YANMAR YDG Series Diesel-Powered Generators User Manual
- June 13, 2024
- YANMAR
Table of Contents
YANMAR YDG Series Diesel-Powered Generators
Product Information
The YDG series is a range of diesel-powered generators manufactured by YANMAR POWER TECHNOLOGY CO., LTD. The specific models in the series are YDG3700N- 6BYI2, YDG3700V-5BYI2, YDG5500N-6BYI2, YDG5500V-5BYI2, YDG3700N-6EBYI2, YDG3700V-5EBYI2, YDG5500N-6EBYI2, and YDG5500V-5EBYI2.
This product is covered by a limited warranty provided by YANMAR. The warranty covers defects in material and/or workmanship for the duration of the warranty period.
It is important to note that this warranty is provided in lieu of all other warranties, except where prohibited by law. YANMAR disclaims any implied warranties of merchantability or fitness for a particular purpose.
Product Usage Instructions
- Transportation: As the owner, you are responsible for transporting the generator to and from the repair location designated by YANMAR.
- Finding Authorized Dealers or Distributors: To locate an authorized YANMAR industrial engine dealer or distributor, visit the YANMAR CO., LTD. website at www.yanmar.co.jp. Click on the Global icon for English language support.
- Repairs and Replacements: If any part(s) of the YANMAR generator covered by the warranty are found to be defective, YANMAR will make repairs and/or replacements at no cost to you for parts or labor. The repairs and/or replacements will be made at a location designated by YANMAR.
Please note that this warranty does not cover any modifications made to the warranty terms unless they are in writing and signed by both parties. This warranty agreement is the complete and exclusive agreement between you and YANMAR regarding warranties.
OPERATION MANUAL
DIESEL POWERED GENERATORS
YDG series
YDG3700N-6BYI2 YDG3700V-5BYI2 YDG5500N-6BYI2 YDG5500V-5BYI2
YDG3700N-6EBYI2 YDG3700V-5EBYI2 YDG5500N-6EBYI2 YDG5500V-5EBYI2
en original instructions
Disclaimers:
All information, illustrations and specifications in this manual are based on
the latest information available at the time of publishing. The illustrations
used in this manual are intended as representative reference views only.
Moreover, because of our continuous product improvement policy, we may modify
information, illustrations and/or specifications to explain and/or exemplify a
product, service or maintenance improvement. We reserve the right to make any
change at any time without notice. YANMAR is a registered trademark of YANMAR
POWER TECHNOLOGY CO., LTD. in Japan, the United States and/or other countries.
All Rights Reserved:
No part of this publication may be reproduced or used in any form by any means
– graphic, electronic, or mechanical, including photocopying, recording,
taping, or information storage and retrieval systems – without the written
permission of YANMAR POWER TECHNOLOGY CO., LTD.
In case of exporting this product and providing the related technical material
to non-residents in Japan or residents in overseas, it is required to comply
with the export and trade control laws and regulations of Japan and other
relevant countries. Please be careful to proceed with necessary procedure.
OPERATION MANUAL
MODEL
YDG3700V-5EBYI2, YDG3700V-5BYI2, YDG5500V-5EBYI2, YDG5500V-5BYI2 YDG3700N- 6EBYI2, YDG3700N-6BYI2, YDG5500N-6EBYI2, YDG5500N-6 BYI2
CODE
YIYDG-EN0000
All Rights Reserved, Copyright YANMAR ITALY S.p.A.
YANMAR YDG Operation Manual WARRANTIES
YANMAR LIMITED WARRANTY
What is Covered by this Warranty?
YANMAR warrants to the original retail purchaser that a new YANMAR YDG diesel
generator will be free from defects in material and/or workmanship for the
duration of the warranty period.
This warranty is provided in lieu of all other warranties, express or implied.
YANMAR specifically disclaims any implied warranties of merchantability or
fitness for a particular purpose, except where such disclaimer is prohibited
by law. If such disclaimer is prohibited by law, then implied warranties shall
be limited in duration to the life of the express warranty.
How Long is the Warranty Period?
The YANMAR standard limited warranty period begins on the date of the delivery
of the new YANMAR YDG diesel generator to the first retail purchaser and
extends for a period of twenty-four (24) months or two-thousand (2000) engine
operation hours, whichever occurs first. The warranty period (by duration or
operation hours) begins on the date of delivery to the original retail
purchaser and is valid only until the applicable warranted duration has passed
or the operation hours are exceeded, whichever comes first.
YDG Operation Manual
i
YANMAR WARRANTIES
YANMAR limited warranty – continued
What the Generator Owner must Do:
If you believe your YANMAR generator has experienced a failure due to a defect
in material and/or workmanship, you must contact an authorized YANMAR
industrial engine dealer or distributor within thirty (30) days of discovering
the failure. You must provide proof of ownership of the generator, proof of
the date of the generator purchase and delivery, and documentation of the
generator operation hours. Acceptable forms of proof of delivery date include,
but are not limited to: the original warranty registration or sales receipts
or other documents maintained in the ordinary course of business by YANMAR
dealers and/or distributors, indicating the date of delivery of the YANMAR
product to the original retail purchaser. This information is necessary to
establish whether the YANMAR product is still within the warranty period.
Thus, YANMAR strongly recommends you register your generator as soon as
possible after purchase in order to facilitate any future warranty matters.
You are responsible for the transportation of the generator to and from the
repair location as designated by YANMAR.
To Locate an Authorized YANMAR Industrial Engine Dealer or Distributor:
You can locate your nearest authorized YANMAR industrial engine dealer or
distributor by visiting the YANMAR CO., LTD. website at:
http://www.yanmar.co.jp (The Japanese language page will be displayed.) For
English language “click” on “Global” icon.
· “Click” on “Dealer Locator” in the website heading to view the “Dealer
Locator” menu.
· Choose the Country from the pull down menu.
· Choose the Product Category from the pull down menu.
· “Click” on “Search” to browse YANMAR dealer or distributor.
· You may also contact YANMAR by clicking on “Contact” icon in the website
heading and typing in your question or comment.
What YANMAR will Do:
YANMAR warrants to the original retail purchaser of a new YANMAR generator
that YANMAR will make such repairs and/or replacements at YANMAR’s option, of
any part(s) of the YANMAR product covered by this warranty found to be
defective in material and/or workmanship. Such repairs and/or replacements
will be made at a location designated by YANMAR at no cost to the purchaser
for parts or labor.
ii
YDG Operation Manual
34127
YANMAR limited warranty – continued
YANMAR WARRANTIES
What is not Covered by this Warranty?
This warranty does not cover parts affected by or damaged by any reason other
than defective materials or workmanship including, but not limited to,
accident, misuse, abuse, “Acts of God,” neglect, improper installation,
improper maintenance, improper storage, the use of unsuitable attachments or
parts, the use of contaminated fuels, the use of fuels, oils, lubricants, or
fluids other than those recommended in your YANMAR Operation Manual,
unauthorized alterations or modifications, ordinary wear and tear, and rust or
corrosion. This warranty does not cover the cost of parts and/or labor
required to perform normal/scheduled maintenance on your YANMAR generator.
This warranty does not cover consumable parts such as, but not limited to
filters, fuel injector nozzle, lubricants and cleaning fluids. This warranty
does not cover the cost of shipping the product to or from the warranty repair
facility.
Warranty Limitations:
The foregoing is YANMAR’s only obligation to you and your exclusive remedy for
breach of warranty. Failure to follow the requirements for submitting a claim
under this warranty may result in a waiver of all claims for damages and other
relief. In no event shall YANMAR or any authorized industrial engine dealer or
distributor be liable for incidental, special or consequential damages. Such
consequential damages may include, but not be limited to, loss of revenue,
loan payments, cost of rental of substitute equipment, insurance coverage,
storage, lodging, transportation, fuel, mileage and telephone costs. The
limitations in this warranty apply regardless of whether your claims are based
on breach of contract, tort (including negligence and strict liability) or any
other theory. Any action arising hereunder must be brought within one (1) year
after the cause of action accrues or it shall be barred. Some states and
countries do not allow certain limitations on warranties or for breach of
warranties. This warranty gives you specific legal rights, and you may also
have other rights which vary from state to state and country to country.
Limitations set forth in this paragraph shall not apply to the extent that
they are prohibited by law.
Warranty Modifications:
Except as modified in writing and signed by the parties, this warranty is and
shall remain the complete and exclusive agreement between the parties with
respect to warranties, superseding all prior agreements, written and oral, and
all other communications between the parties relating to warranties. No person
or entity is authorized to give any other warranty or to assume any other
obligation on behalf of YANMAR, either orally or in writing.
Questions:
If you have any questions or concerns regarding this warranty, please call or
write to the nearest authorized YANMAR industrial engine dealer or distributor
or other authorized facility.
YDG Operation Manual
iii
YANMAR WARRANTIES
YANMAR limited warranty – continued
Retail Purchaser Registration
It is very important for the original retail purchaser to register the YANMAR
product. Registration enables YANMAR to provide the best support for your
YANMAR YDG diesel generator. At the time of purchase, YANMAR highly recommends
registering the retail purchaser’s information through website
http://www.yanmar.co.jp as soon as possible. If it is not possible to access
the website, please contact the nearest authorized YANMAR industrial engine
dealer or distributor.
iv
YDG Operation Manual
[ F I “Qr gtcvkqp”Ocpwcn
INTRODUCTION
Welcome to the world of YANMAR!
YANMAR has been the leader in industrial diesel engines for over 90 years. We
developed the world’s first practical small-sized diesel engine in 1933. Our
engineers are continuously developing new technology to keep YANMAR on the
leading-edge of the industry. The diesel-powered generator is only one example
of the new technology we have developed. We are committed to maintaining our
environment, and are proud of our history of innovation, quality and respect
for operator safety.
To help you enjoy your YANMAR diesel generator (YDG) for many years to come,
please follow these recommendations:
· Read and understand this Operation Manual before you operate the machine to
ensure that you follow safe operating practices and maintenance procedures.
· Keep this Operation Manual in a convenient place for easy access.
· If this Operation Manual is lost or damaged, order a new one from your
authorized YANMAR industrial engine dealer or distributor.
· Make sure this manual is transferred to subsequent owners. This manual
should be considered a permanent part of the generator and remain with it.
· Constant efforts are made to improve the quality and performance of YANMAR
products, so some details included in this Operation Manual may differ
slightly from your generator. If you have any questions about these
differences, please contact your authorized YANMAR industrial engine dealer or
distributor.
· When exporting or providing this product and manual to non-residents, please
comply with the security trade control laws and regulations of Japan and other
relevant countries.
YDG Operation Manual
v
INTRODUCTION
RECORD OF OWNERSHIP
Take a few moments to record the information you need when you contact YANMAR
for service, parts or literature. YDG
model:__
YDG serial
No.:___
Date
purchased:__
Dealer:__
Dealer
phone:____
vi
YDG Operation Manual
INTRODUCTION
34127
EC DECLARATION OF CONFORMITY
According with Machinery Directive 2006/42/CE, Annex II.1.A
Manufacturer: Address:
YANMAR ITALY s.p.a.
Via Camperio, 9 – 20123 Milano (MI)
We DECLARE hereby, under our sole responsibility
That the machine named: YANMAR DIESEL GENERATOR
Model:
Serial Number:
Year of construction:
IS IN CONFORMITY
With the provisions of the following European Directives:
–
Machinery Directive 2006/42/CE
–
Low Voltage Directive 2014/35/UE
–
Electromagnetic Compatibility (EMC) Directive 2014/30/UE
–
RoHS 2011/65/UE
And with the following harmonised standards:
Machinery: EN 12100, UNI EN ISO 8528-1, UNI EN ISO 8528-13 Low Voltage: EN 60204-1 Electromagnetic Compatibility: EN 55012:2007, EN 61000-6-1:2019
The manufacturer of the machinery, take the responsibilty to transmit, in response to a motivated request of the National Authorities, informations regarding the machinery related to this declaration.
Name and address of the pearson authorized to compile and keep the technical documentation :
Pearson empowered to draw up the declaration
__Ing._Ca_rl_o_C_a_v_a_l_le_r_o____ President (—————-)
____I_ng. _C_a_r_lo_C__a_v_a_lle_r_o____ President (—————-)
YDG Operation Manual
vii
INTRODUCTION This Page Intentionally Left Blank
viii
YDG Operation Manual
TABLE OF CONTENTS This Page Intentionally Left Blank
xii
YDG Operation Manual
[ F I “Qr gtcvkqp”Ocpwcn
SAFETY
YANMAR considers safety of great importance and recommends that anyone that
comes into close contact with its products, such as those that install,
operate, maintain or service YANMAR products, exercise care, common sense and
comply with the safety information in this manual and on the machine’s safety
decals. Keep the decals from becoming dirty or torn and replace them if they
are lost or damaged. Also, if you need to replace a part that has a decal
attached to it, make sure you order the new part and decal at the same time.
This safety alert symbol appears with most safety statements. It means
attention, become alert, your safety is involved! Please read and abide by the
message that follows the safety alert symbol.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor
or moderate injury.
NOTICE
Indicates a situation which can cause damage to the machine, personal property
and/or the environment or cause the equipment to operate improperly.
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or
serious injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death
or serious injury.
YDG Operation Manual
1
SAFETY
SAFETY PRECAUTIONS
There is no substitute for common sense and careful practices. Improper
practices or carelessness can cause burns, cuts, mutilation, asphyxiation,
other bodily injury or death. This information contains general safety
precautions and guidelines that must be followed to reduce risk to personal
safety. Special safety precautions are listed in specific procedures. Read and
understand all of the safety precautions before operation or performing
repairs or maintenance.
DANGER
Be assured no children or animals are in the surrounding zone of generator set
during operation and handling.
DANGER
· Never permit anyone to install or operate the generator set without proper
training.
· Read and understand this Operation Manual before you operate or service the
generator set to ensure that you follow safe operating practices and
maintenance procedures.
· Safety signs and decals are additional reminders for safe operating and
maintenance techniques.
· See your authorized YANMAR dealer or distributor for additional training.
Exhaust Hazard
·Never operate the generator in an enclosed area. Operating a generator
indoors can kill you in minutes. Generator exhaust contains carbon monoxide.
This is a poison you cannot see or smell. Only operate the generator outside
and far away from windows, doors and vents.
DANGER
Explosion Hazard
· Always place the diesel fuel container on the ground when transferring the
diesel fuel from the pump to the container. Hold the hose nozzle firmly
against the side of the container while filling it. This prevents static
electricity buildup which could cause sparks and ignite fuel vapors.
· Diesel fuel is flammable and explosive under certain conditions. Always
store any containers containing fuel in a well-ventilated area, away from any
combustibles or sources of ignition. Wipe up all spills immediately and never
use a shop rag to catch spilled fuel.
· Before you operate the engine, check for fuel leaks.
· Avoid serious personal injury. Never jump-start the engine. Sparks caused by
shorting the battery to the starter terminals may cause a fire or explosion.
Only use the key switch to start the engine.
· Avoid serious personal injury or equipment damage. While the engine is
running or the battery is charging, hydrogen gas is being produced and can be
easily ignited. Always keep the area around the battery well-ventilated and
keep sparks, open flames and any other form of ignition out of the area.
· Never place diesel fuel, flammable material such as oil, hay or dried grass
or chemical gases or fumes close to the engine during engine operation or
shortly after shut down.
· Never use metal pipe that carries combustible materials or gases to ground
the generator.
· Never operate the generator in explosion risk ambients
2
YDG Operation Manual
34127
DANGER
Electric Shock Hazard
· Always have a licensed electrician connect the generator to the utility
circuit. The generator must not be connected to other power sources.Improper
installation can cause the generator to back-feed into the utility power line.
This may electrocute a power company line repair person.
· Never use if the generator is wet or damp.
· Never use the generator in a location exposed to rain, snow, water spray or
standing water. If the generator must be used outside, protect it from the
weather. Moisture or ice can cause a malfunction or short circuit in the
electrical components which could result in electrocution.
· Never operate the generator in rain or a floodplain unless proper
precautions are taken to avoid being subject to rain or a flood.
· Never use any worn or damaged electrical cords. Electric shock or damage to
the generator may result.
· Never touch the generator with wet hands or when the generator is wet.
· Never use the generator in highly conductive areas. These areas include
metal decking and steelwork.
· Never handle live terminals or bare wires.
· Protection against indirect contact with live circuit parts is assured by
ELECTRICAL SEPARATION. The exposed conductive parts and conductive structural
parts need to be equipotential bonded. The coils of the alternator of the
generating sets are not bonded to the frame of the machine, therefore the
generating set MUST NOT be connected to an earthling system. Cables length
must be under 200 m in order to properly ensure safety for the end user. The
appliances
SAFETY
connected to the sockets of the gen-set, unless double insulated ones (class
II), must be equipped with PE conductor in order to ensure equipotential
bonding between the conductive structural parts of gen-set and the appliances.
· If using electrical separation protection method for indirect contact, the
GENSET must be physically disconnected from the ground (refer to page 66
scheme).
· It is therefore IMPORTANT that you ONLY use the generator to supply
equipment in the following combinations.
· One or more of “CLASS II“ equipment
· Only ONE item of “CLASS I“ equipment
· One or more of “CLASS II“ equipment and only ONE item of “CLASS I“
equipment.
· At page 66 are shown different cases of load connections. All not mentioned
connection schemes are NOT allowed.
· Protection by means of ELECTRICAL SEPARATION is not suitable for complex
circuits or for those ones placed in dangerous environments that could easily
lead to an electric shock. In these cases, the end user must comply with local
safety standards and laws. I.E. It is possible to install an RCD (30 mA) and
bond neutral to the frame of the gen-set (refer to page 67). This operation
must be carried out by qualified electricians only. Now the connection to an
earthling system become mandatory (see page 30), in order to ensure protection
against indirect contacts with live circuits by means of RCD, use the earth
terminal placed on the control panel of the gen-set and a high efficiency
cable.
YDG Operation Manual
3
SAFETY
DANGER
Fire Hazard
· Never use metal pipe that carries combustible materials or gases to ground
the generator.
· Do not put the generator indoors while the engine is still hot.
· Never jump-start the engine. Sparks caused by shorting the battery to the
starter terminals may cause a fire or explosion.
· Never operate the generator if powered items overheat, electrical output
drops, there is sparking, flames or smoke coming from the generator or if the
receptacles are damaged.
· Never operate the generator closer than 3.3 ft (1 m) away from buildings and
other equipment or sources of combustion during operation.
Falling Hazard
Avoid injury or equipment damage due to the generator set falling. Always
secure the generator set to prevent the generator set from falling during
maintenance.
WARNING
Explosion Hazard
· Avoid serious personal injury or equipment damage. While the engine is
running or the battery is charging, hydrogen gas is being produced and can be
easily ignited. Keep the area around the battery well-ventilated and keep
sparks, open flame and any other form of ignition out of the area.
· Avoid serious personal injury or equipment damage. Always turn off the
battery switch (if equipped) or disconnect the negative battery cable before
servicing the equipment.
Fire Hazard
· Avoid personal injury or equipment damage. Have appropriate safety equipment
available.
· Keep fire extinguishers handy in case of fire. Clearly indicate the location
of the fire extinguishers with a safety sign.
· Ensure that the type of fire extinguishers are appropriate for material that
might catch fire. Check with local authorities.
· Have all fire extinguishers checked periodically for proper operation and/or
readiness.
· Post evacuation routes prominently. Periodically conduct fire drills.
Avoid personal injury. Always read and follow safety-related precautions found
on containers of hazardous substances like parts cleaners, primers, sealants
and sealant removers.
Always wipe up all spills immediately.
The user must comply with safety regulation applicable in the place where the
genset has been sold.
4
YDG Operation Manual
34127
WARNING
Entanglement Hazard
· Rotating parts can cause severe injury or death. Never wear jewelry,
unbuttoned cuffs, ties or loose fitting clothing and always tie long hair back
when working near moving/rotating parts such as the flywheel or PTO shaft.
Keep hands, feet and tools away from all moving parts.
· Avoid personal injury. Never leave the key in the key switch when servicing
the generator set. Someone may accidentally start the engine and not realize
you are servicing it. Attach a “Do Not Operate” tag near the key switch while
performing maintenance on the equipment.
Severe Hazard
· Avoid personal injury. Rotating parts can cause severe injury or death.
·Never operate the generator without the guards in place.
Lifting Hazard
· Avoid serious personal injury. Additional equipment is necessary to lift the
generator set. Always use lifting equipment with sufficient capacity to lift
the generator.
· When you need to transport a generator set for repair, have a helper assist
you when attaching it to a hoist and loading it on a truck.
· During transportation, the generator must be switched off, the cables must
be disconnected and the tank must be empty.
· When you need to transport a generator set for repair, have a helper assist
you when attaching it to a hoist and loading it on a truck.
SAFETY
WARNING
Electrical Hazard
· Make welding repairs safely.
· Always turn off the battery switch (if equipped) or disconnect the negative
battery cable and the leads to the alternator when welding on the equipment.
· Connect the weld clamp to the component to be welded and as close as
possible to the welding point.
· Never connect the weld clamp to the generator set or in a manner which would
allow current to pass through a mounting bracket.
· When welding is completed, reconnect the leads to the engine charging system
prior to reconnecting the battery.
Shock Hazard
· Check the electrical harnesses for cracks, abrasions and damaged or corroded
connectors. Always keep the connectors and terminals clean.
· Avoid serious personal injury or equipment damage. Always turn off the
battery switch (if equipped) or disconnect the negative battery cable before
servicing the equipment.
· Avoid personal injury or equipment damage. Always keep the electrical
connectors and terminals clean. Check the electrical harnesses for cracks,
abrasions, and damaged or corroded connectors.
YDG Operation Manual
5
SAFETY
WARNING
Alcohol and Drug Hazard
Never operate the generator set while you are under the influence of alcohol
or drugs or are feeling ill.
Exposure Hazard
To avoid injury, always wear personal protective equipment including
appropriate clothing, gloves, work shoes, eye and hearing protection as
required by the task at hand.
Slip and Trip Hazard
Keep the generator free of oil, mud and other foreign matter.
Remove anything that creates slippery areas around the generator.
Sudden Movement Hazard
· Never attach tools or appliances to the generator before it is started.
Starting the generator may cause sudden movement of the equipment. Disconnect
any tools and appliances from the generator before starting.
· Before you start the engine make sure that all bystanders are clear of the
area.
· Check before starting the engine that any tools or shop rags used during
maintenance have been removed from the area.
· Always remove anything that creates slippery areas around the generator.
· Avoid personal injury. Always stop the engine before beginning service.
WARNING
Burn Hazard
· Avoid serious injury. Some of the generator set surfaces become very hot
during operation and shortly after shut down. Always keep hands and other body
parts away from hot generator set surfaces.
· Always handle hot components with heat-resistant gloves.
· Never remove shields present on generator set. Ordinary maintenance
activities can be safely carried out with shields assembled.
· Before starting any maintenance activity, let the generator set components
(such as muffler) cool down for at least 20 minutes
Tool Hazard
Avoid personal injury or equipment damage. Always remove any tools or shop
rags used during maintenance from the area before operation.
Exhaust Hazard
Avoid serious injury or death. Always ensure that all connections are
tightened to specifications after repair is made to the exhaust system. All
internal combustion engines create carbon monoxide gas during operation and
special precautions are required to avoid carbon monoxide poisoning.
6
YDG Operation Manual
34127
CAUTION
Flying Object Hazard
· Avoid personal injury. Always wear eye protection when servicing the
generator set or when using compressed air or high-pressure water. Dust,
flying debris, compressed air, pressurized water or steam may injure your
eyes.
· Avoid personal injury. Always wear eye protection when servicing the engine
or when using compressed air or high-pressure water. Dust, flying debris,
compressed air, pressurized water or steam may injure your eyes.
Poor Lighting Hazard
Avoid personal injury or equipment damage. Ensure that the work area is
adequately illuminated. Always install wire cages on portable safety lamps.
Tool Hazard
Avoid personal injury or equipment damage. Always use tools appropriate for
the task at hand and use the correct size tool for loosening or tightening
machine parts.
Before starting the engine, always turn the switches on the working appliances
(lighting apparatus, motor, etc.) to their OFF position. If the switches are
not OFF, the sudden application of load when the engine is started could be
very dangerous.
SAFETY
NOTICE
Never attempt to modify the generator set design or safety features such as
defeating the engine speed limit control or the diesel fuel injection quantity
control.
Modifications may impair the generator set’s safety and performance
characteristics and shorten the generator set’s life. Any alterations to this
generator set may avoid its warranty. Always use YANMAR genuine replacement
parts.
Always be environmentally responsible. Follow the guidelines of the
governmental agencies for the proper disposal of hazardous materials such as
engine oil, and diesel fuel. Consult the local authorities or reclamation
facility.
Contact your authorized YANMAR industrial engine dealer or distributor if you
need to operate the engine at high altitudes. At high altitudes the engine
will lose power, run rough, and produce exhaust gases that exceed the design
specifications.
· Always use correct polarity when you connect battery cables to the battery.
This generator uses a negative ground, 12 VDC starting system.
· Make sure battery terminals are clean.
· Make sure cable connections are tight.
· Always shut down engine before removing or attaching battery cables.
YDG Operation Manual
7
SAFETY
NOTICE
If you remove battery from generator, insulate the terminal on the end of the
red, positive (+) battery cable. If the terminal is not insulated, it may
spark when generator runs. Sparks may cause damage to the generator’s
electronic circuits
Never operate the generator if it vibrates at high levels, if engine speed
changes greatly or if the engine misfires often.
Never use an engine starting aid such as ether. Engine damage will result.
Always make sure the generator is operated on a level surface. If operated at
an angle greater than 20° (in any direction) the battery could leak fluid. The
generator must be on a flat level surface when checking the battery fluid
level. If an engine runs for short periods of time (less than three minutes)
at an angle greater than 25° in any direction, engine oil may enter the
combustion chamber causing excessive engine speed and generate white smoke.
This may cause serious engine damage.
Always run the engine at full speed. Never run engine at lower speeds. At full
speed, the engine runs at 3000 (or 3600) min-1 (rpm) under load. The engine
must maintain 3000 (or 3600) min-1 (rpm) for generator to create correct
voltage. Running engine at lower speeds will damage generator and powered
items.
Never attach tools or appliances to the generator before it is started. Always
disconnect tools and appliances from the generator before starting.
NOTICE
Observe the following environmental operating conditions to maintain engine
performance and avoid premature engine wear:
· The standard range of ambient temperatures for the normal operation of
YANMAR engines is from +5 °F (-15 °C) to +113 °F (+35 °C).
· If the ambient temperature exceeds +113 °F (+35 °C) the engine may overheat
and cause the engine oil to break down.
· If the ambient temperature is below +5 °F (-15 °C) the engine will be hard
to start and the engine oil may not flow easily.
Contact your authorized YANMAR industrial engine dealer or distributor if the
engine will be operated outside of this standard temperature range.
Observe the following environmental operating conditions to maintain generator
set performance and avoid premature engine wear:
· Avoid operating in extremely dusty conditions.
· Avoid operating in the presence of chemical gases or fumes.
· Avoid operating in a corrosive atmosphere such as salt water spray.
Any part which is found defective as a result of inspection or any part whose
measured value does not satisfy the standard or limit must be replaced.
Always tighten components to the specified torque. Loose parts can cause
equipment damage or cause it to operate improperly.
Only use replacement parts specified. Other replacement parts may affect warranty coverage.
8
YDG Operation Manual
34127
NOTICE
If any indicator illuminates during engine operation, stop the engine
immediately. Determine the cause and repair the problem before you continue to
operate the engine.
Never operate the generator if:
· Engine speed changes greatly
· Engine misfires often
· Powered items overheat
· Electrical output drops
· It is sparking
· It produces smoke or flames
· It vibrates at high levels
· It has a damaged receptacle
Always protect the air cleaner and electric components from damage when you
use steam or high pressure water to clean the generator.
Always turn battery switch OFF (if equipped) or disconnect the negative
battery cable before servicing the electrical system.
Never operate the generator set while wearing a headset to listen to music or
radio because it will be difficult to hear warning signals.
When the engine is operated in dusty conditions, clean the air cleaner element
more frequently. Never operate the engine with the air cleaner element(s)
removed. This may cause foreign material to enter the engine and damage it.
SAFETY
YDG Operation Manual
9
SAFETY
FORESEEABLE MISUSE
Foreseeable misuse and improper applications include, but are not limited to,
the following:
– Operation not in compliance with the instructions given into this manual.
– Operation not in compliance with safety related instructions.
– Operation with the machine when it is not working in perfect conditions,
either functionally or in terms of safety.
– Operation without following the inspection/maintenance schedule.
– Any unauthorized modification of or removal of safety equipment.
– Use of spare parts and accessories that are unsuitable or have not been
approved by Yanmar.
– Operation in flammable or hazardous environments.
– Operation in closed-off or poorly ventilated rooms.
10
YDG Operation Manual
PRODUCT YDG Operation Manual
OVERVIEW
YANMAR YDG DIESEL GENERATOR FEATURES AND APPLICATIONS
To achieve the highest performing miniaturized and light-weight diesel
engines, YANMAR CO., LTD. developed the LV series single cylinder, air-cooled,
diesel engine for applications such as YANMAR YDG generators.
YANMAR’s series of LV engines use one of the most advanced single cylinder
technologies available.
Yanmar YDG generators are designed to supply power to a wide variety of
applications including:
· Construction
· Agriculture
· Household
We are sure that you will agree these features provide excellent value in an
industrial diesel generator.
YDG Operation Manual
11
PRODUCT OVERVIEW
COMPONENT IDENTIFICATION
YDG3700V-5(E)BYI2 and YDG3700N-6(E)BYI2 (Typical model)
1 23 4
5
7
89
10 11
12
13 6
14 15
22
21
20
19 18 17 16
1 Muffler 2 Starter solenoid (only for electric version) 3 Starter motor (only for electric version) 4 Engine nameplate decal 5 Frame 6 Control panel 7 Fuel tank 8 Fuel filler cap 9 Starter switch (only for electric version) 10 Compression release lever 11 Fuel injection pump 12 Air cleaner
13 Generator set model and serial number decal 14 Engine control lever 15
Recoil starter 16 Oil filler cap/dipstick 17 Oil drain plug 18 Oil
filter 19 Oil pressure switch 20 Generator unit 21 Generator/engine
damper mounts 22 Battery (only for electric version)
Figure 1
12
YDG Operation Manual
PRODUCT OVERVIEW
34127
YDG5500V-5(E)BYI2 and YDG5500N-6(E)BYI2 (Typical model)
12 3 4
5
7
89
10 11
12
13 6
14 15
22
21
20
19 18 17 16
06346 -00X00
1 Muffler 2 Starter solenoid (only for electric version) 3 Starter motor (only for electric version) 4 Engine nameplate decal 5 Frame 6 Control panel 7 Fuel tank 8 Fuel filler cap 9 Starter switch (only for electric version) 10 Compression release lever 11 Fuel injection pump 12 Air cleaner
. 13 Generator set model and serial number decal
14 Engine control lever 15 Recoil starter 16 Oil filler cap/dipstick 17
Oil drain plug 18 Oil filter 19 Oil pressure switch 20 Generator unit
21 Generator/engine damper mounts 22 Battery (only for electric version)
Figure 2
YDG Operation Manual
13
PRODUCT OVERVIEW
LOCATION OF LABELS
Safety Decals
YDG3700V-5(E)BYI2, YDG5500V-5(E)BYI2, YDG3700N-6(E)BYI2, YDG5500N-6(E)BYI2
DIESEL FUEL ONLY
DO NOT USE GASOLINE
14
H L
CAUTION
DIESEL FUEL FLAMMABLE
ENGINE MUST BE TURNED OFF WHEN ADDING FUEL DO NOT OPERATE THE ENGINE INDOORS
OR IN POORLY VENTILATED PLACES. “SLOW” POSITION : NO LOAD ONLY
CHECK THE ENG -INE OIL (CC CLASS) SAE 10W30 (OIL CHANGE EYE
-RY 100hr.
H L
DO NOT OPERATE THE ENGINE IN STAND WATER OR RAIN
READ OPERATION MANUAL FOR COMPLETE INSTRUCTIONS.
OPERATION
CHECK FUEL AND ENGINE OIL LEVEL BEFORE STARTING. (OPEN THE FUEL COCK) MOVE THE ENGINE SPEED LEVEL TO THE “RUN” POSITION.
STARTING (RECOIL) 1) PULL THE STARTING ROPE SLOWLY UNTIL
YOU FEEL RESISTANCE, RETURN ROPE. 2) PUSH THE DECOMPRESSION LEVER DOWN. 3)
PULL THE STARTER ROPE HARD AND FAST,
ALL THE WAY OUT. (ELECTRIC)
(RECOIL) RETURN ENGINE SPEED LEVER TO “STOP” POSITION. (ELECTRIC) TURN KEY TO “OFF” POSITION. (CLOSE FUEL COCK.)
WARM UP ENGINE FOR ABOUT 5 MINUTES.
View Y
Y
LOW OIL WARNING
IN THE CASE OF AUTO-STOP, DO NOT RUN WITHOUT CHECKING OIL LEVEL
CHECK ENGINE OIL EACH TIME FUEL TANK IS FILLED SAE 10W30(CC CLASS)
Figure 3
YDG Operation Manual
34127
Generator Set Decal
PRODUCT OVERVIEW
The YDG generator set model and serial number information decal is located inside the top front frame rail.
DIESEL FUEL ONLY
DO NOT USE GASOLINE
CAUTION
DIESEL FUEL FLAMMABLE
ENGINE MUST BE TURNED OFF WHEN ADDING FUEL DO NOT OPERATE THE ENGINE INDOORS
OR IN POORLY VENTILATED PLACES. “SLOW” POSITION : NO LOAD ONLY
CHECK THE ENG -INE OIL (CC CLASS) SAE 10W30 (OIL CHANGE EYE
-RY 100hr.
H L
DO NOT OPERATE THE ENGINE IN STAND WATER OR RAIN
READ OPERATION MANUAL FOR COMPLETE INSTRUCTIONS.
OPERATION
CHECK FUEL AND ENGINE OIL LEVEL BEFORE STARTING. (OPEN THE FUEL COCK) MOVE THE ENGINE SPEED LEVEL TO THE “RUN” POSITION.
STARTING (RECOIL) 1) PULL THE STARTING ROPE SLOWLY UNTIL YOU FEEL RESISTANCE, RETURN ROPE. 2) PUSH THE DECOMPRESSION LEVER DOWN. 3) PULL THE STARTER ROPE HARD AND FAST, ALL THE WAY OUT. (ELECTRIC)
726723(1*,1(
(RECOIL) RETURN ENGINE SPEED LEVER TO “STOP” POSITION. (ELECTRIC) TURN KEY TO
“OFF” POSITION. (CLOSE FUEL COCK.)
WARM UP ENGINE FOR ABOUT 5 MINUTES.
Yanmar Italy S.p.A Via Camperio, 9 – 20123 Milano, Italia
Low power generating set model: A Serial Number: B
Performance Class: G2
Made in Italy: C Mass (dry): D
RATED (ISO 8528)
E kW
MAX (ISO 8528)
H kW
Frequency K Hz
FV
GA
IV
JA
Power Factor 1
RPM L
I.C. H
IP 23M
ALTIT. 100 m
TEMP. 25 ~C
Figure 4
Description of Generator Set Model Number
YDG 5500 V – 5 (E) B Destination
Starting system E: Electric starting No symbol: Manual starting
Frequency 5: 50Hz 6: 60Hz
Exhaust gas emission regulations V : Euro Stage V emission regulation N: No
emission regulation
Type
Generator series
YDG Operation Manual
15
PRODUCT OVERVIEW
Generator Decal
The generator decal is located on the left side of the generator body.
Engine Nameplate (Typical)
The engine nameplate (Figure 7) is located on the cooling shroud on the PTO
side of engine above the starter (1, Figure 6).
1
View Z Z
Figure 5
Figure 6
MODEL MAX. OUTPUT DISPLACEMENT ENGINE NO.
kW /
min-1
l
MADE IN ITALY
Figure 7
16
YDG Operation Manual
34127
FUNCTION OF MAJOR COMPONENTS
PRODUCT OVERVIEW
Components Air cleaner Dynamo
Low engine oil shutdown
Engine oil filter Side filler ports (engine oil) Fuel filters Fuel tank Oil
cap/dipstick (engine oil) Starter motor Control panel
Generator
Functions
The air cleaner prevents airborne contaminants from entering the engine.
Periodic replacement of the air cleaner filter element is necessary. See
Periodic Maintenance Schedule on page 47 for the replacement frequency.
If the engine is equipped with electric start, a charging dynamo is located
under the engine flywheel. The dynamo supplies regulated electricity to the
engine systems and charges the battery while the engine is running.
The generator is equipped with a low oil shutdown feature. If the engine is
run when it is low on oil, the oil pressure will drop. The oil pressure switch
will sense the drop in pressure and activate the stop solenoid, which will
shut the engine down. Once the oil level is corrected, and pressure is normal,
the engine can be run again.
The engine oil filter removes contaminants and sediment from the engine oil.
Periodic cleaning of the oil filter is necessary. See Periodic Maintenance
Schedule on page 47 for the frequency of cleaning.
You can fill the crankcase with engine oil from either side of the engine
depending upon which filler port is most convenient.
Inlet and outlet fuel filters are provided to remove contaminants and sediment
from the diesel fuel. Periodic cleaning/replacement is required. See Periodic
Maintenance Schedule on page 47.
The fuel tank is a reservoir that holds diesel fuel. Fuel is gravity-fed to
the fuel injection pump. Since fuel is used to keep fuel system components
cool and lubricated, more fuel than is necessary for combustion enters the
fuel system. Any fuel that is not used for combustion is returned to the fuel
tank.
The engine oil cap/dipstick combines the oil cap and dipstick in one assembly.
The dipstick part of the assembly is used to determine the amount of engine
oil in the crankcase.
The starter motor is powered by the battery. When you turn the key switch to
the START position, the starter motor engages with the ring gear installed on
the flywheel and starts the flywheel in motion.
The control panel houses all the controls, switches, terminals, outlets and
meters for the generator. All electrical power created by the generator is
directed to the control panel and output is sent through various outlets and
terminals located on the control panel.
The generator is coupled to the engine to produce electrical power to operate
various loads and or machines. The generator is constructed as a self-exciting
single phase A/C, and is comprised of a stator, rotor, automatic voltage
regulator, rectifier and housing components.
YDG Operation Manual
17
PRODUCT OVERVIEW
GENERATOR CONTROL PANEL
YDG3700V-5BYI2, YDG5500V-5BYI2, YDG3700N-6BYI2, YDG5500N-6BYI2
1
2
0
240
~ 0 V 200
3
7
6
5
4
1 Voltage meter 2 AC circuit breaker
(Generator main switch-circuit breaker) 3 DC circuit breaker (12 VDC output)
. 4 12 VDC output receptacle
(For 12 VDC battery charging only) 5 Grounding terminal 6 Schuko socket
(230V) 7 CEE socket (230V)
Figure 8
18
YDG Operation Manual
PRODUCT OVERVIEW
34127
YDG3700V-5EBYI2, YDG5500V-5EBYI2, YDG3700N-6EBYI2, YDG5500N-6EBYI2
1
2
3
0
240
~ 0 V 200
4
8
1 Voltage meter 2 AC circuit breaker
(Generator main switch-circuit breaker) 3 Engine start key switch 4 DC
circuit breaker (12 VDC output)
7
6
5
. 5 12 VDC output receptacle
(For 12 VDC battery charging only) 6 Grounding terminal 7 Schuko socket
(230V) 8 CEE socket (230V)
Figure 9
YDG Operation Manual
19
PRODUCT OVERVIEW
AIR COOLED ENGINE
The engine is air-cooled by a cooling fan. The cooling system consists of a
fan attached to the flywheel. The fan blows air past the cooling fins on the
cylinder head and cylinder, which are enclosed by shrouds that direct the air
flow.
2
ENGINE CONTROLS – RECOIL
STARTER
1
The engines are equipped with a recoil and an electric starter. This section explains the controls available with the recoil starter.
Recoil Starter
A recoil starter allows you to manually start an engine by pulling on the recoil starter handle (1, Figure 10). When you pull on the handle you set the flywheel and crankshaft in motion. The recoil starter is spring-loaded so the handle and attached rope automatically return to the recoil starter assembly.
Decompression Lever
Pressing the decompression lever (2, Figure 10) helps you start the engine by reducing the effort needed to pull the recoil starter handle. The decompression lever will automatically return to the original position when the engine starts.
Figure 10
K0002447A-00X
20
YDG Operation Manual
34127
ENGINE CONTROLS – ELECTRIC STARTER
Key Switch
The generator is equipped with a three position key switch – OFF, ON, and
START.
1
2
OFF
ON
PRODUCT OVERVIEW
START (3, Figure 11) – Turn the key to this position to start the engine. As
soon as the engine starts, release the key and it will automatically return to
the ON position.
NOTICE
Never hold the key in the START position for longer than 15 seconds or the
starter motor will overheat.
Engine Speed Control Lever
NOTICE
If using the stop lever to shut-down the engine, be sure to return the key
switch to the OFF position to prevent discharging of the battery.
3
START
STARTER SW
K0002413A-00X
Figure 11
OFF (key straight up and down) (1, Figure 11) When you turn the key to this
position the engine shuts down. Electric current to the battery, low engine
oil shutdown device and other electric devices is shut off. The key can be
inserted and removed from this position.
ON (2, Figure 11) – This is the position the key will be in when the engine is
running. After starting engine, key switch will automatically return to this
position.
The engine speed control lever (1, Figure 12) is moved to the run position (2,
Figure 12) for generator operation. To stop the generator, turn the key switch
to the OFF position, or push down on the stop lever (3, Figure 12) and the
speed control lever (1, Figure 12), which is spring-loaded, will move back to
the stop position.
1 2
RUN STOP
3
K0002443A-00X
Figure 12
YDG Operation Manual
21
PRODUCT OVERVIEW This Page Intentionally Left Blank
22
YDG Operation Manual
BEFORE YOU YDG Operation Manual OPERATE
INTRODUCTION
This section of the Operation Manual describes activating a new battery,
diesel fuel and engine oil specifications and how to replenish them. It also
describes the proper way to connect the electrical loads to the generator and
the daily engine checkout.
Before performing any storage procedures within this section, review the
Safety section on page 1.
YDG Operation Manual
23
BEFORE YOU OPERATE
BATTERY
Checking Battery Electrolyte Level
DANGER
Never check the remaining battery charge by shorting out the terminals. This
will result in a spark and may cause an explosion or fire. Use a hydrometer to
check the remaining battery charge.
WARNING
Batteries contain sulfuric acid. Never allow battery fluid to come in contact
with clothing, skin or eyes. Severe burns could result. Always wear safety
goggles and protective clothing when servicing the battery. If battery fluid
contacts the eyes and/or skin, immediately flush the affected area with a
large amount of clean water and obtain prompt medical treatment.
· If the engine cranking speed is so slow that the engine does not start, recharge the battery.
· If the engine still will not start after charging, have
your authorized YANMAR industrial engine dealer
or distributor check the battery and the engine’s
1
starting system.
· If operating the machine where the ambient
temperature could drop to 14 °F (-10 °C) or less,
remove the battery from the machine at the end
of the day. Store the battery in a warm place until
2
the next use. This will help start the engine easily
at low ambient temperatures.
Figure 1
· When the amount of fluid nears the lower limit line (2, Figure 1), remove
caps and fill with distilled water so it is at the upper limit line (1, Figure
1). If operation continues with insufficient battery fluid, the battery life
is shortened, and the battery may overheat and explode. During the summer,
check the fluid level more often than specified.
24
YDG Operation Manual
34127
Charging the Battery
1. Disconnect the battery cables from the battery. See Disconnecting and
Connecting Battery Cables on page 25.
2. Clean terminals on the battery and clamps on the end of the cables.
3. Connect the positive (+) clamp from the charger to the positive (+)
terminal on the battery.
DANGER
· If the electrolyte is frozen, slowly warm the battery before you recharge
it.
· Avoid serious personal injury or equipment damage. Before charging, remove
the cap from each cell of the battery and always make sure there is plenty of
ventilation when charging battery. Discontinue charging if the electrolyte
temperature exceeds 117 °F (45 °C). While the engine is running or the battery
is charging, hydrogen gas is being produced and can be easily ignited. Always
keep the area around the battery well-ventilated and keep sparks, open flames
and any other form of ignition out of the area.
· Never charge the battery while connected. The diodes will be damaged by the
high voltage. Connect the (+) lead of the charger to the (+) terminal of the
battery, and the () lead to the () terminal. Reversed polarity will damage
the charger rectifier or the battery. After charging is completed, connect the
battery cables correctly to the battery. Reversed polarity wiring will damage
the diodes. Quick-charging should only be done in an emergency; slow charging
is recommended.
BEFORE YOU OPERATE
(-)
(+)
Figure 2
5. When finished charging the battery, unplug the charger before
disconnecting clamps from the battery. See Disconnecting and Connecting
Battery Cables on page 25.
Disconnecting and Connecting Battery Cables
CAUTION
This generator uses a negative ground 12 VDC starting system. Always shut down
the engine before removing or attaching battery cables. Always remove the
negative () cable first. Always attach the negative () cable last
1. When disconnecting cables, loosen and disconnect negative () cable (1,
Figure 3) first from battery.
2. Disconnect positive (+) cable (2, Figure 3) from battery last.
4. Connect the negative () clamp from the charger to the negative () terminal on the battery.
YDG Operation Manual
25
BEFORE YOU OPERATE
(-) 1
(+)
2
Figure 3
3. When connecting cables to battery connect the positive (+) cable (1,
Figure 4) first.
CAUTION
When you install a battery, always use correct polarity when you connect
battery cables to the battery. Always make sure the battery terminals are
clean and tight.
4. Connect the negative () cable (2, Figure 4) to the battery last.
(-) 2
(+)
1
Figure 4
DIESEL FUEL
Diesel Fuel Specifications
Diesel fuel should comply with the following specifications. The table lists
several worldwide specifications for diesel fuels.
NOTICE
Always use diesel fuels recommended by YANMAR for the best engine performance,
to prevent engine damage. Only use clean diesel fuel.
Diesel fuel specification EN590:96 ISO 8217 DMX BS 2869-A1 or A2 JIS K2204 grade No.2 KSM-2610 GB252
Location European Union International United Kingdom Japan Korea China
Additional technical fuel requirements
· The fuel cetane number should be equal to 45 or higher.
· The sulfur content must not exceed 0.5 % by volume. Less than 0.05 % is
preferred.
· Bio-diesel fuels. See Bio-diesel fuels on page 27.
· Never mix kerosene, used engine oil, or residual fuels with the diesel fuel.
· Water and sediment in the fuel should not exceed 0.05 % by volume.
· Keep the fuel tank and fuel-handling equipment clean at all times.
· Poor quality fuel can reduce engine performance and/or cause engine damage.
· Fuel additives are not recommended. Some fuel additives may cause poor
engine performance. Consult your YANMAR industrial engine dealer or
distributor for more information.
26
YDG Operation Manual
34127
· Ash content not to exceed 0.01 % by volume.
· Carbon residue content not to exceed 0.35 % by volume. Less than 0.1 % is
preferred.
· Total aromatics content should not exceed 35 % by volume. Less than 30 % is
preferred.
· PAH (Polycyclic Aromatic Hydrocarbons) content should be below 10 % by
volume.
· Metal content of Na, Mg, Si, and Al should be equal to or lower than 1 mass
ppm. (Test analysis method JPI-5S-44-95)
· Lubricity: Wear mark of WS1.4 should be Max. 0.018 in. (460 µm) at HFRR
test.
Bio-diesel fuels
In Europe and in the United States, as well as some other countries, non-
mineral oil based fuel resources such as RME (Rapeseed Methyl Ester) and SOME
(Soybean Methyl Ester), collectively known as FAME (Fatty Acid Methyl Esters),
are being used as extenders for mineral oil derived diesel fuels.
YANMAR approves the use of bio-diesel fuels that do not exceed a blend of 7 %
(by volume) of FAME with 93 % (by volume) of approved mineral oil derived
diesel fuel. Such bio-diesel fuels are known in the marketplace as B7 diesel
fuels.
These B7 diesel fuels must meet certain requirements 1. The bio-fuels must
meet the minimum
specifications for the country in which they are used.
· In Europe, bio-diesel fuels must comply with the European Standard EN14214
and EN590 (for Oxidation stability).
· In the United States, bio-diesel fuels must comply with the American
Standard ASTM D-6751 and ASTM D-7467 (for Oxidation stability).
2. Bio-fuels should be purchased only from recognized and authorized diesel
fuel suppliers.
In North America, bio-diesel and bio-diesel blends must be purchased from the
BQ-9000 accredited producers and BQ-9000 certified distributors.
BEFORE YOU OPERATE
Precautions and concerns regarding the use of bio-fuels:
1. Free methanol in FAME may result in corrosion of aluminum and zinc FIE
components.
2. Free water in FAME may result in plugging of fuel filters and increased
bacterial growth.
3. High viscosity at low temperatures may result in fuel delivery problems,
injection pump seizures, and poor injection nozzle spray atomization.
4. FAME may have adverse effects on some elastomers (seal materials) and may
result in fuel leakage and dilution of the engine lubricating oil.
5. Even bio-diesel fuels that comply with a suitable standard as delivered,
will require additional care and attention to maintain the quality of the fuel
in the equipment or other fuel tanks. It is important to maintain a supply of
clean, fresh fuel. Regular flushing of the fuel system, and/or fuel storage
containers, may be necessary.
6. The use of bio-diesel fuels that do not comply with the standards as
agreed to by the diesel engine manufacturers and the diesel fuel injection
equipment manufacturers, or bio-diesel fuels that have degraded as per the
precautions and concerns above, may affect the warranty coverage of your
engine. See YANMAR Limited Warranty on page i.
YDG Operation Manual
27
BEFORE YOU OPERATE Filling the Fuel Tank
DANGER
Only fill the fuel tank with diesel fuel. Filling the fuel tank with gasoline
may result in a fire and will damage the engine, never refuel with the engine
running.
1
2
ENGINE OIL
The YANMAR YDG generators are equipped with a low oil pressure stop device.
This device stops the engine automatically when the oil pressure falls below
the specified level and prevents engine seizure when engine oil is low.
Engine Oil Specifications
NOTICE
Never mix different types of engine oil. This may adversely affect the
lubricating properties of the engine oil. Only use the engine oil specified.
Other engine oils may affect warranty coverage, cause internal engine
components to seize, and/or shorten engine life.
Figure 5
K0002458A-00X
1. Clean the area around the fuel cap.
2. Remove the fuel cap (1, Figure 5) from the fuel tank.
CAUTION
Never remove inlet fuel screen from the filler port when filling the fuel
tank. If removed, dirt and debris could get into the fuel system causing it to
clog.
3. Stop fueling when the fuel is at the same level as the red ring (2, Figure
5) at the bottom of the inlet fuel screen.
DANGER
Never overfill the fuel tank.
4. Replace the fuel cap and hand-tighten. Over-tightening the fuel cap will damage it.
Use an engine oil that meets or exceeds the following guidelines and
classifications:
Service categories
· API service categories CD or higher
· ACEA service categories E-3, E-4, and E-5
· JASO service category DH-1
Definitions
· API classification (American Petroleum Institute)
· ACEA classification (Association des Constructeurs Européens d’Automobilies)
· JASO (Japanese Automobile Standards Organization)
Note:
· Be sure the engine oil, engine oil storage containers, and engine oil
filling equipment are free of sediments and water.
· Change the engine oil after the first 50 hours of operation and then every
200 hours thereafter.
· Select the oil viscosity based on the ambient temperature where the engine
is being operated. See the SAE service grade viscosity chart (Figure 6).
· YANMAR does not recommend the use of engine oil “additives”.
28
YDG Operation Manual
34127
Additional technical engine oil requirements:
The engine oil must be changed when the Total Base Number (TBN) has been
reduced to 2.0. TBN (mgKOH/g) test method; JIS K-201-5.2-2 (HCI), ASTM D4739
(HCI).
Engine Oil Viscosity
Select the appropriate engine oil viscosity based on the ambient temperature
using the SAE service grade viscosity chart in (Figure 6).
SAE 10W SAE 20W SAE 10W-30 SAE 15W-40 SAE 20 SAE 30 SAE 40 SAE 20W – 50
-4°F 14°F 32°F 50°F 68°F 86°F 104°F 122°F (-20°C) (-10°C) (0°C) (10°C) (20°C) (30°C) (40°C) (50°C)
K0000005A00
Figure 6
BEFORE YOU OPERATE
Checking Engine Oil
1. Make sure engine is level. 2. Remove oil cap/dipstick (1, Figure 7) from
either location and wipe with clean cloth.
NOTICE
Prevent dirt and debris from contaminating the engine oil. Always clean the
oil cap/dipstick and the surrounding area before you remove the cap.
3. Reinsert oil cap/dipstick into crankcase and turn clockwise for one-half
revolution to engage the first thread in the crankcase opening.
4. Remove oil cap/dipstick. The oil level should be between upper (2, Figure
7) and lower (3, Figure 7) lines on the oil cap/dipstick.
NOTICE
Always keep the oil level between the upper and lower lines on the oil
cap/dipstick.
5. Fully reinsert oil cap/dipstick (1, Figure 7) and hand-tighten. Over-
tightening the oil cap/dipstick will damage it.
1
2
3
4
Figure 7
YDG Operation Manual
29
BEFORE YOU OPERATE
Adding Engine Oil
1. Make sure engine is level. 2. Remove oil cap/dipstick (1, Figure 7). 3.
Add indicated amount of engine oil at either one
of the engine oil filler ports (4, Figure 7). 4. Wait one minute and check oil
level. 5. Add engine oil as needed until the level is
between the upper (2, Figure 7) and lower (3, Figure 7) lines on the oil
cap/dipstick.
NOTICE
Never overfill. Overfilling may result in white exhaust smoke, engine
overspeed or internal damage.
6. Fully reinsert oil cap/dipstick and hand-tighten. Over-tightening the oil
cap/dipstick will damage it.
Engine Oil Capacity
The following table shows engine oil capacities for YANMAR YDG generators.
Engine/generator model
Engine L70V(N) generator YDG3700V(N)
Engine L100V(N) generator YDG5500V(N)
Dipstick upper limit/lower limit
1.11/0.69 qt (1.05/0.65 L)
1.7/1.06 qt (1.6/1.0 L)
GENERATOR CHECK
WARNING
Always have a licensed electrician connect the generator to the utility
circuit. The generator must not be connected to other power sources. Improper
installation can cause the generator to back-feed into the utility power line.
This may electrocute a power company line repair person. Also, if the
generator is powering electrical circuits, the chance of an electrical fire
exists.
1. Only use grounded extension cords. Be sure to use an extension cord with the proper wire gauge size. See the following table.
Recommended minimum wire gauges (AWG) for extension cords
Ampere load
AWG for length of cord ft (m)
50 (15) 100 (30) 150 (46)
2
18
18
18
3
18
18
18
4
16
16
16
5
16
16
16
6
16
16
14
8
16
14
12
10
16
14
12
12
14
14
12
14
14
12
10
16
12
12
10
20
10
10
8
2. If electrical separation cannot be adopted for indirect contact protection
(see page 3), properly ground the unit:
· Attach a #10 stranded-copper ground wire to the ground lug.
· Drive a grounding point into the ground. The grounding point can be a stake,
grounding rod or pipe. The grounding point should be copper or brass.
CAUTION
Never use metal pipe that carries combustible materials or gases to ground the
generator. Always ground the generator. Connect a length of heavy wire between
the generator ground terminal and an external ground.
30
YDG Operation Manual
34127
· Attach the ground wire to the grounding point (1, Figure 8). You must supply
the ground wire and grounding point. These are not supplied with the
generator. Follow the local safety standards. Consult your power company or a
licensed electrician.
YDG3700V-5B, YDG5500V-5B
YDG3700N-6B, YDG5500N-6B
BEFORE YOU OPERATE
. (1, Figure 9) shows the main AC switch on the YDG3700V-5B generator.
YDG3700V-5B, YDG5500V-5B YDG3700N-6B, YDG5500N-6B
1
0
240
~ 0 V 200
0
240
~ 0 V 200
1
Figure 8
3. Select the proper load for use with the generator set. See Selecting the
Proper Load on page 32.
4. Before starting, always turn OFF the main AC switch of the generator (1,
Figure 9) or (1, Figure 10) and any other loads. Make sure nothing is plugged
into or connected to the generator.
CAUTION
Do not start two or more appliances simultaneously and always start them one
at a time. Never use floodlights with other appliances. Connection with
utilities must be done only with sockets located on generator control panel.
Figure 9 (1, Figure 10) shows the main AC switch on the YDG5500V-5EB
generators.
YDG3700V-5EB, YDG5500V-5EB YDG3700N-6EB, YDG5500N-6EB
1
0
240
~ 0 V 200
Figure 10
YDG Operation Manual
31
BEFORE YOU OPERATE
Selecting the Proper Load
CAUTION
· Never exceed the specified current limit for any one electrical terminal.
· Most home utility electric service is more than 60 amps. This generator will
not power your entire home. This will exceed generator output. Only power
items needed during a power outage. Always ensure total wattage of electrical
load does not exceed rated wattage of generator.
NOTICE
Most electric appliances require more than their rated wattage for start-up.
The following appliance wattage table shows wattage of some common household
appliances. This should be used as a generic guide only. Different
manufacturers of certain products may require more wattage. See your
authorized YANMAR industrial engine dealer or distributor with any questions.
Decide what electrical load your generator can power. Do this before using the
generator. Use the following four step method. It will help to select a load
that is not too large. Make sure total wattage of all electrical loads does
not exceed the rated output capacity of your generator.
1. Make two lists of items you want powered by the generator. List all motors
and motor powered appliances in one. List all lights and small appliances in
the other. For standby service to home or building, only include items you
must power.
CAUTION
Do not start two or more appliances simultaneously and always start them one
at a time. Never use floodlights with other appliances.
2. Enter running watts of each item except electric motors. The light bulb or
appliance nameplate lists its wattage. Remember, 1 kW = 1000 watts. Note: The
nameplate may not list wattage. It may only list volts and amps.
· The formula for finding wattage is: volts amps = watts.
· For example, an appliance nameplate states 3 amps at 220 volts: 3 amps 220
volts = 660 watts.
3. Electric motors present a special problem when figuring load as they
require up to three times their rated wattage to start. · For example, an
electric motor nameplate states 5 amps at 220 volts. 5 amps 220 volts = 1100
watts: Running Watts
Multiply this by 3. This will show the starting watts needed.
1100 watts 3 = 3300 watts: Starting Watts
NOTICE
When figuring the generator load for motors, you must use the Starting Watts
and not the Running Watts.
Note: Some motors require nearly the same wattage to run as to start. These
items include saws, drills, hair dryers and food mixers.
4. Add running watts and starting watts of all items. This total must not
exceed the rated output capacity of your generator. It is a good idea to have
up to 25 % extra capacity for future needs or extra equipment.
32
YDG Operation Manual
34127
Typical electrical appliance wattages
Application/equipment Light bulb (100 W) AM/FM radio CB radio Fan Television
Microwave oven Air conditioner (12,000 BTU) Furnace fan (1/3 hp blower motor)
Vacuum cleaner Sump pump (1/3 hp) Refrigerator/freezer Deep freezer Circular
saw Circular saw 6 in. Floodlight Drill 1/2 in. electric Toaster Coffee maker
Skillet Chain saw 14 in. electric Water well pump (1/2 hp) Hot plate/range
(per burner) Table saw 10 in. Water heater (storage type) 12 VDC battery
charger
BEFORE YOU OPERATE
Running/rated watts 100
50 – 200 50 200
300 – 400 700 3250 600 600 700 800 500
1000 – 2500 800 1000 1000 1200 1200 1200 1200 1000 1500 2000 5000 120
Starting/surge watts 100
50 – 200 50 600
300 – 400 1000 5000 1800 750 2100 2400 1500
2300 – 4600 1000 1000 1250 1200 1200 1200 1500 3000 1500 6000 5000 120
YDG Operation Manual
33
BEFORE YOU OPERATE
INITIAL ENGINE START UP
NOTICE
On the initial engine start-up, allow the engine to run without a load for
approximately 15 minutes while you check for abnormal noises or vibration,
diesel fuel leaks, engine oil leaks, and for proper operation.
Avoid continuous operation at maximum load for the remainder of the first hour
of operation.
During the first 10 hours of operation, check the engine oil level frequently.
See Checking Engine Oil on page 29.
DAILY CHECKS
Before you operate, make sure the YANMAR YDG generator is in good operating
condition. Make sure you check the following items before you start your
generator and have any repairs completed before starting the generator.
CAUTION
It is important to perform daily checks as periodic maintenance prevents
unexpected downtime, reduces the number of accidents due to poor engine
performance and helps extend the life of the engine.
· Visual checks
· Check battery electrolyte level
· Check diesel fuel and engine oil levels
Visual Checks
CAUTION
If any problem is noted during the visual check, the necessary corrective
action should be taken before you operate the generator set.
1. Check for engine oil leaks. 2. Check for fuel leaks.
WARNING
Always wear eye protection when servicing the generator set. Never check for a
fuel leak with your hands. Always use a piece of wood or cardboard. Have your
authorized YANMAR dealer or distributor repair the damage.
3. Check for damaged or missing parts. 4. Check for loose, missing or damaged
fasteners. 5. Check the electrical harnesses for cracks,
abrasions and damaged or corroded connectors. 6. Check hoses for cracks,
abrasions and damaged, loose or corroded clamps.
Check Battery Electrolyte Level
Follow the procedures in Checking Battery Electrolyte Level on page 24 to
check the battery levels.
Check Diesel Fuel and Engine Oil Levels
Follow the procedures in Filling the Fuel Tank on page 28 and Checking Engine
Oil on page 29 to check these levels.
34
YDG Operation Manual
GENERATOR [ FI “Qr gtcvkqp”Ocpwcn OPERATION
INTRODUCTION
This section of the Operation Manual describes the procedures for starting the
generator, checking generator performance during operation and shutting the
generator down. Before performing any storage procedures within this section,
review the Safety section on page 1.
YDG Operation Manual
35
GENERATOR OPERATION
STARTING THE GENERATOR
CAUTION
During manual starting operation, a knockback from recoil could happen, with
risk of serious injuries, if proper starting procedure is not carried on. Be
assured to read and understand starting manual procedure.
. 5. Move the engine control lever (1, Figure 24) to the RUN position (2,
Figure 24).
1 2
RUN STOP
Recoil Start
Use the following procedure to start the engine using the recoil starter.
1. Make sure you follow the procedures stated in Daily Checks on page 34.
2. Fill fuel tank with clean, fresh fuel. See Filling the Fuel Tank on page
28.
3. Before starting, always turn OFF the main AC switch of the generator and
any other loads. Make sure nothing is plugged into or connected to the
generator. See Generator Check on page 30.
4. Turn the key clockwise from the OFF position (1, Figure 23) to the ON
position (2, Figure 23).
1
OFF
2
ON
K0001355A
Figure 24
6. Grasp the recoil starter handle (1, Figure 25). 7. Pull the handle out
slowly until you feel strong
resistance. 8. Slowly return the recoil starter handle to the
initial position. 9. Push the decompression lever (2, Figure 25)
down until it locks in place and then release it.
CAUTION
Always depress the decompression lever to allow the engine to start more
quickly and prevent damage to the recoil starter.
The decompression lever will automatically return to the original position
when the engine starts.
START
STARTER SW
Figure 23
K0002413C-00X
36
YDG Operation Manual
34127
2
1
K0002447A-00X
Figure 25 10. Grasp the recoil starter handle (1, Figure 25). 11. Pull the
handle all the way out with a strong and
even motion. Use two hands if necessary.
NOTICE
Always pull recoil starter handle all the way out or the engine will not
start. Pulling out the recoil starter handle too hard or fast will damage the
equipment. Never allow the recoil starter handle to snap back against the
engine. Return the handle to the starting position gently to prevent damage to
the recoil starter.
12. Slowly return the recoil starter handle to the initial position.
13. If the engine does not start, repeat this procedure from Step 5.
GENERATOR OPERATION
Electric Start
Use the following procedure to start the engine using the electric starter. 1.
Make sure you follow the procedures stated in
Daily Checks on page 34. 2. Fill fuel tank with clean, fresh fuel. See Filling
the Fuel Tank on page 28. 3. Before starting, always turn OFF the main AC
switch of the generator and any other loads. Make sure nothing is plugged into
or connected to the generator. See Generator Check on page 30. 4. Move the
engine speed control lever (1, Figure 26) to the RUN position (2, Figure 26).
1 2
RUN STOP
K0001355A
Figure 26 5. Insert the key into the key switch. 6. Turn the key clockwise to
the START position
(1, Figure 27). Release the key as soon as the engine starts. It will return
to the ON position (2, Figure 27).
NOTICE
Never hold the key in the START position for longer than 15 seconds or the
starter motor will overheat.
YDG Operation Manual
37
GENERATOR OPERATION
OFF
2
ON
1
START
STARTER SW
K0002413B-00X
Figure 27 7. If the engine fails to start:
· Wait until the engine comes to a complete stop before you attempt to start
it again.
NOTICE
Engaging the starter while the engine is still rotating will result in damage
to the starter motor and flywheel.
· Wait at least 30 seconds before you attempt to start the engine again.
NOTICE
Waiting 30 seconds will allow the battery voltage to recover to prevent damage
to the starter motor due to the low battery voltage.
CHECKING THE GENERATOR SET DURING OPERATION
1. Check for fuel or engine oil leaks. If any leaks are found, shut down the
engine and have the necessary repairs performed.
2. Check for abnormal sounds or vibration. If the abnormal sounds or
vibration cannot be resolved, shut down the engine and have the necessary
repairs performed. Contact your authorized YANMAR industrial engine dealer or
distributor.
3. Check for white or black smoke from the exhaust system. A small amount of
white exhaust smoke is normal on start-up of a cold engine. Black exhaust
smoke could mean the engine is overloaded or is being over-fueled. If either
of these conditions persists, contact your authorized YANMAR industrial engine
dealer or distributor.
4. Check the fuel level during operation. If the fuel level runs low, stop
the engine and refuel. See Filling the Fuel Tank on page 28.
5. If the oil pressure falls below the specified minimum, the low oil
pressure shutdown will automatically stop the engine. Check the oil level and
refill. See Checking Engine Oil on page 29.
6. If the engine suddenly stops, See Troubleshooting on page 62, then re-make
the starting procedure. If the failure remains, contact your authorized YANMAR
industrial engine dealer or distributor.
38
YDG Operation Manual
34127
Low Load Operation
Avoid low load operation as much as possible. Always operate at 1/4 load or
greater when possible.
NOTICE
Always run the engine at full speed. Never run engine at lower speeds. At full
speed, the engine runs at 3000 (3600) min-1 under load. The engine must
maintain 3000 (3600) min-1 for generator to create correct voltage. Running
engine at lower speeds will damage generator and powered items.
Operating at 1/4 load or less for extended periods will cause carbon to mix
with unburned fuel, clogging the head of the injection nozzle and piston head
and fouling the muffler. Carbon buildup can be recognized by bluish white
smoke being emitted from the engine. To avoid this, run the engine at 3/4 load
or greater for 30 minutes or longer every 50 hours operation.
GENERATOR OPERATION
SHUTTING DOWN THE GENERATOR
NOTICE
For maximum engine life, YANMAR recommends that when shutting the engine down,
you allow the engine to run, without load, for five minutes. This will allow
the engine components that operate at high temperatures, such as the exhaust
system, to cool slightly before the engine itself is shut down.
Follow these steps to shut down the engine:
1. Turn the generator main AC switch (1, Figure 28) OFF.
2. With the engine speed lever in the RUN position, operate the engine
without load for about five minutes.
3. Turn the generator key switch (2, Figure 28) to OFF.
YDG3700V-5EB, YDG5500V-5EB, YDG3700N-6EB, YDG5500N-6EB
1
2
0
240
~ 0 V 200
Figure 28
4. If the engine will not be used for six months or longer, follow the
additional instructions in Long-Term Storage on page 69.
YDG Operation Manual
39
GENERATOR OPERATION
AC APPLICATION
1. Start the engine. See Starting the Generator on page 36. Once the engine
is started, make sure the voltage meter (1, Figure 29) or (1, Figure 30)
indicates the voltage. If it does not, STOP the generator as the generator or
voltage meter may be damaged.
YDG3700V-5B, YDG5500V-5B, YDG3700N-6B, YDG5500N-6B
1
0
240
~ 0 V 200
2. Plug in the appliance.
CAUTION
Always ensure that all appliances are in good working order before connecting
them to the generator. If an appliance begins to operate abnormally, becomes
sluggish or stops suddenly, turn off the generator main AC switch immediately.
Then disconnect the appliance and examine it for malfunction.
Due to high mechanical stresses, only tough rubber-sheathed flexible cables
are permitted.
When using extension lines or mobile distribution networks the resistance
value shall not exceed 1,5 Ohm.
Figure 29 YDG3700V-5EB, YDG5500V-5EB YDG3700N-6EB, YDG5500N-6EB
1
3. Turn the main AC switch to the ON position.
NOTICE
If an overload trips the AC circuit protector, reduce the electrical load on
the circuit and wait a few minutes before resuming operation.
0
240
~ 0 V 200
Figure 30
40
YDG Operation Manual
34127
DC APPLICATION
NOTICE
DC terminals should be used for charging 12 VDC batteries only. Using the DC
terminals for any other type of 12 VDC appliance may cause damage to generator
and appliance.
The DC terminal (1, Figure 31) may be used for charging 12 volt automotive-
type batteries only. (Other loads may not be used.)
NOTICE
Never use the 12 VDC terminals at the same time as the AC terminals.
1. Always disconnect the negative () battery cable (if connected) from the
battery to be charged before charging.
WARNING
Never allow the free ends of the cables to touch each other. If this occurs
the battery will short circuit.
2. Start the generator set. 3. Connect the charging cable to the battery
terminals and to the DC output terminals of the generator.
NOTICE
Always connect the positive battery terminal to the positive DC terminal on
the generator. Never reverse the charging cables or serious damage to the
generator and or battery may occur. Do not attempt to start an automobile
engine while the generator is still connected to the battery as the generator
may be damaged.
GENERATOR OPERATION
YDG3700V-5EB, YDG5500V-5EB YDG3700N-6EB, YDG5500N-6EB
0
240
~ 0 V 200
1 1 12 VDC output terminal
(for 12 VDC battery charging only)
Figure 31
YDG Operation Manual
41
GENERATOR OPERATION This Page Intentionally Left Blank
42
YDG Operation Manual
PERIODIC YDG Operation Manual MAINTENANCE
INTRODUCTION
This section of the Operation Manual describes the procedures for proper care
and maintenance of the generator set. Before performing any storage procedures
within this section, review the Safety section on page 1.
YDG Operation Manual
43
PERIODIC MAINTENANCE
PRECAUTIONS
The Importance of Periodic Maintenance
Engine deterioration and wear occurs in proportion to length of time the
generator has been in service and the conditions the generator is subject to
during operation. Periodic maintenance prevents unexpected downtime, reduces
the number of accidents due to poor machine performance and helps extend the
life of the engine.
CAUTION
Establish a periodic maintenance plan according to the engine application and
make sure you perform the required periodic maintenance at intervals
indicated. Failure to follow these guidelines will impair the engine’s safety
and performance characteristics, shorten the engine’s life and may affect the
warranty coverage on your engine. See YANMAR Limited Warranty on page i.
Consult your authorized YANMAR industrial engine dealer or distributor for
assistance when checking items marked with a .
Performing Periodic Maintenance
Perform periodic maintenance procedures in an open, level area free from
traffic. If possible, perform the procedures indoors to prevent environmental
conditions, such as rain, wind, or snow, from damaging the machine.
The Importance of Daily Checks
Periodic maintenance schedules assume that the daily checks are performed on a
regular basis. Make it a habit of performing daily checks before the start of
each shift. See Daily Checks on page 34.
CAUTION
It is important to perform daily checks. Periodic maintenance prevents
unexpected downtime, reduces the number of accidents due to poor engine
performance and helps extend the life of the engine.
Keep a Log of Generator Hours and Daily Checks
Keep a log of the number of hours the generator is run each day and a log of
the daily checks performed. Also note the date, type of repair, and parts
needed for any service needed between the periodic maintenance intervals.
Periodic maintenance intervals are every 50, 200, 400, 1000, 1500 and 2000
hours of generator operation. Failure to perform periodic maintenance will
shorten the life of the generator.
YANMAR Replacement Parts
Yanmar recommends that you use genuine YANMAR parts when replacement parts are
needed. Genuine replacement parts help ensure long generator life. Replace
circuit breakers only with components that have the same ratings and
performance.
Tools Required
Before you start any periodic maintenance procedure make sure you have the
tools you need to perform all of the required tasks.
Ask Your Authorized YANMAR Industrial Engine Dealer or Distributor for Help
YANMAR professional service technicians have the expertise and skills to help
you with any maintenance or service related procedures.
44
YDG Operation Manual
34127
CAUTION
Before starting any maintenance procedure, ensure that the engine is cold and
the speed control lever is set on STOP position.
Before starting any maintenance procedure, disconnect negative battery cable.
Attach a “Do Not Operate” tag near the key switch while performing maintenance
procedure on the equipment.
PERIODIC MAINTENANCE
Tightening Fasteners
Use the correct amount of torque when you tighten fasteners on the machine.
Applying excessive torque may damage the fastener or component and not enough
torque may cause a leak or component failure.
YDG Operation Manual
45
PERIODIC MAINTENANCE
TIGHTENING TORQUES FOR STANDARD BOLTS AND NUTS
Use the correct amount of torque when you tighten fasteners on the machine.
Applying excessive torque may damage the fastener or component and not enough
torque may cause a leak or component failure.
NOTICE
The tightening torque in the following chart should be applied only to the
bolts with a “7” head. (JIS strength classification: 7T) Apply 60 % torque to
bolts that are not listed. Apply 80 % torque when tightened to aluminum alloy.
Item Hexagon bolt (7T) and nut
PT plug
Pipe joint bolt
Nominal thread diameter pitch
M6 1.0 mm M8 1.25 mm M10 1.5 mm M12 1.75 mm M14 1.5 mm M16 1.5 mm
1/8 1/4 3/8 1/2 M8 M10 M12 M14 M16
Tightening torque
Remarks
7 – 9 lb-ft (87 – 104 lb-in., 9.8 -11.8 N·m, 1.0 – 1.2 kgf·m)
17 – 21 lb-ft (200 – 251 lb-in., 22.6 – 28.4 N·m, 2.3 – 2.9 kgf·m)
33 – 40 lb-ft (44.1 – 53.9 N·m, 4.5 – 5.5 kgf·m)
58 – 72 lb-ft (78.4 – 98.0 N·m, 8.0 – 10 kgf·m)
94 – 108 lb-ft (127.5 – 147.1 N·m, 13 – 15 kgf·m)
159 – 174 lb-ft (215.7 – 235.4 N·m, 22 – 24 kgf·m)
7 lb-ft (87 lb-in., 9.8 N·m, 1.0 kgf·m)
14 lb-ft (173 lb-in., 19.6 N·m, 2.0 kgf·m)
22 lb-ft (29.4 N·m, 3.0 kgf·m)
43 lb-ft (58.8 N·m, 6.0 kgf·m)
9 – 12 lb-ft (112 – 148 lb-in., 12.7 – 16.7 N·m, 1.3 – 1.7 kgf·m)
14 – 19 lb-ft (173 – 225 lb-in., 19.6 – 25.4 N·m, 2.0 – 2.5 kgf·m)
18 – 25 lb-ft (24.5 – 34.3 N·m, 2.5 – 3.5 kgf·m)
29 – 36 lb-ft (39.2 – 49.0 N·m, 4.0 – 5.0 kgf·m)
36 – 43 lb-ft (49.0 – 58.8 N·m, 5.0 – 6.0 kgf·m)
Use 80 % of the value at left when the tightening part is aluminum. Use 60 %
of the value at left for 4T bolts and locknuts.
Note: Torque values shown in this manual are for clean, non-lubricated fasteners unless otherwise specified.
46
YDG Operation Manual
34127
PERIODIC MAINTENANCE SCHEDULE
PERIODIC MAINTENANCE
Daily and periodic maintenance is important to keep the engine in good operating condition. The following is a summary of maintenance items by periodic maintenance intervals. Periodic maintenance intervals vary depending on engine application, loads, diesel fuel and engine oil used and are hard to establish definitively. The following should be treated only as a general guideline.
: Check
System Air intake Cylinder head
Electrical equipment
Emission control warranty
Engine oil
Engine speed control
: Replace : Contact your authorized YANMAR industrial engine dealer or distributor for these maintenance services
Periodic maintenance interval
Check item
Daily
Every 50 hours
Every 200
hours
Every 400
hours
Every 1000 hours
Every 1500 hours
Every 2000 hours
Clean or replace air
cleaner element – (may
need more frequent
service in dusty
conditions)
Adjust intake/exhaust valve clearance
Check compression
Check battery (if equipped) and add water as necessary
Before operation
Check battery indicator (if equipped) and other driven machine indicators (if equipped)
When engine is started
Wiring harness
Voltmeter
Inspect, clean and test
fuel injection nozzle, if
necessary
Check engine oil level and
add engine oil as
Before
necessary
operation
Drain and refill engine oil
Clean engine oil filter replace if damaged
1st time
2nd and
after
2nd and
after
Check for engine oil leakage
Before and after operation
Check for proper operation Verify adjustment
1st time
2nd and
after
YDG Operation Manual
47
PERIODIC MAINTENANCE
: Check
: Replace
: Contact your authorized YANMAR industrial engine dealer or distributor for these maintenance services Periodic maintenance interval
System
Check item
Daily
Every 50 hours
Exhaust system
Check spark arrester for clogging (if equipped)
Before operation
Check fuel tank level and add fuel as necessary
Before operation
Drain and clean fuel tank
Fuel
Clean inlet fuel screen
Replace outlet fuel filter
Check for fuel leakage
Before and after operation
Every 200
hours
Hoses
Replace fuel system hose(s)
Every 400
hours
Every 1000 hours
Every 1500 hours
Every 2000 hours
or every 2
years whicheve r comes
first
Check brushes for wear or damage
Generator Frame
Check slip rings for wear or damage
Check coils and Automatic Voltage Regulator (AVR) for correct operation
Check main and sub frames for damage
Check engine/frame dampers for wear, damage and tightness
Check all fasteners for damage and tightness
Note: These procedures are considered normal maintenance and are performed at the owners expense.
48
YDG Operation Manual
34127
PERIODIC MAINTENANCE PROCEDURES
Daily, Before Operation
PERIODIC MAINTENANCE
Check engine speed control
Before you operate the driven machine check the engine speed control. See
Check and adjust engine speed control on page 55.
Before performing periodic maintenance procedures, read the complete procedure
including safety information.
Perform the following maintenance daily before operation.
· Check battery
· Check battery indicator
· Check engine oil level
· Check for engine oil leakage
· Check engine speed control (first time only)
· Check spark arrester
· Check fuel level
· Check for fuel leakage
Check battery
Check the battery electrolyte level. See Checking Battery Electrolyte Level on
page 24.
Check battery indicator
Visually check the battery indicator (if equipped) and any other indicator
provided by the driven machine manufacturer.
Check engine oil level
Before you operate the engine check the engine oil level. See Checking Engine
Oil on page 29.
Check for engine oil leakage
Before you operate the engine check for any engine oil leaks. If you discover
any engine oil leaks, contact your authorized YANMAR industrial engine dealer
or distributor for service.
YDG Operation Manual
49
PERIODIC MAINTENANCE
Check fuel level
Before you operate the engine, check the fuel level. See Filling the Fuel Tank
on page 28.
- Check for fuel leakage
Before you operate the engine, check for any fuel leaks.
DANGER
Avoid personal injury. Always wear eye protection when checking for fuel leaks and never check for a fuel leak with your hands. Always use a piece of wood or cardboard. Have your authorized YANMAR dealer or distributor repair the damage.
Daily, After Operation
· Check for engine oil leakage · Check for fuel leakage
Check for engine oil leakage
After you shut down the engine check for any engine oil leaks.
WARNING
Avoid being burned by contact with hot engine oil.
Check for fuel leakage
After you shut down the engine check for any fuel leaks.
DANGER
Avoid personal injury. Always wear eye protection when checking for fuel leaks
and never check for a fuel leak with your hands. Always use a piece of wood or
cardboard. Have your authorized YANMAR dealer or distributor repair the
damage.
50
YDG Operation Manual
34127
After Initial 50 Hours of Operation
Perform the following maintenance after the initial 50 hours of operation.
· Replace engine oil
· Clean/inspect engine oil filter
Replace engine oil
The engine oil on a new engine becomes contaminated from the initial break-in
of internal parts. The initial 50 hour oil change and filter cleaning is very
important.
Drain the engine oil as follows:
1. Make sure the engine is level. 2. Start the engine and bring it up to
operating
temperature. 3. Stop the engine. 4. Position a container under the engine to
collect
waste oil. 5. Remove one of the drain plugs located on the
bottom of the cylinder block (2, Figure 32). Allow oil to drain.
WARNING
The engine oil will be hot after engine operation, stay clear of the hot
engine oil to avoid being burned. Always wear eye protection.
PERIODIC MAINTENANCE
1
2
3
4
Figure 32
6. Remove the oil cap/dipstick (1, Figure 32) to allow the engine oil to
drain more easily.
NOTICE
Prevent dirt and debris from contaminating the engine oil. Carefully clean the
oil cap/dipstick and the surrounding area before you remove the cap.
7. After all oil has been drained from the engine, reinstall the drain plug
(2, Figure 32) and tighten to 173 – 208 lb-in. (19.6 – 23.5 N·m, 2.0 – 2.4
kgf·m).
YDG Operation Manual
51
PERIODIC MAINTENANCE
. 8. Dispose of used oil properly.
NOTICE
Always be environmentally responsible. Follow the guidelines of the
governmental agencies for the proper disposal of hazardous materials such as
engine oil, diesel fuel and engine coolant. Consult the local authorities or
reclamation facility. Never dispose of hazardous materials by dumping them
into a sewer, on the ground or into ground water or waterways.
NOTICE
Never overfill. Overfilling may result in white exhaust smoke, engine
overspeed or internal damage.
1
9. Inspect engine oil filter. See Clean/inspect engine oil filter on page 53.
10. Add engine oil until the level is between the upper (2, Figure 33) and
lower (3, Figure 33) lines on the oil cap/dipstick (1, Figure 33). See Adding
Engine Oil on page 30.
2
3
4
Figure 33
11. Warm up the engine by running it for five minutes and check for any
engine oil leaks.
12. After engine is warm, shut it off and let it sit for 10 minutes.
13. Recheck the engine oil level by reinserting the oil cap/dipstick into the
crankcase and turn clockwise for one-half revolution to engage the first
thread in the crankcase opening. See Checking Engine Oil on page 29.
14. Add oil if necessary.
NOTICE
Always keep the oil level between the upper and lower lines on the oil
cap/dipstick.
15. Replace the oil cap/dipstick and tighten by hand. Over-tightening may damage the cap. If any engine oil is spilled, wipe it away with a clean cloth.
52
YDG Operation Manual
34127
Clean/inspect engine oil filter
3 21
4
K0001123B-00X
Figure 34
It is recommended that this procedure be performed at the same time as the
Replace engine oil procedure on page 51.
1. Remove the oil filter retaining bolt (1, Figure 34).
2. Drain engine oil. See Replace engine oil on page 51.
3. Pull the oil filter cap (2, Figure 34) out and remove the oil filter (3,
Figure 34).
4. Clean the oil filter in suitable parts cleaner or replace if damaged.
5. Lubricate the O-ring (4, Figure 34) with oil and reinstall the oil filter
(3, Figure 34).
Applicable engine oil filter Part No.
L70V and L100V
114250-35070
6. Make sure the oil filter cap (2, Figure 34) is fully seated.
7. Reinstall and tighten the oil filter retaining bolt (1, Figure 34).
8. Add new engine oil to the engine as specified in Adding Engine Oil on page
30.
PERIODIC MAINTENANCE
NOTICE
Never overfill. Overfilling may result in white exhaust smoke, engine
overspeed, or internal damage.
9. Warm up the engine by running it for five minutes and check for any engine
oil leaks.
10. After engine is warm, shut it off and let it sit for 10 minutes.
11. Recheck the engine oil level by reinserting the oil cap/dipstick into the
crankcase and turn clockwise for one-half revolution to engage the first
thread in the crankcase opening. See Checking Engine Oil on page 29.
12. Add oil if necessary.
NOTICE
Always keep the oil level between the upper and lower lines on the oil
cap/dipstick.
13. Replace the oil cap/dipstick (1, Figure 33) and tighten by hand. Over-
tightening may damage the cap. If any engine oil is spilled, wipe it away with
a clean cloth.
YDG Operation Manual
53
PERIODIC MAINTENANCE
Every 50 Hours of Operation
Perform the following maintenance every 50 hours of operation. · Clean inlet
fuel screen · Test GFCI outlet
Clean inlet fuel screen
1. Clean the area around the fuel cap (1, Figure 35).
2. Remove the fuel cap from the fuel tank. 1 2 3
K0002456A-00X
Figure 35 3. Lift out the inlet fuel screen (3, Figure 35).
CAUTION
Wipe up all spills immediately.
Every 200 Hours of Operation
Perform the following maintenance every 200 hours of operation.
· Clean air cleaner element
· Replace engine oil and clean/inspect engine oil filter
· Check engine speed control
· Drain the fuel tank and replace outlet fuel filter
Clean air cleaner element
Engine performance is adversely affected when the air cleaner element is
clogged with dust. Be sure to clean or replace the air cleaner element
periodically.
Avoid operating in extremely dusty conditions. When the engine is operated in
dusty conditions, clean the air cleaner element more frequently. Never operate
the engine with the air cleaner element(s) removed. This may cause foreign
material to enter the engine and damage it.
Clean or replace the air cleaner element if the air intake restriction exceeds
the following specifications:
(L100V: 0.21 psi (1.47 kPa; 150 mmAq) or less), (L70V: 0.20 psi (1.37 kPa; 140
mmAq) or less).
4. Clean the inlet fuel screen using suitable parts cleaner or replace it if
damaged.
5. Inspect fuel cap gasket (2, Figure 35) and replace if damaged.
6. Reinstall the inlet fuel screen.
7. Reinstall the fuel cap and hand-tighten. Over-tightening the fuel cap will
damage it.
54
YDG Operation Manual
34127
L70V and 100V models
The L70V and 100V model engines use a “dry” type air filter element. The air
filter element is an open paper type element. This type of air filter element
should be cleaned or replaced every 200 hours or earlier if found excessively
dirty.
PERIODIC MAINTENANCE
123
4
5
CAUTION
Avoid personal injury. Always wear eye protection when servicing the engine or
when using compressed air or high pressure water. Dust, flying debris,
compressed air, pressurized water or steam may injure your eyes.
1. Remove the wing nut (1, Figure 36).
2. Remove the air cleaner cover (2, Figure 36).
3. Remove the wing nut (3, Figure 36).
4. Remove the air cleaner element (4, Figure 36) and outer foam element (5,
Figure 36).
5. Blow air through both elements using 42 – 71 psi (0.29 – 0.49 MPa, 3.0 –
5.0 kgf/cm2) compressed air to remove any debris. Blow air from the inside to
the outside of the filter element using the lowest possible air pressure to
remove dust without damaging the elements.
6. Check the condition of the air filter element by shining a flashlight from
the back of the air filter element. If light is not visible on the outside of
the air filter element, replace the air filter element.
Air cleaner element Part No.
L70V and L100V
114210-12590
7. If either element is damaged replace both of them. (They are not sold
individually.)
8. Clean the inside of the air cleaner cover (2, Figure 36).
K0001549A-00X
Figure 36
9. Reinstall the air cleaner element (4, Figure 36) into the air cleaner
housing.
10. Slide the outer foam element (5, Figure 36) over the air cleaner element
(4, Figure 36).
11. Reinstall the wing nut (3, Figure 36) and hand-tighten. Over-tightening
the wing nut will damage the air cleaner assembly.
12. Reinstall the air cleaner cover (2, Figure 36).
13. Reinstall the wing nut (1, Figure 36) and hand-tighten. Over-tightening
the wing nut will damage the air cleaner assembly.
Replace engine oil and clean/inspect engine oil filter
Change the engine oil every 200 hours of operation after the initial change at
50 hours. Clean and inspect the engine oil filter at the same time. See
Replace engine oil on page 51 and Clean/inspect engine oil filter on page 53.
Check and adjust engine speed control
After you operate the engine for 200 hours, check the engine speed control.
Never attempt to adjust the low or high idle speed limit screw. This may
impair the safety and performance of the machine and shorten its life. If
adjustment is ever required, contact your authorized YANMAR industrial engine
dealer or distributor.
YDG Operation Manual
55
PERIODIC MAINTENANCE
A constant speed control device is used on YDG generator sets, to govern the
engine speed to a pre-set constant engine speed under various loads. When
moved to the full throttle position, the speed control lever “locks” at full
throttle.
Never force the throttle lever to move. This may deform the governor lever and
cause irregular operation of the engine speed control.
Always run the engine at full speed. Never run engine at lower speeds. At full
speed, the engine runs at 3000 (3600) min-1 under load. The engine must
maintain 3000 (3600) min-1 for generator to create correct voltage. Running
engine at lower speeds will damage generator and powered items.
1. Check that the speed control lever (1, Figure 37) operates smoothly and
locks into the full speed RUN position (2, Figure 37) when advanced and
returns to the stop position when the stop lever (3, Figure 37) is actuated.
If the speed control lever does not operate as indicated or adjustment is
needed, see your authorized YANMAR industrial engine dealer or distributor for
service.
1 2
RUN
STOP
3
K0001355C-00X
1 Speed control lever 2 RUN position 3 Stop lever
Figure 37
Drain the fuel tank and replace outlet fuel filter
1. Position an approved container under the fuel tank to collect the fuel.
DANGER
Always wipe up all spills immediately. Diesel fuel is flammable and explosive
under certain conditions. Store any containers containing fuel in a well-
ventilated area, away from any combustibles or sources of ignition. Wipe up
all spills immediately and never use a shop rag to catch spilled fuel.
2. Remove the fuel cap (1, Figure 38). 3. Remove the fuel tank drain plug (8,
Figure 38)
and gasket (9, Figure 38) to drain the fuel. Inspect the gasket and replace if
damaged.
NOTICE
Always be environmentally responsible. Follow the guidelines of the
governmental agencies for the proper disposal of hazardous materials such as
engine oil, diesel fuel and engine coolant. Consult the local authorities or
reclamation facility.
4. Remove clamps (2, Figure 38) and disconnect fuel supply (3, Figure 38) and
return lines (4, Figure 38).
5. Remove the fuel tank mounting bolts and remove the fuel tank from the
generator frame.
6. Remove the three fuel filter nuts (5, Figure 38) and pull the fuel filter
(6, Figure 38) out through bottom of the tank.
56
YDG Operation Manual
34127
1
9 8
7
2
4 6
2
5
3
K0002457B-00X
Figure 38
7. Install a new filter into the tank using a new O-ring (7, Figure 38).
8. Reinstall the three fuel filter nuts and tighten securely.
9. Reinstall the drain plug and gasket.
10. Reinstall the fuel tank into the generator frame and secure with mounting
bolts.
11. Reconnect the fuel supply and return lines to the tank with clamps.
12. Fill the fuel tank with fuel and inspect for leaks. Repair or replace
components as necessary.
PERIODIC MAINTENANCE
Every 400 Hours of Operation
Perform the following maintenance every 400 hours of operation.
· Adjust intake and exhaust valve clearance
· Check brushes for wear or damage
· Check slip rings for wear or damage
· Check coils and Automatic Voltage Regulator (AVR) for correct operation
· Check main and sub-frames for damage
· Check all fasteners for damage and tightness
Adjust intake and exhaust valve clearance
Proper adjustment is necessary to maintain the correct timing for opening and
closing the valves. Improper adjustment will cause the engine to run noisily,
resulting in poor engine performance and engine damage. See your authorized
YANMAR industrial engine dealer or distributor for this service.
Check brushes for wear or damage
Check the generator brushes for wear and damage. Generator brushes wear with
normal use of the generator over time. It is important to check the condition
of the brushes to ensure generator performance is maintained at an optimum.
See your authorized YANMAR industrial engine dealer or distributor for this
service.
Check slip rings for wear or damage
Check the generator slip rings for wear and damage. Generator slip rings wear
with normal use of the generator over time. It is important to check the
condition of the slip rings to ensure generator performance is maintained at
an optimum. See your authorized YANMAR industrial engine dealer or distributor
for this service.
YDG Operation Manual
57
PERIODIC MAINTENANCE
Check coils and Automatic Voltage Regulator (AVR) for correct operation
Check the generator coils and AVR for correct operation and output. It is
important to check the condition of the generator coils and AVR to ensure
generator performance is maintained at an optimum. See your authorized YANMAR
industrial engine dealer or distributor for this service.
Check main and sub-frames for damage
Check the main frame and sub-frames for damage. The main and sub-frames are
the structural support for the engine, generator, fuel tank and all other
generator controls and components. Any damage to the frames, including
corrosion may compromise the structural integrity of the frame and should be
repaired or replaced to avoid costly repairs and/or personal injury. See your
authorized YANMAR industrial engine dealer or distributor for service and
replacement parts.
Check all fasteners for damage and tightness
Check all fasteners used on the generator set. All fasteners should be
properly installed and tightened to the specified value given in the YDG
Service Manual. See your authorized YANMAR industrial engine dealer or
distributor for service and replacement parts.
Every 1000 Hours of Operation
Perform the following maintenance every 1000 hours of operation.
· Check compression
· Check engine/frame dampers for wear, damage and tightness
Check compression
An engine compression check is required every 1000 hours to obtain optimum
engine performance. See your authorized YANMAR industrial engine dealer or
distributor for this service.
Check engine/frame dampers for wear, damage and tightness
Inspect all frame components for damage and repair or replace as required.
The damper mount butyl rubber has excellent shock absorption performance.
Prevent contamination of the damper with diesel oil or gasoline as much as
possible during operation, to prevent deterioration of the rubber damper. See
your authorized YANMAR industrial engine dealer or distributor for service and
replacement parts.
1. Check for separation at rubber baked portion (1, Figure 39).
2. Check the damper rubber material (2, Figure 39) for cracks and
deformation. Replace the damper if cracked or deformed.
1 2
K0002858-00X
Figure 39
58
YDG Operation Manual
34127
Every 1500 Hours of Operation
Perform the following maintenance every 1500 hours of operation.
· Inspect, clean and test fuel injection nozzle
Inspect, clean and test fuel injection nozzle, if necessary
Proper operation of the fuel injectors is required to obtain the optimum
injection pattern for full engine performance. See your authorized YANMAR
industrial engine dealer or distributor for this service.
PERIODIC MAINTENANCE
Every 2000 Hours of Operation
Perform the following maintenance every 2000 hours of operation.
· Check and replace fuel hoses
Check and replace fuel hoses
Regularly check the fuel system hoses. If they are cracked or degraded,
replace them. Replace rubberized fuel hoses every two years or every 2000
hours of engine operation, whichever comes first, even if the engine has been
out of service. Rubberized fuel lines tend to dry out and become brittle after
two years or 2000 hours of engine operation, whichever comes first.
YDG Operation Manual
59
PERIODIC MAINTENANCE
PERIODIC MAINTENANCE PROCEDURES
Dismantling
The user is in charge of all the operations that must be done when the
generator’s life is over and must follows laws and local regulation.
Dismantling operations must be done by qualified technicians.
60
YDG Operation Manual
[ F I “Qr gtcvkqp”Ocpwcn
TROUBLESHOOTING
TROUBLESHOOTING INFORMATION
If your generator does not operate properly, refer to the Troubleshooting
Chart on page 62 or see your authorized YANMAR industrial engine dealer or
distributor. You can refer to Troubleshooting Chart on page 62 even if your
generator suddenly stops.
Provide the authorized YANMAR industrial engine dealer or distributor with the
following information:
1. Model name and serial number of your generator.
The YDG generator set model and serial number information label is located
inside the top front frame rail. See Generator Set Decal on page 15.
2. Model name and serial number of your engine.
The engine nameplate is located on the cooling shroud on the PTO side of
engine above the starter. See Engine Nameplate (Typical) on page 16.
3. How long the generator has been in service (the number of generator hours
or the number of calendar months).
4. Operating conditions when problem occurs: · Load on engine · Color of
exhaust smoke · Type of diesel fuel · Type of engine oil · Any abnormal noises
or vibration · Operating environment such as high altitude or extreme ambient
temperatures
5. Maintenance history and previous problems. 6. Other factors that
contribute to the problem.
YDG Operation Manual
61
TROUBLESHOOTING
TROUBLESHOOTING CHART
If a problem occurs, stop the engine immediately. Refer to the symptom column
in the chart below to identify the problem.
Symptom Engine does not start
Starter motor operates but engine does not start
Engine starts with recoil starter but then stops Starter motor does not
operate or rotates too slowly (engine can be turned manually) Engine cannot be
turned manually White or black exhaust smoke
Black exhaust smoke
White exhaust smoke
Probable cause
No diesel fuel Engine control lever not in the RUN position Engine oil level
low
Improper diesel fuel
Clogged engine oil filter
Clogged fuel filter
Poor fuel injection Compressed air leakage from intake/exhaust valves Faulty
engine stop solenoid Key switch not in the ON position Battery needs charging
Faulty cable connection at battery terminals Faulty starter switch Faulty
starter motor Inner parts seized or damaged
Engine overloaded Clogged air cleaner element
Improper diesel fuel
Faulty spraying of fuel injection Excessive intake/exhaust valve clearance
Improper diesel fuel
Faulty spray pattern of fuel injection Fuel injection timing delay Engine
burning oil
Action
Refuel fuel system Move engine control lever to the RUN position Check and
fill oil to proper level Replace with recommended diesel fuel Replace engine
oil filter
Replace fuel filter
See authorized YANMAR industrial engine dealer or distributor
Turn key to the ON position Check electrolyte, recharge
Clean terminals, retighten
See authorized YANMAR industrial engine dealer or distributor
Reduce load Clean element or replace
Replace with recommended diesel fuel See authorized YANMAR industrial engine
dealer or distributor Replace with recommended diesel fuel
See authorized YANMAR industrial engine dealer or distributor
Refer to
Filling the Fuel Tank on page 28
Diesel Fuel Specifications on page
26 Drain the fuel tank and replace outlet fuel filter on page 56
Disconnecting and Connecting Battery Cables on page 25
Clean air cleaner element on page 54 Diesel Fuel Specifications on page 26
Diesel Fuel Specifications on page 26
62
YDG Operation Manual
34127
Symptom Generator
No electricity generated
Lack of no-load voltage Too low or too high no-load voltage Too low load
voltage Too high load voltage Unstable voltage Overheating Noisy alternator
TROUBLESHOOTING
Probable cause
Action
Refer to
Main switch is off
Turn main switch on
Equipment incorrectly connected to generator Defective AVR Winding short
circulated or loose connections Electrical load too high Loss of residual
magnetism Engine speed too low Defective rotor diode Defective stator
Defective rotor Engine not running properly
Demagnetized machine AVR fuse interrupted Faulty AVR Winding failure
Insulation failure
Wrong or incorrectly carried out connections Faulty AVR
Winding failure Faulty slip-ring
Faulty AVR
Possible overload
Faulty AVR
Faulty AVR
Protections activated
Possible overload
Alternator inlet or outlet openings are clogged
Bearing broken
Connect the equipment correctly
See authorized YANMAR industrial engine dealer or distributor Reduce
electrical load See authorized YANMAR industrial engine dealer or distributor
See authorized YANMAR industrial engine dealer or distributor
See authorized YANMAR industrial engine dealer or distributor
See authorized YANMAR industrial engine dealer or distributor Check load
current value See authorized YANMAR industrial engine dealer or distributor
See authorized YANMAR industrial engine dealer or distributor Turn off and
restart the equipment Check load current value See authorized YANMAR
industrial engine dealer or distributor See authorized YANMAR industrial
engine dealer or distributor
Generator Check on page 30
YDG Operation Manual
63
TROUBLESHOOTING
ELECTRICAL WIRING DIAGRAM
YDG3700V-5B, YDG5500V-5B, YDG3700N-6B, YDG5500N-6B
STOP SOLENOID
BU
RE
BU
RE
RELAY
RE
DC
BL
TERMINALS
–
DC BREAKER
BL
OIL
PRESSURE
BL SWITCH
–
GE + AC
COIL
GE
BL RE
ALTERNATOR AVR
FREQ. JUMPER
VOLTAGE TRIMMER
AC COIL AC COIL
BL BR BU
RE
AUX COIL
4P
ROTOR COIL
BL
VOLTMETER
AC BREAKER
V
BR
BR BU BU
BL
Black
RE
Red
BU
Blue
BR
Brown
GE
Grey
YE/GR Yellow/Green
Figure 40
BR
BU
YE/GR
AC 230 V
AC 230 V
SCHUKO SOCKET
CEE SOCKET
YE/GR EARTH
TERMINAL
YE/GR
64
YDG Operation Manual
65
YDG Operation Manual
Figure 41
STOP SOLENOID
BU
RE
BU RE
BL
BL
RELAY
RE
DC
BL
TERMINAL
–
DC BREAKER
BL OIL
PRESSURE
SWITCH BL
BL RE
KEY SWITCH OPERATION DIAGRAM
E B IG BAT ST
OFF
OFF
I I
II II
–
BAT
BAT
KEY
IG ST
SWITCH
B
IG
ST B
E
E
GR RE
YE
ALTERNATOR AVR
GE
AC
COIL
GE
FREQ. JUMPER
VOLTAGE TRIMMER
AC COIL AC COIL
BL BR BU
RE
AUX COIL
4P BL
ROTOR COIL
VOLTMETER
AC BREAKER
V
BR
GR/WH
STARTER
RECTIFIER
BL/RE
GR/WH BL
–
BATTERY
GR/WH
CHARGE COIL
GR/WH
BL
Black
RE
Red
YE
Yellow
GR
Green
BU
Blue
BR
Brown
GE
Grey
YE/GR Yellow/Green
BL/RE Black/Red
GR/WH Green/White
BR
BU
BU
BR
BU
AC 230 V SCHUKO SOCKET
YE/GR
AC 230 V CEE
SOCKET
GR/WH
YE/GR
EARTH TERMINAL
YE/GR
TROUBLESHOOTING
34127
YDG3700V-5EB, YDG5500V-5EB, , YDG3700N-6EB, YDG5500N-6EB
TROUBLESHOOTING
ELECTRICAL EQUIPMENTS’ CONNECTIONS
(under “Electrical Separation” condition)
THE GENSET MUST BE PLACED ON A NON CONDUCTIVE SURFACE (SEE ASIDE FIGURE)
INSULATING MATERIAL (I.E. WOOD, RUBBER, ETC.)
L1 PE N
L1 PE N
– x2 CLASS II EQUIPMENT; – NO GROUNDING;
L1 PE N
L1 PE N
L1 PE N
L1 PE N
L1 PE N
L1 PE N
– x1 CLASS I EQUIPMENT; – NO GROUNDING;
– x1 CLASS I EQUIPMENT; – x1 CLASS II EQUIPMENT; – NO GROUNDING;
NOT PERMISSIBLE – x2 CLASS I EQUIPMENT;
66
YDG Operation Manual
TROUBLESHOOTING
34127
(/(&75,&$/(48,30(176¶&211(&7,216 71VVWHPZLWK5&’
L1 PE N
L1 PE N
/ 1
:,5,1’,$5$0 )255&’127,1& /8′(‘,16&23(2) 6833/<
/HJHQG
&/$66,,(48,30(17 &/$66,(48,30(17 ($57+187 ($57+52’
YDG Operation Manual
67
TROUBLESHOOTING This Page Intentionally Left Blank
68
YDG Operation Manual
LONG-TERM [ FI “Qr gtcvkqp”Ocpwcn STORAGE
INTRODUCTION
This section of the Operation Manual describes the procedures necessary to
place the generator into long-term storage (three months or longer) and how to
prepare it for operation.
YDG Operation Manual
69
LONG-TERM STORAGE
BEFORE YOU PLACE THE GENERATOR IN LONG-TERM STORAGE
1. Perform the next periodic maintenance procedure. For example, if there are
10 hours remaining before the 200 hour maintenance, you should do the
maintenance before you place the engine in storage. See Periodic Maintenance
Schedule on page 47.
2. Start the engine. Allow the engine to run without load for approximately
five minutes and then stop the engine.
3. Drain the engine oil while the engine is still warm and fill with new oil.
See Replace engine oil on page 51.
4. Push the decompression lever down and hold it while slowly pulling the
recoil starter two or three times. Do not start the engine.
5. Pull the decompression lever up. Pull the recoil starter slowly and stop
when there is resistance. This procedure closes the intake and exhaust valves
in the compression position and helps prevent rust.
6. Allow the engine to completely cool then drain the fuel tank or fill it
completely.
7. Protect the air cleaner, muffler and electrical components (dynamo,
starter motor, switches) from water and dust.
8. Disconnect the negative (-) battery cable to prevent the battery from
discharging.
9. Check the battery fluid and add distilled water as required. See Check
Battery Electrolyte Level on page 34.
10. Charge the battery once a month during storage. See Charging the Battery
on page 25.
11. Clean the generator and store it in a dry place.
NOTICE
Always protect the air cleaner and electric components from damage when you
use steam or high pressure water to clean the generator.
RETURNING THE ENGINE TO SERVICE
1. Perform the Daily Checks on page 34. 2. Start the engine. Allow the engine
to run
without load for approximately 5 to 10 minutes while you check for: · abnormal
noises or vibration · fuel and engine oil leaks
DANGER
Avoid personal injury. Always wear eye protection when checking for fuel leaks
and never check for a fuel leak with your hands. Always use a piece of wood or
cardboard. Have your authorized YANMAR dealer or distributor repair the
damage.
3. Avoid prolonged operation at maximum load for the remainder of the first
hour of operation.
12. Rotate the engine without starting, every four to six months.
70
YDG Operation Manual
[ F I “Qr gtcvkqp”Ocpwcn
SPECIFICATIONS
PRINCIPAL SPECIFICATIONS
Generator
Model Type Excitation Voltage regulation Frequency
Rated output
Generator
Rated voltage
Rated current
Power factor
Phase
No. of poles
Type of insulation
Bearing system
AC Output terminal
DC
AC Breaker
DC
Voltmeter
Emergency stop system
L
Dimension
W
H
Protection
Performance Class (ISO8528-8)
Quality Class (ISO8528-8)
Vibation Level
Dry weight
Generator unit
YDG3700N-6(E)BYI2
YDG5500N-6(E)BYI2
Revolving field-type AC generator (with brush)
Self-excited
Automatic Voltage Regulator (AVR)
60 Hz ±1% (±2% on transient)
3.4 kVA
5.2 kVA
DC12 V – 10 A
240 V ±2%
14.2 A
21.7 A
1.0
Single-phase
2
H-class
Ball bearing (grease-enclosed)
AC240 V/16 A
Terminal (-: Black, +: Red)
14 A (NFB)
22 A (NFB)
12 A (thermal breaker)
AC300 V
Engine stop device by low level oil sensor
650 mm
720 mm
496 mm
480 mm
530 mm
578 mm
IP23M
G2
B
Amp [Avg]1mm – Acc [RMS] 52.4m/s2 Amp [Avg]1mm – Acc [RMS] 55.5 m/s2
71 kg (81 kg)
96 kg (106 kg)
YDG Operation Manual
71
SPECIFICATIONS
Generator
Model Type Excitation Voltage regulation Frequency
Rated output
Rated voltage
Rated current
Power factor
Phase
No. of poles
Type of insulation
Bearing system
AC Output terminal
DC
AC Breaker
DC
Voltmeter
Emergency stop system
L
Dimension
W
H
Protection
Performance Class (ISO8528-8)
Quality Class (ISO8528-8)
Vibation Level
Dry weight
Generator unit
YDG3700V-5(E)BYI2
YDG5500V-5(E)BYI2
Revolving field-type AC generator (with brush)
Self-excited
Automatic Voltage Regulator (AVR)
50 Hz ±1% (±2% on transient)
3.0 kVA
4.5 kVA
DC12 V – 10 A
230 V ±2%
13 A
19.6 A
1.0
Single-phase
2
H-class
Ball bearing (grease-enclosed)
AC230 V/16 A
Terminal (-: Black, +: Red)
13 A (NFB)
20 A (NFB)
12 A (thermal breaker)
AC300 V
Engine stop device by low level oil sensor
650 mm
720 mm
496 mm
480 mm
530 mm
578 mm
IP23M
G2
B
Amp [Avg]1mm – Acc [RMS] 51.7m/s2 Amp [Avg]1mm – Acc [RMS] 54.7 m/s2
71 kg (81 kg)
96 kg (106 kg)
72
YDG Operation Manual
34127
Engine
Engine model
(Generator)
Type
Combustion system
No. of cylinders
Bore × stroke
Displacement
Compression ratio
RPM (min-1)
hp SAE Continuous rated output
kW
PS
RPM (min-1)
Max. rated output (net)
hp SAE kW
PS
High idling
RPM (min-1)
Fuel injection timing
bTDC by FIC
Valve clearance
PTO position
Direction of rotation
Fuel injection pump
Fuel injection nozzle
Valve opening pressure
Fuel selection
Fuel filter
Governor
Balancer shaft
Engine weight (dry)
with electric start without electric start
Cooling system
Lubricating system
Oil selection
Oil filter
Permissible angle of inclination
Air cleaner
Muffler
SPECIFICATIONS
L70N6-G(E)YDG2
L100N6-G(E)YDG2
YDG3700N-6(E)B
YDG5500N-6(E)B
4-stroke, vertical cylinder, air-cooled diesel engine
Direct injection
1
78 × 67 mm
86 × 75 mm
0.320 L
0.435 L
20
20
3600
3600
5.9
8.9
4.4
6.6
6.0
9.0
3000
3000
6.6
9.9
4.9
7.4
6.0
10
3800
3800
20°
20°
0.15 ± 0.05 mm
Crankshaft
Counterclockwise viewed from PTO side
200 kgf/cm2
See Diesel Fuel on page 26
5 µm
All speed type, mechanical
Single shaft
41.0 kg
53.5 kg
36.0 kg
48.5 kg
Forced air by flywheel fan
Forced lubrication with trochoid pump
See Engine Oil on page 28.
Resin, 60 mesh
20° (momentary 30°)
Dry-type paper element filter
Expansion silencer with cover
YDG Operation Manual
73
SPECIFICATIONS
Engine model
(Generator)
Starting system
L
Dimensions
W
H
Oil capacity
Upper limit Lower limit
Fuel tank capacity
Battery capacity
L70N6-G(E)YDG2
L100N6-G(E)YDG2
YDG3700N-6(E)B
YDG5500N-6(E)B
Electric start/recoil start
354 mm
367 mm
436 mm
459 mm
453 mm
492 mm
1.05 L
1.6 L
0.65 L
1.0 L
13.0 L
35 Ah
Note:
1. Engine rating conditions are as follows (SAE J1349, ISO 3046/1): ·
Atmospheric condition: Room temperature 77 °F (25 °C), atmospheric pressure
29.53 in. Hg (100 kPa, 750 mm Hg), relative humidity 30 % · Fuel temperature
at fuel injector pump inlet: 104 °F (40 °C) · With cooling fan, air cleaner,
muffler: YANMAR standard · After engine break-in period. Output allowable
deviation: ±3 % · 1 PS = 0.7355 kW · 1 hp SAE (Society of Automotive
Engineers) = 0.7457 kW
74
YDG Operation Manual
SPECIFICATIONS
34127
Engine model
(Generator)
Type
Combustion system
No. of cylinders
Bore × stroke
Displacement
Compression ratio
RPM (min-1)
hp SAE Continuous rated output
kW
PS
RPM (min-1)
Max. rated output (net)
hp SAE kW
PS
High idling
RPM (min-1)
Fuel injection timing
bTDC by FIC
Valve clearance
PTO position
Direction of rotation
Fuel injection pump
Fuel injection nozzle
Valve opening pressure
Fuel selection
Fuel filter
Governor
Balancer shaft
Engine weight (dry)
with electric start without electric start
Cooling system
Lubricating system
Oil selection
Oil filter
Permissible angle of inclination
Air cleaner
Muffler
L70V5-G(E)YDG2
L100V5-G(E)YDG2
YDG3700V-5(E)B
YDG5500V-5(E)B
4-stroke, vertical cylinder, air-cooled diesel engine
Direct injection
1
78 × 67 mm
86 × 75 mm
0.320 L
0.435 L
21.1
21.2
3000
3000
5.4
7.6
4.0
5.7
5.4
7.7
3000
3000
5.9
8.4
4.4
6.3
6.0
8.6
3175
3175
13.5°
13.0°
0.15 ± 0.05 mm
Crankshaft
Counterclockwise viewed from PTO side
200 kgf/cm2
See Diesel Fuel on page 26
5 µm
All speed type, mechanical
Single shaft
41.0 kg
53.5 kg
36.0 kg
48.5 kg
Forced air by flywheel fan
Forced lubrication with trochoid pump
See Engine Oil on page 28.
Resin, 60 mesh
20° (momentary 30°)
Dry-type paper element filter
Expansion silencer with cover
YDG Operation Manual
75
SPECIFICATIONS
Engine model
(Generator)
Starting system
L
Dimensions
W
H
Oil capacity
Upper limit Lower limit
Fuel tank capacity
Battery capacity
L70V5-G(E)YDG2
L100V5-G(E)YDG2
YDG3700V-5(E)B
YDG5500V-5(E)B
Electric start/recoil start
354 mm
367 mm
436 mm
459 mm
453 mm
492 mm
1.05 L
1.6 L
0.65 L
1.0 L
13.0 L
35 Ah
Note:
2. Engine rating conditions are as follows (SAE J1349, ISO 3046/1): ·
Atmospheric condition: Room temperature 77 °F (25 °C), atmospheric pressure
29.53 in. Hg (100 kPa, 750 mm Hg), relative humidity 30 % · Fuel temperature
at fuel injector pump inlet: 104 °F (40 °C) · With cooling fan, air cleaner,
muffler: YANMAR standard · After engine break-in period. Output allowable
deviation: ±3 % · 1 PS = 0.7355 kW · 1 hp SAE (Society of Automotive
Engineers) = 0.7457 kW
Basing on altitude working conditions a derating factor for available genset
output power must be applied, according to the following graph:
DERATING PERCENTAGE vs ALTITUDE
0
-5
DERATING [%]
-10
-15
-20
-25 0
250 500 750 1000 1250 1500 1750 2000 ALTITUDE [m]
76
YDG Operation Manual
Yanmar Energy System Co., Ltd.
Umeda Gate Tower 1-9, Tsurunocho, Kita-ku, Osaka, Japan
Yanmar America Corporation
101 International Parkway Adairsville, GA 30103, U.S.A. TEL:
+1-770-877-9894 FAX:
+1-770-877-9009
https://www.yanmar.com/us/
Yanmar Europe B.V.
Brugplein11, 1332 BS Almere -de Vaart The Netherlands.
TEL: +31-36-5493200 FAX: +31-36-5493209 https://www.yanmar.com/eu/
Yanmar Asia (Singapore) Corporation Pte Ltd.
4 Tuas Lane, Singapore 638613 TEL: +65-6861-3855 FAX: +65-6862-5189
https://www.yanmar.com/sg/
Yanmar Engine (Shanghai) Corporation Ltd.
1101-1106 Gopher Center Building, No.757 Meng Zi Road Shanghai, China P.R.C.
200023 TEL: +86-21-2312-0688 FAX: +86-21-6880-8682
http://www.yanmar-china.com/cn/
Yanmar South America Industria De Maquinas Ltda.
Av. Presidente Vargas 1400, Indaiatuba, S.P., Brazil, CEP: 13338-901 TEL:
+55-19-3801-9224 FAX: +55-19-3875-3899, 2241 https://www.yanmar.com/br/
As of December 31, 2020
OPERATION MANUAL
ORIGINAL INSTRUCTIONS
YDG3700V-5BYI2, YDG3700V-5EBYI2, YDG5500V-5BYI2, YDG5500V-5EBYI2 YDG3700N-
6BYI2, YDG3700N-6EBYI2, YDG5500N-6BYI2, YDG5500N-6EBYI2
1st edition: October 2021
Issued by: YANMAR ITALY S.p.A. Edited by: YANMAR ITALY S.p.A. ENGINEERING
DEPARTMENT
YANMAR ITALY S.p.A
http://www.yanmaritaly.it
YIYDG-EN0000 2021.10
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>