SEIFERT 340 BTU Thermoelectric Cooler User Manual
- June 13, 2024
- SEIFERT
Table of Contents
- SEIFERT 340 BTU Thermoelectric Cooler
- Product Information
- Product Usage Instructions
- User manual
- PLEASE ENSURE TO USE THE RIGHT VERSION OF THE INSTRUCTION MANUAL SUITABLE
- Legal regulations
- Safety instructions
- Settings
- Functional principle
- Technical data
- Performance graph
- Wiring Diagram
- Taking into Operation
- Trouble Shooting
- Maintenance & Cleaning
- Maintenance
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SEIFERT 340 BTU Thermoelectric Cooler
Product Information
The product is a unit designed for the dissipation of heat from control cabinets and enclosures in order to protect temperature sensitive components in an industrial environment. It is intended for stationary use and should not be moved. The unit is equipped with safety features to ensure safe operation and compliance with relevant regulations.
Key Features
- Efficient heat dissipation
- Designed for control cabinets and enclosures
- Stationary use
- Protects temperature sensitive components
- Complies with safety regulations
Important Notes
- Use the correct version of the instruction manual suitable for your unit.
- Adhere to all information and instructions provided in the manual.
- Ensure external protection against overloading and electrical faults using suitable protective devices.
- Only technical competent and qualified personnel should install, maintain, and clean the unit.
Product Usage Instructions
- Ensure you have the correct version of the instruction manual for your unit.
- Familiarize yourself with the safety instructions provided in the manual.
- Follow the instructions on taking the cabinet out of operation when necessary.
- Prevent unauthorized cabinet reconnection by following the instructions provided.
- Refer to the type plate and wiring diagram for proper operation of the unit.
- Protect the unit from overloading and electrical faults using suitable protective devices.
- Only allow technical competent and qualified personnel to install and maintain the unit.
- When performing maintenance and cleaning, ensure the unit is disconnected from the power supply.
User manual
This instruction manual contains information and instructions to enable the user to work safely, correctly and economically on the unit. Understanding and adhering to the manual can help one
- Avoid any dangers.
- Reduce repair costs and stoppages.
- Extend and improve the reliability and working life of the unit.
PLEASE ENSURE TO USE THE RIGHT VERSION OF THE INSTRUCTION MANUAL SUITABLE
FOR YOUR UNIT.
Intended use
qä=unit is to be used exclusively for the dissipation of heat from control
cabinets and enclosures (stationary, not moving) in order to protect
temperature sensitive components in an industrial environment. To meet the
conditions of use, all the information and instructions in the instruction
manual must be adhered to.
General danger
Indicates compulsory safety regulations which are not covered by a specific
pictogram such as one of the following.
High electric voltage
Indicates electric shock danger.
Important safety instruction
Indicates instructions for safe maintenance and operation of the unit.
Attention
Indicates possible burns from hot components.
Attention
Indicates possible damage to the unit.
Instruction
Indicates possible danger to the environment.
Legal regulations
Liability
The information, data and instructions contained in this instruction manual
are current at the time of going to press. We reserve the right to make
technical changes to the unit in the course of its development. Therefore, no
claims can be accepted for previously delivered units based on the
information, diagrams or descriptions contained in this manual. No liability
can be accepted for damage and production caused by
- Disregarding the instruction manual
- Operating error
- Inappropriate work on or with the unit
- The use of non-specified spare parts and accessories
- Unauthorised modifications or changes to the unit by the user or his personnel
The supplier is only liable for errors and omissions as outlined in the guarantee conditions contained in the main contractual agreement. Claims for damages on any grounds are excluded.
Safety instructions
Upon delivery the unit is already meeting current technical standards and can
therefore be safely taken into operation. Only authorised personnel is allowed
to work on the unit. Unauthorised personnel must be prohibited from working on
the unit. Operating personnel must inform their superiors immediately of any
malfunction of the unit.
Please note that before starting to work on or with the unit, a procedure must
be carried out inside the cabinet on which the unit is to be mounted.
Before commencing work inside the cabinet, the control cabinet manufacturer’s
instruction must be read with regards to
- Safety instructions.
- Instructions on taking the cabinet out of operation.
- Instructions on the prevention of unauthorised cabinet reconnection.
The electric equipment meets the valid safety regulations. One can find dangerous voltages (above 50 V AC or above 100 V DC)
- Behind the control cabinet doors.
- On the power supply in the unit housing.
The unit has to be operated according to the type plate and the wiring diagram, and must be protected externally from overloading and electrical faults via suitable protective devices.
Danger through incorrect work on the unit
The unit can only be installed and maintained by technical competent and
qualified personnel, using only supplied material according to the supplied
instructions.
Danger from electrical voltage
Only specialised personnel are allowed to maintain and clean the unit. The
personnel must ensure that for the duration of the maintenance and cleaning,
the unit is disconnected from the electrical supply.
Attention
Damage to the unit through the use of inappropriate cleaning materials. Please
do not use aggressive cleaning material.
Instruction
Damage to the environment through unauthorised disposal. All spare parts and
associated material must be disposed according to the environmental laws.
Settings
Peltier cooling units are intended to be used as a complementary accessory to
larger industrial equipment. They are used where heat needs to be dissipated
from electrical control cabinets or similar enclosures to protect heat
sensitive components.
Peltier cooling units can dissipate heat from sealed enclosures such as
control cabinets. At the same time, they can reduce the cabinet internal
temperature to below the ambient air temperature. They are available in
powder-coated sheet steel or stainless steel housings. Peltier units have
additional heating function by changing the supply polarity of the
thermoelectric elements. This is possible by using a combination of
thermostats or having a specific polarity controller.
Peltier air conditioners are resistant to extreme ambient conditions and can
operate effectively even in environments which are dusty and oily and where
temperatures may vary from -20°C to +65°C. For the cooling capacities and
environmental ratings please refer to the type plate data.
Functional principle
The thermoelectric elements create a temperature difference between the internal and ambient heat sinks, making internal air cooler while dissipating heat into the external environment. Fans help the transfer of convective heat from the heat sinks, which are optimized for maximum flow. Peltier units be mounted in any position because these units don’t have a compressor and no moving parts.
- Ambient fans
- Ambient heat sinks
- Thermolelectric elements
- Insulation
- Internal heat sink
- Internal fan
Technical data
- Order Number 6105305
- Cooling capacity L35L35 100 W
- Rated COP 0.89
- Operating Temperature Range -20°C – 70°C
- UL temperature range -20°C – 65°C
- Air flow volume (system / unimpeded) Ambient air circuit : 128 / 213 m³/h
- Cabinet air circuit: 46 / 90 m³/h
- Mounting Wall mounted (with frame)
- Housing Material Stainless steel AISI 304 (V2A)
- Dimensions A x B x C (D+E) 280 x 350 x 160 mm
- Weight 11 kg
- Cut out dimensions 350 x 280 mm
- Voltage / Frequency 120 – 230 V ~ 50/60 Hz
- Current L35L35 1.0 A @ 120 V
- 0.5 A @ 230 V
- Starting current 1.6 A @ 120 V
- 0.8 A @ 230 V
- Max. current 1.2 A @ 120 V
- 0.6 A @ 230 V
- Nominal power L35L35 125 W
- Max. power 139 W
- Fuse 2 A (T) @ 120 V
- 1 A (T) @ 230 V
- Connection 8-Pole Connector
- Ingress Protection IP 66 / UL Type 12, 4, 4X
- Approvals CE, cURus
Performance graph
Mounting
^lways switch off power supply before starting any work on the unit.=
Installation
Ensure that flows of air leaving and entering the cooling unit, internal and
external, are not obstructed. Before drilling the enclosure, ensure the fixing
elements and couplings will not interfere with the equipment inside the
enclosure itself. When all mounting preparations are complete the actual
mounting operation can commence. Only use the enclosed material to mount the
unit on the cabinet.
Proceed as follows to mount the unit on the cabinet
- Set the unit up on the cabinet.
- Ensure that the electrical connection is above the internal fan.
- Unit without duct : screw the M6 locknuts & washers into the M6 set screws in the unit.
- Unit with duct : screw the M6 screws & washers into the M6 threaded rivets in the unit. The resistance of the earth connection between cabinet and cooling unit must be <0.1Ω.
Condensate management
Depending on the mounting situation the condensation management may need to be
considered and possibly adjusted.
Mounting Principle
In order to maintain the TYPE 4X rating, the tightening torque for this unit
should be 4.5 Nm and needs to follow the below sequence.
Cut Out Dimension
Dimension (H x W x D)
Electrical Connection
High electric voltage present. Installation, maintenance, cleaning and any
other work must be carried out by qualified personnel only. The personnel must
ensure that for the duration of this work the unit and the cabinet are
disconnected from the electrical supply and protected against
unauthorised/accidental reconnection.
Instruction: Check that the available voltage, frequency and fuse rating are the same as those stated on the unit data label.
Connection to the main electricity supply
The mains connection is made via a cable. To connect the unit to the mains
supply, proceed as follows
- Disconnect the control cabinet from the mains.
- See the connection details on the circuit diagram.
- Note the connections on the 3-pole terminal block from the following diagram.
Terminal 230 V ~ 50/60 Hz
- L Live
- PE Protective earth
- N Neutral
Connect the unit to the mains.
Take the control cabinet back into operation in the prescribed manner.
Controller
The display shows the temperature in the range of -50°C to +150°C (-58°F to
+302°F). The temperature is displayed with resolution of tenths between
-19.9°C and +99.9°C (-3.8°F to +211.8°F). During programming, it shows the
codes and values of the parameters. The display also shows icons according to
occurring events.
Display icons
- Icon Function Description
- 1 Cooling relay active Flashes when activation
- is delayed or inhibited by
- protection times, external
- disabling or other procedures
- in progress
- 2 Alarm relay active
- 3 Heating relay active
- 4 Ambient blower relay active
- Alarm Flashes when alarms are active
- Cooling mode Signal operation of unit in cooling mode
- TEST Test mode in progress Activated only by manual procedure
Programming
The operating parameters can be modified using the front keypad. Access differs
depending on the type of parameter. Access to configuration parameters is
protected by a password that prevents unwanted modifications or access by
unauthorised persons.
Setting cooling set point, St1
- Press “SET” and display should show St1 and then the pre-set value of St1. (default: +35°C / +95°F)
- Reach the desired value by using ▲ or ▼.
- Press “SET” again to save the new value of St1.
Setting temperature units (°C / °F), low temperature alarm and high temperature alarm
- Press “PRG” button for 5 seconds to reach the modifiable parameter list.
- Use ▲ or ▼ to reach the desired parameter:
- C18 for temperature unit of measure
- °C = 0
- °F = 1
- P25 for low temperature alarm threshold (default -10°C / +14°F) P26 for high temperature alarm threshold (default +55°C / +131°F)
- Press “SET” on the desired parameter to display the current value.
- Use ▲ or ▼ to reach the desired value.
- Pressing “SET” temporarily saves the new value and returns to the parameters list.
- Repeat steps 2-5 to set other parameters.
- Press “PRG” for 5 seconds to permanently save the new values.
Set Point Parameter Default Range
- Cooling St1 35°C / 95°F 20°C – 50°C / 68°F -122°F
- Low Temperature Alarm P25 -10°C / 14°F -50°C – P26 / -58°F – P26
- High Temperature Alarm P26 55°C / 131°F P25 – 150°C / P25 – 302°F
Test function
Different test functions can be used depending on the combination of keys
pressed. Such tests run for the duration of 4 minutes.
- “SET+▲” tests cooling relays
- “SET+▼” tests alarm relays
Important Notes
Whilst programming, if no button is pressed for 10 seconds, the display starts
flashing, and after 1 minute returns to the main display without saving
changes.
To increase scrolling speed, press and hold the ▲ or ▼ button for at least 5
seconds.
When pressing “PRG” for 3 seconds, the firmware revision code is displayed for
2 seconds.
When cleaning the controller panel, do not use ethanol, hydrocarbons, ammonia
or their by-products. Use neutral detergents and water.
The hysteresis is 5K, the minimum ON-time is 0s, the minimum OFF-time is 0s.
Wiring Diagram
X1- 8Pole Connector Positions
- Live
- Neutral
- PE
- Door Contact P1 (NO)
- Door Contact P2
- Alarm P1 NC (NO when ON)
- Alarm P2 (COM)
- Alarm P3 NO (NC when ON)
Taking into Operation
The power supply rating on the rating plate must comply with mains supply
Always disconnect the power supply before opening the unit.
Heat load to be dissipated from enclosure should not exceed specific cooling
output of the unit at any condition. While selecting a cooling unit always
cater for a safety margin of at least 15% extra cooling output.
The Peltie r – elements should be controlled by a suitable thermostat. Models TG 6XXX with 100 – 230 V supply have already a controller integrated.
Trouble Shooting
In case of a fault please contact your nearest servicing office. A list of service partners can be found on our website www.seifertsystems.com
Maintenance & Cleaning
Always switch off power supply before starting any work on the unit. Only
qualified personal may conduct any maintenance work on the cooling unit.
All Peltier units are virtually maintenance-free and no filters which need to
be cleaned or replaced. Check the ambient heat sinks from time to time. In
case they are dirty proceed as following
- Disconnect the enclosure from the mains.
- Clean the heat sink profile as required by blowing it out with compressed air.
- In cases of extreme pollution wet cleaning is required.
The unit must be removed from the control cabinet for wet cleaning
Should a wet cleaning be necessary proceed as following
- Disconnect the whole plant from the mains.
- Remove the unit from the cabinet.
- Ensure that the seals are not damaged.
- Wash the heat sink with an environmentally safe cleaning fluid.
Danger to the environment through unauthorized disposal.
Disposal
Dispose of cooling unit and used parts with due regard for the environment and
in accordance with environmental laws and regulations.
Maintenance
Note: Only use original replacement parts when repairing the unit. This ensures that the unit functions perfectly and remains safe.
Fan replacemen t: The average working life of the fan is ca. 40,000 hours under normal conditions. Should a fan replacement be necessary proceed as following
- Disconnect the unit from the mains.
- Remove the unit cover.
- Remove the screws from the relevant fan.
- Mount a new fan.
Damage to the unit through incorrect work.
Make sure that the cabinet fan or the ambient fan are not misplaced in the
unit as they are different. Ensure that the correct polarity is maintained.
- Replace the 4 fan fixing screws.
- Close the unit and take it back into operation.
Transport & Storage
During transport and storage, the cooling unit must be kept in the position
marked on the box and at a temperature between -40˚C and 70˚C and a relative
humidity of max. 95% (at 25°C). In case of damaged packaging after transport
or in-house handling, we recommend controlling the unit for any internal
damages.
Parts supplied / Spare parts / Accessories
Accessories
- Description Order no.
- Condensate Kit 6105 1004303
- Seifert Systems GmbH
- Seifert Systems Ltd.
- Seifert Systems AG
- Seifert Systems GmbH
- Seifert Systems Ltd.
- Seifert Systems Inc.
- Seifert Systems Pty Ltd.
- Albert-Einstein-Str.
- 3 HF09/10 Wilerstrasse 16 Bärnthal 1 Rep.
- Office 75 Circuit Drive 105 Lewis Road
- Hal-Far Industrial Estate North Kingstown Wantirna South
- 42477 Radevormwald Birzebbuga, BBG 3000 4563 Gerlafingen 4901 Ottnang 26100 Cremona RI 02852 3152 Victoria
- Germany Malta Switzerland Austria Italy USA Australia
- Tel.+49 2195 68994-0
- Tel.+356 2220 7000
- Tel.+41 32 675 35 51
- Tel.+43 7676 20712 0
- Tel.+39 349 259 4524
- Tel.+1 401-294-6960
- Tel.+61 3 98 01 19 06
- info.de@seifertsystems.com
- info@seifertsystems.com
- info.ch@seifertsystems.com
- info.at@seifertsystem.com
- nfo@seifertsystems.com
- info.us@seifertsystems.com
- info@seifertsystems.com.au
References
- Seifert Systems – Industrielle Schaltschrankklimatisierung
- Condensate Kits for thermoelectric cooling units
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>