±7% of reading
Warm-up time| 30 seconds
Response time
CO2| <2min for 63% of step change or
<4.6min for 90% step change
LCD size| 47 x 104 mm
Meter size| 158 x 106 x 50 mm
Sensor size| 124 x 33 x 26 mm
Operating condition| 0~50° C , 5~95% RH (avoid condensation)
Storage condition| -20~ 60 °C,5~95%RH(avoid condensation)
Power supply| AC100~240VAC
Piggyback socket load| 5A@250VAC; 10A@120VAC
Weight| 700g
Standard package| Sensor, controller, manual, screws
Warranty
Triplett / Jewell Instruments extends the following warranty to the original
purchaser of these goods for use. Triplett warrants to the original purchaser
for use that the products sold by it will be free from defects in workmanship
and material for a period of (1) one year from the date of purchase. This
warranty does not apply to any of our products which have been repaired or
altered by unauthorized persons in any way or purchased from unauthorized
distributors so as, in our sole judgment, to injure their stability or
reliability, or which have been subject to misuse, abuse, misapplication,
negligence, accident or which have had the serial numbers altered, defaced, or
removed. Accessories, including batteries are not covered by this warranty.
Copyright © 2023 Triplett
www.triplett.com
Appendix
FUSE SPECIFICATION
Dimension: Dia.5 x 20(L) mm
- Amp code: 1600
- Rated Current: 6.00A
- Max. Voltage:300 VAC 300 VDC
- Max. Voltage Drop: 150 mV
- Breaking Capacity: 3kA@300V AC 3kA@300V DC
- Typical Pre-arcing I2t (A 2 Sec):30
Location:
The fuse is on the PCB.
Please unscrew 7 screws on the back side of meter then you can find the fuse
as shown.
CO2 LEVELS AND GUIDELINES
Plant
This CO2 is default as 1200ppm for Target Zone (center) value and 1200ppm is
suitable for most application. However, you still can adjust center and zone
value to customize a best controlling output for your plant!
Plant Name | Target Zone/PPM |
---|---|
bean | 600-900 |
chilies cucumber grape | 800-1000 1000-1500 800-1400 |
orchid potato | 800-1400 1200-1800 |
strawberry tomato | 800-1200 800-1200 |
Appendix
CO2 LEVELS AND GUIDELINES
Non-Enforced Reference levels
NIOSH recommendations 250-350ppm: normal outdoor ambient concentrations
600ppm: minimal air quality complaints
600-1000ppm: less clearly interpreted
1000ppm: indicates inadequate ventilation; complaints such as headaches,
fatigue and eye/throat irritation will be more widespread. 1000ppm should be
used as an upper limit for indoor levels.
Regulatory exposure limit
ASHRAE Standard 62-1989: 1000ppm
CO2 concentration in occupied building should not exceed 1000ppm.
Building bulletin 101 (BB101): 1500ppm
UK standards for schools say that CO2 at averaged over the whole day(i.e. 9am
to 3.30 pm) should not exceed 1500ppm.
OSHA: 5000ppm
Time weighted average over five 8-hour work days should not exceed 5000ppm.
References