Dwyer P-AVLV Series Low Air Velocity Transmitter Instruction Manual
- June 15, 2024
- Dwyer
Table of Contents
Bulletin P-AVLV
Series AVLV Low Air Velocity Transmitter
Specifications – Installation and Operating Instructions
P-AVLV Series Low Air Velocity Transmitter
The Series AVLV Low Air Velocity Transmitter quickly and accurately measures
air velocity or volumetric flow in imperial or metric units. Simultaneous
current and voltage outputs on all models provide universal inputs to
monitoring equipment while the output range, units, and 0-5/10 VDC output can
be configured via local DIP switches. The optional integral display, or the
portable remote display tool, provide a convenient way to locally monitor
process values and configure the unit. Models are available in 1% and 2%
accuracy models and low velocity ranges to suit a variety of needs, and the
optional BACnet MS/TP or Modbus® RTU/ASCII communication protocol allows units
to be daisy-chained while providing access to all of the velocity and flow
data, as well as additional information such as air temperature.
The lower ranges in these high accuracy units allow for applications in
quality intensive environments, such as the pharmaceutical industry.
ACCURACY CHART
Velocity Range | Accuracy Rating* |
---|
20 to 100 FPM (0.15 to 0.5 m/s)
20 to 200 FPM (0.15 to 1.0 m/s)
20 to 300 FPM (0.15 to 1.5 m/s)
20 to 400 FPM (0.15 to 2.0 m/s)| ± (2% of reading + 0.04 m/s [7.9 FPM])
± (1% of reading + 0.04 m/s [7.9 FPM])
± (2% of reading + 0.04 m/s [7.9 FPM])
± (1% of reading + 0.04 m/s [7.9 FPM])
± (2% of reading + 0.05 m/s [9.8 FPM])
± (1% of reading + 0.05 m/s [9.8 FPM])
± (2% of reading + 0.06 m/s [11.8 FPM])
± (1% of reading + 0.06 m/s [11.8 FPM])
*Accuracy dependent on model selected when ordering.
SPECIFICATIONS
Service: Clean air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Range: 100, 200, 300, 400 FPM (0.5, 1, 1.5, 2.0 m/s); field selectable.
Accuracy: See chart.
Temperature Limits: 32 to 122°F (0 to 50°C).
Power Requirements: 24 VDC ±20% or 24 VAC ±20%.
Humidity Limits: 5 to 95% RH, non-condensing.
Output Signals: 4-20 mA, 0-5 VDC, 0-10 VDC.
Response Time (90%): 4 s, typical; 1 s at constant temperature.
Zero and Span Adjustments: Digital push buttons.
Output Load Resistance: Current output: 0 to 1100 Ω max.; Voltage output:
Minimum load resistance 1 kΩ.
Current Consumption: 60 mA max.
Display: 5 digit LCD (optional).
Electrical Connections: Analog: Power and output: four wire removable European
style terminal block for 16 to 26 AWG; Communication: Connections: BACnet
MS/TP or Modbus ®
RTU/ASCII: three wire removable European style terminal block for 16 to 26
AWG.
Supported Communication Baud Rates: 9600, 19200, 38400, 57600, 76800, 115200
(optional).
Device Load: 1/8 unit load.
Electrical Entry: 1/2˝ NPS thread; Accessory: Cable gland for 5 to 10 mm
diameter cable, A-151.
Enclosure Rating: NEMA 4X (IP66).
Mounting Orientation: Flow direction must be parallel to the sensor tip.
Weight: 6.0 oz (160 g).
Agency Approval: BTL, CE.
INSTALLATION
Duct Mount:
The transmitter should be mounted away from fans, corners, heating and cooling
coils, and other equipment that will effect the measurement of the air
velocity. It is recommended that the AVLV is mounted 10 duct diameters
downstream of any disturbances and 5 duct diameters upstream of any
disturbances, if possible.
- Mark and drill a 0.750-0.938˝ (20-24 mm) diameter hole into the duct.
- Insert and center the duct mount flange in the previously drilled hole and mark location of the three mounting screw holes.
- Remove the mounting flange and drill or punch the mounting holes in the marked locations.
- Fasten the flange to the duct using three #8 x 1/2 pan head sheet metal screws. Do not over tighten screws.
- Insert the AVLV probe into the ducts mount flange and set the desired insertion depth.
- Note the flow direction and unit alignment as shown on sensor tip and product label, tighten probe retention set screw on the duct mount flange screw to affix the probe in place.
Electrical Connection:
The Series AVLV is powered and simultaneously transmits a two-wire 4-20 mA
current output and a three-wire 0-5 VDC or 0-10 VDC voltage output via a
removable four conductor terminal block. The transmitter power supply common
is used to reference the current and voltage outputs so either current,
voltage, or current and voltage may be wired according to the application. The
range of the voltage output can be selected using the on board DIP switches as
described in the Analog DIP Switch Settings section of this manual.
Power Supply
Choose a power supply with a voltage and current rating sufficient to meet the
power specifications under all operating conditions. If the power supply is
unregulated, make sure the output voltage remains within the required voltage
range under all power line conditions. Ripple on the supply should not exceed
100 mV.
CAUTION
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS.
PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT.
Current Output Operation
CAUTION
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS.
PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT.
The terminal block is removable, and each of the terminals are labeled underneath the terminal block on the circuit board. As the power supply and outputs share the same common signal (GND), the outputs may have separate wires but must effectively join at terminal 2 of the transmitter, as shown in Figure 1. The connections to the transmitter are made to terminals 1, 2, and 3 (PWR, GND, and IOUT respectively) on the terminal block as shown in Figure 4.
Although low loop resistances are recommended, the absolute maximum current
loop load resistance, RMAX , is defined by the following the equation:
RMAX = (VPS – 2.0) / 0.02 where VPS is the power supply voltage
For a 24 VDC nominal power supply, this evaluates to RMAX = 1100 ohms.
Shielded two wire cable is recommended for current output loop wiring. Ground
the shield at the power supply end only.
The maximum length of connecting wire between the current transmitter and the
receiver is a function of wire size and receiver resistance. That portion of
the total current loop resistance represented by the resistance of the
connecting wires themselves should not exceed 10% of the receiver resistance.
For extremely long runs (over 1,000 ft.), it is desirable to select receivers
with higher resistances in order to keep the size and cost of the connecting
leads as low as possible. In installations where the connecting run is no more
than 100 ft, connecting lead wire as small as No. 22 Ga. can be used.
Voltage Output Operation
CAUTION
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS.
PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT.
The terminal block is removable, and each of the terminals are labeled
underneath the terminal block on the circuit board. The voltage output and the
power supply must have separate wire leads that are only joined at terminal 2
of the transmitter, as shown in
Figure 2. Additional error may occur for the voltage output if a single wire
is used or if the wires are joined at the power supply or receiver. The
connections to the transmitter are made to terminals 1, 2, and 4 (PWR, GND,
and VOUT respectively) on the terminal
block as shown in Figure 4.
The minimum receiver load is 1 kΩ. The resistance due to the wire should be
low compared to the receiver load resistance. While the voltage at the
terminal block remains unchanged with a 10 mA current flow, resistive losses
in the wiring do cause errors in the voltage delivered to the receiver. For a
1% accurate gauge, the resistance of the wires should be less than 0.1% of the
value of the receiver load resistance. This will keep the error caused by the
current flow below 0.1%.
The output across VOUT and COM will be either 0-5 VDC, 0-10 VDC, or the
inverse depending on the DIP switch setting. See the Analog DIP Switch
Settings section for more information.
Simultaneous Current and Voltage Output Operation
CAUTION
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS.
PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT.
The terminal block is removable, and each of the terminals are labeled
underneath the terminal block on the circuit board. The voltage output and the
power supply must have separate wire leads that are only joined at terminal 2
of the transmitter, as shown in
Figure 3. Additional error may occur for the voltage output if a single wire
is used or if the wires are joined at the power supply or receiver. The
connections to the transmitter are made to terminals 1, 2, 3 and 4 (PWR, GND,
IOUT, and VOUT respectively) on the terminal block as shown in Figure 4, which
reflects both the 4-20 mA and 0-5/10 VDC outputs in the same circuit. Details
of each output are detailed in their electrical connection sections.
ANALOG DIP SWITCH SETTINGS
The analog output DIP switches (SW1) are located above the terminal blocks on
the left are as shown in Figure 4. A small screw driver or pen can be used to
change the position of the switches as required. DIP switch positions for SW2
and SW3 are RESERVED or have no affect.
CAUTION
All power should be turned off to the transmitter before adjusting the DIP
switch settings to avoid electrical shock.
Factory Default Settings (DIP SW1 – All Switches ON)
Range = Highest Range Setting (400 FPM)
Units = Imperial (FPM)
Voltage Output Range = 0-10 VDC
Direct / Reverse Output Action = Direct
Setting the Air Velocity Range
The range of the instrument is selected by using DIP switches 1 and 2 on SW1.
Table 1 shows the maximum full scale value for the selected range and unit.
Refer to Setting the Engineering Units section for information on setting the
unit.
DIP Switch SW1 | Full Scale Range |
---|---|
1 | 2 |
ON | ON |
ON | OFF |
OFF | ON |
OFF | OFF |
Table 1: DIP switch SW1 settings for full scale range
Setting the Engineering Units
The Series AVLV can be configured to indicate velocity in imperial (FPM, CFM)
or metric (m/s, m³ /h) units using DIP switches 4 and 5 on SW1, and Table 2
shows the values. The units will be displayed on the optional LCD display if
connected.
DIP Switch SW1 | Units |
---|---|
4 | 5 |
ON | ON |
ON | OFF |
OFF | ON |
OFF | OFF |
Table 2: DIP switch SW1 settings for units
The default operating mode is velocity, but changes can be made, such as flow mode, via the menu system while an optional display or remote display accessory is connected. Please refer to Appendix III for a full menu flow chart.
Setting the Output Voltage Range
Voltage Output can be either 0-5 VDC or 0-10 VDC depending on the position of
DIP Switch 6 ON SW1.
- When the switch is in the ON position, the output will be 0-10 VDC.
- When the switch is in the OFF position, the output will be 0-5 VDC.
Setting the Input / Output Action
The output will either follow the process directly (DIRECT) or inverted
(REVERSED) based on the position of DIP Switch 7 on SW1.
- When the switch is in the ON position, the output directly follows the input (i.e. output increases as the input increases).
- When the switch is in the OFF position, the output acts in reverse of the input (i.e. output decreases as the input increases).
CALIBRATION
NOTICE There is a 5 second delay from the time the zero or span
calibration buttons are released until the time that the change in calibration
takes place. This delay is used to reduce vibration or disturbances of the
user related to the button presses.
NOTICE
The security level that is set in the Programming Menu section of the manual
will determine which calibrations, if any, may be adjusted by the user.
Zero Calibration
The zero calibration can be set by covering the sensor to ensure no air flow
and pressing the zero button for 3 seconds. If either the remote or local LCD
is present, the display will read ZEro and then sequence back to the home
display.
SPAN Calibration
The span calibration can be adjusted only after setting the zero adjustment.
It must be completed within 5 minutes of the last zero calibration. The span
calibration button will be ignored until the zero calibration is completed.
Place the sensor in airflow that
matches the maximum selected range of the transmitter. Press and hold the span
button for 3 seconds. If either the remote or local LCD is present, the
display will read SPAn and then sequence back to the home display. If the span
calibration is attempted before adjusting the zero calibration, the FAiL error
message will be displayed briefly before returning to the home display.
LCD Display
The Series AVLV can be ordered with an optional, integral LCD. It comes with a
housing cover and overlay to protect the display. The display will plug into
the pins as shown in Figure 5. If the display is not needed for normal
operation, the transmitter can be ordered without the LCD.
Another option for models that do not have a display would be to use a Model A-435-A remote display tool which can plug into the connector shown in Figure 6. The remote display tool has two buttons that function identically to the buttons on the PCB.
Display Error Messages
= The air velocity is greater than the maximum span value causing an Over
Range Error
= The air velocity is less than the minimum span value causing an Under Range
Error
= When the span or zero buttons are pressed, the air velocity value is out of
the range to allow a correct setting. This may be due to a sensor failure.
= The sensor is damaged.
PROGRAMMING MENUS
Home Menu
During normal operation, the display will be in the Home Menu and will display
the current measured pressure and the engineering units.
Menu Access Security
While in the Home Menu, press and hold the Zero and Span buttons
simultaneously until appears on the display in order to access the other
programming menus.
Upon releasing the buttons, the display will indicate the current security
level.
If the current security level is the security level desired (i.e. Security
Level 0), press and hold the span button for 3 seconds to enter the Velocity
or Air Flow Menu.
If the security level is not the desired level, the security level can be
changed temporarily to a lower security level or permanently to a higher level
of security by pressing the zero button. A security code will appear on the
display, and it can be changed to one of the codes listed in Table 3. The span
button chooses which digit and the zero button increments the value of that
digit. Pressing and holding the span button will store the value.
The level of access to the programming menus and the calibration is limited
based on the security level. Table 3 details the level of access for each
security level.
Security Level | Setting | Access |
---|---|---|
View Menu | Edit Menu | Span |
0
1
2
3| 000
111
222
333| Yes
Yes
No
No| Yes
No
No
No| Yes
No
No
No| Yes
Yes
No
No
Table 3: Security settings
Mode Selection / Digital Dampening Menu
From the home display, pressing the span and zero button simultaneously for 3
seconds will access the Menu Security Level. If the level is set to 0 or 1,
pressing and holding the span button for 3 seconds, a second time, will access
the Mode Selection Menu. The display will default to air velocity when first
powered up. Pressing the zero button will cycle to air flow.
Once the desired mode is displayed, pressing and holding the span button for 3
seconds will save the selected mode and display the digital dampening or
averaging parameter. This parameter stabilizes the output and the display by
averaging the readings. There are 2.5 readings taken each second and the user
can select the number of seconds that they would like to average, up to 240
seconds. The display and the output will continue to update at a rate of 2.5
updates per second, but the moving average is used for these updates.
Velocity Mode
K-Factor Adjustment
If the Velocity Mode was selected, pressing and holding the span after
adjusting the digital dampening will enter the Velocity Mode and the
transmitter will display the engineering unit that has been selected by the
DIP switch. Pressing and holding the span button for 3 seconds will enter the
K – Factor adjustment. The K – Factor can be adjusted between 0.001 to 9.999.
The K-Factor can be adjusted by pressing the span button to select the digit
and pressing the zero button to increment the value of the digit. Pressing and
holding the span button for 3 seconds will enter the Maximum Output Adjustment
parameter.
Flow Mode
K-Factor Adjustment
If the Flow Mode was selected, pressing and holding the span after adjusting
the digital dampening will enter the Flow Mode and the transmitter will
display the engineering unit that has been selected by the DIP switch.
Pressing and holding the span button for
3 seconds will enter the K–Factor adjustment. The K–Factor can be adjusted
between 0.001 to 9.999. The K-Factor can be adjusted by pressing the span
button to select the digit and pressing the zero button to increment the value
of the digit. Pressing and holding the span button for 3 seconds will enter
the Area Adjustment parameter.
Area Adjustment
For flow applications, the area is multiplied by the velocity to determine the
volumetric air flow. The area will be listed in either CFM or m³/h depending
on the DIP switch settings. The units will appear on the display at the time
of adjustment. The area can be adjusted by pressing the span button to select
the digit and pressing the zero button to increment the value of the digit.
Pressing and holding the span button for 3 seconds will enter the Maximum
Output Adjustment parameter.
Maximum Output Adjustment
The maximum output can be equivalent to air velocity or air flow. After
adjusting the K-Factor, the display will indicate if the adjustment is set for
velocity or air flow.
Pressing the zero button will toggle between the selections. Pressing and
holding the span button for 3 seconds will enter the maximum output
adjustment. The maximum output can be adjusted by pressing the span button to
select the digit and pressing the zero button to increment the value of the
digit. Pressing and holding the span button for 3 seconds will save this value
and go to the Security Update Menu.
Security Update / Save Changes Menu
The Security Update Menu allows the security level to be set either higher or
lower than the current security level setting. This security level will be
displayed the next time the Menus are accessed from the home screen. Pressing
the zero button cycles through the security levels. Pressing and holding the
span button for 3 seconds accepts the new security level and gives the option
to save all the menu changes.
Pressing the zero button will toggle between yes and no. Yes will save the
changes made to all menu items and no will discard all the changes made to all
menu items. If the display is set to yes, pressing and holding the span will
save the menu items and return the display to the home position.
FACTORY DEFAULT PROCEDURE
In order to reset all of the menu settings back to their factory programmed
values, press and hold both the span and zero buttons simultaneously for 10
seconds until is displayed on the LCD. Upon releasing the buttons, the unit
will be factory defaulted. Since resetting the transmitter will wipe out all
changes, it is necessary to zero (and possibly span) the transmitter before
taking measurements.
MAINTENANCE/REPAIR
Upon final installation of the Series AVLV Air Velocity Transmitter, no
routine maintenance is required besides zeroing the transmitter occasionally.
Besides routine calibration and installation of the LCD, the Series AVLV is
not field serviceable, and it is not possible to repair the unit. Field repair
should not be attempted and may void warranty.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sales” in our catalog and on our website.
Contact customer service to receive a Return Goods Authorization number before
shipping the product back for repair. Be sure to include a brief description
of the problem plus any additional application notes.
APPENDIX I: Air Velocity / Air Flow Calculations
Velocity in m/s is then calculated from the equation:
Velocity (m/s) = Velocity (FPM) x 0.00508
Flow in m³/h is then calculated using the below equation:
Flow (CFM) = Area (ft²) x K-Factor x Velocity (FPM)
Flow (m³/h) = Flow (CFM) x 1.6992
APPENDIX II: Maximum Flow
Max Flow | Max K Factor x Area |
---|---|
CFM | m3/h |
5885000 | 9999000 |
Table 4: Maximum flow values
APPENDIX III: Menu Flow Chart
BUTTON PRESS LEGEND
= PRESS ZERO BUTTON
= PRESS SPAN BUTTON
= PRESS AND HOLD ZERO BUTTON
= PRESS AND HOLD SPAN BUTTON
= PRESS AND HOLD ZERO AND SPAN BUTTONS
MENU CONVENTIONS
IN HOME POSITION:
CALIBRATE UNIT TO ZERO PRESSURE.
CALIBRATE UNIT TO SPAN PRESSURE.
ENTER MENU DISPLAY
IN MENU DISPLAY:
SEQUENCES TO NEXT MAIN MENU ITEM, AND IF A MENU ITEM IS CHANGED TEMPORARILY
SAVES THE SELECTION
SEQUENCES THROUGH SUB MENU SELECTIONS OR INCREMENTS DIGITS
SEQUENCE TO NEXT DIGIT. ACTIVE DIGIT WILL BLINK.
= BLINKING DIGIT
Averaging Menu
Velocity Mode Menu
Flow Mode Menu
Security Menu
Modbus® is a registered trademark of Schneider Electric USA, Inc.
©Copyright 2023 Dwyer Instruments, LLC
Printed in U.S.A. 5/23
FR# 444499-00 Rev. 2
DWYER INSTRUMENTS, LLC
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057
dwyer-inst.com
e-mail: info@dwyermail.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>