NARVI T600 6015 Kota 15 Steel Chimney Instruction Manual
- June 12, 2024
- NARVI
Table of Contents
Kota 15 steel chimney
125 mm, T600
6015
T600 6015 Kota 15 Steel Chimney
- Chimney modules painted black with a heat-resistant powder coat (KKM)
- Stencil
- Installation kit:
- Installation instructions
- Data plate
- Vapour barrier sealing tape, ALUMINIUM + BLUE
- Sheeting pass-through support sealing tape, BLUE
- Aluminium collar, 4 pcs
- Mounting screws
- 3 pcs screw M6 × 16
- 3 pcs nut M6 nyloc
- 32 pcs roofing screw, black
- 8 pcs screw 4.5 × 25, black
- 3 pcs perforated strap
- 3 pcs screw 5 × 50
- Mounting strap, 1 m + fastener
KOTA STEEL CHIMNEY SYSTEM INSTRUCTIONS – INSTALLATION, USE & MAINTENANCE
Before installation, check that all products received match the order
confirmation and are free of surface defects.
The purpose of the steel chimney system is to safely conduct combustion gases
from a stove or other fireplace to outdoor air (in dry conditions when burning
wood, for example).
The steel chimney system’s temperature class is T600 – check your fireplace’s
compatibility before installation!
The chimney’s temperature class (T600) must meet or exceed the fireplace’s
average combustion gas temperature. The number of the class refers to the
temperature in Celsius. The fireplace must also be used in accordance with the
manufacturer’s instructions regarding heating and fuel amounts to prevent the
combustion gas temperature from exceeding the manufacturer’s rating.
Chimney system CE marking:
Manufacturer: Jalotakka Oy, Kangaskatu 1,
48600 Kotka, Finland
Year of manufacture: 2023
Standard number: EN 1856-1:2009
Product description: Chimney systems
Chimney system
T600 – N1 – D/W – Vm L20100 – G70
T600 = temperature class, 600 °C
N1 = negative-pressure chimney (2 L/sm2 at 40 Pa)
D/W = chimney suitable for both dry and wet conditions
Vm L20100 = corrosion resistance and liner thickness
G70 = soot fire tested, safety distance from chimney to combustibles is 70 mm
or 40 mm in open and ventilated spaces (Eurofins report number
EUFI29-2000360-T1)
Kangaskatu 1, 48600 Kotka,
Finland
09
EN 1856-1:2009
Metal prefabricated chimney
T600 – N1 – D/W – Vm L20100 – G70
Compression strength
Maximum load: 15 m of chimney modules
Wind load: Free-standing height: 1.5 m above the last support
Maximum distance between horizontal supports: 3 m
Resistant to soot fires: Yes
Other than vertical installations:
Maximum support distance 2.5 m at 30°
Flow resistance: NPD
Thermal resistance: NPD
Resistant to freezing and thawing
STEEL CHIMNEY DIAMETER AND WEIGHT PER METRE
STEEL CHIMNEY | CHIMNEY 125 |
---|---|
Flue inside diameter | 125 |
Shell outside diameter | 255 |
Weight, kg/m | 10 |
Note! The dimensions are in millimetres.
STEEL CHIMNEY SYSTEM SAFETY DISTANCES
The chimney’s safety distance refers to the distance that must be kept from
combustible materials whose fire class is not A1. The safety distance of the
JT steel chimney system is 70 mm at the pass-through connections. In open
ventilated spaces, the safety distance is 40 mm (Eurofins report number
EUFI29-2000360-T1). For the uninsulated connector, the safety distance to
combustibles is 700 mm. The chimney system’s rated safety distance must also
be considered for the installation of vapour barriers, sheeting, and roofing.
If battens or other lightweight building materials are located within the
safety distance, they must not be attached to chimney. This excludes the
collars and similar products included in the delivery. For safety distances,
see Appendices 2 and 4.
STEEL CHIMNEY SYSTEM LOCATION AND HEIGHT
The steel chimney system should be installed as close to the ridgeline as
possible. For fire safety reasons, the minimum distance between the chimney’s
mouth and the roofing is 80 cm at the ridge if the roofing’s fire class is at
least A1 or Broof (t2). For chimneys installed to a side, add 10 cm to the
height of the chimney for every metre away from the ridge (for typical roof
pitches). If the roofing is not rated for the above fire classes, the minimum
distance to the roofing is 1.5 metres. The fireplace also affects the length
of the chimney – contact the fireplace’s manufacturer for their requirements.
See Appendix 1 for dimensioning the chimney for your roof. If a natural
material is used (dry peat or moss), the cowl must include a spark catcher.
In steam rooms, the insulated part of the chimney must reach 400 mm or more
inside the room from the bottom of the ceiling. See Appendix 5. For sauna
stoves, we recommend a minimum separation of 100 mm between the stove’s
stones and the insulated part.
STEEL CHIMNEY SYSTEM BRACING AND SUPPORTS
When designing your steel chimney system, note that the maximum unsupported
height of the chimney above the roofing is 1.5 metres. If the chimney’s height
exceeds 1.5 metres above the roofing, check that your delivery includes the
necessary mounting hardware and roof braces for the installation. The delivery
includes a chimney brace collar and three half-metre perforated straps. The
chimney is supported against the rafters or the roof by folding the straps
under the rubber flashing (Figure 4). The chimney support may be installed
permanently into the roof structure. Once the chimney support has been
permanently installed, the stove can be replaced by simply opening the
uninsulated connector’s collar and sliding the connector inside the insulated
chimney module. The damper must be open for the uninsulated connector to slide
inside the insulated module.
STEEL CHIMNEY SYSTEM DAMPER
The Kota steel chimney includes a damper. The damper is not used for
fireplaces with a continuous fuel feed: oil- and gas-fired boilers, wood
pellet fireplaces with a feed system, etc.
STEEL CHIMNEY SYSTEM INSTALLATION
Note! Refer to the first page of the installation instructions for your
chimney’s delivery contents.
Handle the chimney modules with care, avoid scratching the paint.
A protective plastic film is attached to the shells. Wait until installation
is complete before removing the film from the visible parts – must be removed
before using the fireplace. Remove the plastic film from the hidden parts
during installation.
Begin the installation by planning the connection holes in the ceiling and
roof. Use the included stencil to cut the holes, observing the safety distance
requirements (Appendices 2 and 4).
First, install the connector to the fireplace’s connection. Note the
instructions of the fireplace’s manufacturer regarding chimney connections.
Fit the connector with the two grooves facing up – the grooves are used to
mount the support collar (M6 × 12 + M6 nyloc), which will make stoves easier
to remove later without moving the chimney. If the connector must be
shortened, take the length off the opposite side (bottom). For the connector’s
safety distances, see Appendix 5.
Next, fit the chimney’s damper section to the connector. Lower the chimney
onto the support collar.
(For correct orientation, the damper section’s floor plate must face down.)
If the damper section has already been passed through the ceiling, it should
be supported with the two-part flange (fixed to the ceiling with eight
screws). Before fixing the chimney in place, check that it is straight.
Note! When fitting the flange, leave a 3 mm gap between the flange’s inner
edge and the chimney. During heating, the chimney may shift vertically by up
to 15 mm. Leaving a gap between the chimney and the flange prevents damage to
the paint.
Install the middle section’s modules with the liners’ flare and the shells’
corrugation facing up. The liners must overlap by 60 mm. The shells must
overlap by about 25 mm. Attach the shells with the locking bands.
The shells are in the correct position when the band sets easily into both
mounting grooves. Also see that the tongue of the upper insulation fits into
the groove of the lower insulation (check that the shell’s top and the
insulation’s tongue are level, for example; see Figure 5).
Fit the cowl. Check that the cowl is flush with chimney’s mouth and fix it
with two roofing screws (Figure 4).
The chimney must be insulated inside and outside the roof as explained in
Appendices 2 and 4.
The extra insulation consists of 70 mm of fire-rated ceramic kaolin wool. The
wool sheet is wrapped around the chimney three times. The pass-through
insulation is finished by enclosing the wool in a metal covering (Appendices 2
and 4). The metal covering must reach 100 mm above the base insulation.
Carefully install the vapour barrier sealing flange around the chimney in
front of the extra insulation. Next, use the aluminium tape to seal the gap
between the flange and the chimney and then tape the flange’s outer edges
with the blue tape to the vapour barrier membrane. If necessary, shape the
vapour barrier flange with tin snips. The vapour barrier membrane must be
installed at least 70 mm away from the chimney. The flange and aluminium
vapour barrier tape are allowed to touch the chimney (Appendices 2, 4, and 5).
If the building has an insulated sloping roof structure, taller extra
insulation and pass-through covering must be ordered (optional extras). If the
order states the angle required, the extra insulation and covering can be
modified at the factory to match. Note! The height of the extra insulation
(wool) may not exceed 200 mm.
The extra insulation and covering can be shaped with a wool knife and tin
snips.
Carefully seal the roof around the chimney or hire a professional to do the
job. The delivery includes rubber flashing that is suited for felted roofs,
for example. See the last pages for detailed installation instructions.
Place the rubber flashing over the chimney, pull it down against the roof, and
fix it to the roof with five roofing screws per side at the mounting points.
We recommend using a sealant under the mounting points (Würth or Soudal
polymer adhesive and sealant, for example) and at the junction of the chimney
and rubber. For timber houses, note any sagging of the house. Jalotakka offers
flashing kits for all chimney sizes. Also note the winter snow load of the
roof.
Pay special attention to the correct installation of sheeting around the
chimney to prevent condensation and melting snow from dripping down along the
chimney into the insulation or room. The delivery includes a top
brace/sheeting pass-through that is suitable for most installations (chimney
bracing and sheeting insulation). The sheeting support/gasket can be modified
with tin snips. If the building or sheeting makes it impossible to install the
included top brace/sheeting pass-through, see the sheeting supplier’s
instructions.
Mount the sheeting pass-through plate to the roof battens with roofing screws
and make sure it supports the chimney. Tape the sheeting to the plate with the
blue tape (note safety distances). The safety distance from the sheeting to
the chimney’s shell is 70 mm.
If the chimney rises more than 1.5 metres above its load-bearing mounting
point, it must be supported with a roof brace or thimble and steel cables, for
example.
No additional equipment may be attached to the cowl!
Jalotakka offers various wall mounts and other special parts for its chimneys.
The steel chimney has been tested in an enclosed configuration as well.
Contact the manufacturer for enclosure instructions. Enclosures must be
constructed according to the manufacturer’s instructions.
STEEL CHIMNEY SYSTEM USE AND MAINTENANCE
Check that the damper is open before lighting a fire in the fireplace. The
damper may not be used to restrict the chimney’s flow – it may only be closed
once the embers have died completely.
The chimney must be swept regularly according to the applicable legislation
(in Finland, once a year for permanent dwellings and once every three years
for recreational dwellings). The rescue authorities may order more frequent
sweeps, if necessary.
Note! The chimney brush must be suitable for acid-resistant steel pipe
(contact the local chimney sweep).
Make sure that the chimney sweep has safe access to the chimney and can sweep
it safely.
Inspect the chimney regularly from the roof (annually, for example) – check
that it is watertight and that the cowl is intact and secure.
Install the chimney’s data plate on the shell or near the fireplace for easy
access. Mark the chimney’s size, installation date, and installer on the data
plate.
ENQUIRIES: Manufacturer
745/2017, Decree of the Ministry of the Environment on Chimney Structures and
Fire Safety
Chimney certification and other documents: nettitakka.fi/ladattavat-
materiaalit
Manufacturing
Jalotakka Oy
Kangaskatu 1
48600 Kotka, Finland
Tel. +358 10 239 4770
Fax +358 5 266 653
info@jalotakka.com
Technical support
(open in the evening and on weekends):
Niko Muurinen
Mobile +358 50 378 2974
niko.muurinen@jalotakka.com
RUBBER FLASHING, oval, 530 × 600 mm
The rubber flashing is suitable for felted and tin roofs, pitches 0–38. It may
also be used on certain fibre cement and tiled roofs if their profiles pose no
issue for shaping the aluminium mounting and proper glue adhesion. A square
430 × 430 mm flashing with a shoulder is available for roof pitches 0–22.
For tin, tiled, and fibre cement roofs, we recommend extended rear flashing
(our 1,250 × 800 mm roofing collar extension, for example). The extension must
reach up to the ridge and over the rubber flashing’s rear edge (use as many
extensions as required). The extension must overlap the rubber flashing by at
least 50 mm and the junction must be sealed with a sealant.
If the roof connection intersects the seam of a mechanically jointed roof, the
extension must be installed by a professional.
The rubber flashing is glued to the roof (with a Würth or Sikaflex adhesive or
sealant, for example). The roof must be completely dry before the flashing may
be glued into place. The surface feeling dry is not enough – the roof must be
dry within as well. Also note the adhesive manufacturer’s instructions
regarding installation temperatures.
Rubber flashing installation
-
Open up the rubber flashing to fit the chimney as follows:
1. Make a cut on the front side of the tear-off part at the correct location for the chimney’s outside diameter.
• Tear off the excess (smaller sections).
• Carefully stretch the rubber over the chimney’s shell. -
Check that the rubber sits flush with the roof, appropriate to the pitch. On a tiled roof, the flashing’s mounting points must be shaped by pressing to the profile of the tiles. The upper part must be installed under the upper tiles by at least 50 mm and over the lower tiles by at least 50 mm.
-
Use an adhesive or sealant to glue the roof part of the rubber flashing to the roof and secure it with roofing screws every 60 mm or so.
-
Fix the mouth of the rubber flashing to the chimney with the strap and sealant.
(Please note that sealant is not included in the delivery. Choose the appropriate adhesive or sealant for your roof’s material.)
Delivery includes:
– Roofing screws 4.8 × 28, 30 pcs
– Mounting strap + fastener
If necessary, trim the top module’s insulation down to the shell’s level.
LOCKING THE COWL
The liner must pass the cowl’s flange.
The cowl must be fixed to the chimney with two roofing screws.
CHIMNEY SUPPORT INSTALLATION
For example, the straps can be fixed to the rafters with 5 × 60 mm screws.
Shape the three straps and fasten them under (between) the collar.
Appendix 1
If the chimney is located on a side away from the ridge, add 10 cm to the
chimney’s height for every metre away from the ridgeline.
The above-roof chimney’s safety distance to the roof is 1–1.5 metres
vertically and three metres to other structures horizontally.
If the chimney passes through a side that slopes by 30 degrees or more, the
minimum safety distance is three metres horizontally to other structures and
1–1.5 metres vertically.
To calculate the height of the chimney, combine two measurements: take 0.8
metres above the highest point of vertical roof and combine with the height of
the point directly above the eave at the level of the roof’s highest point.
When deciding the height of the chimney, note the minimum safety distance to
make-up air vents and ventilation windows: eight metres from the chimney, or
five metres if there is at least three metres of horizontal clearance.
Note! The safety distance is always 1.5 metres to roofing other than
classes A1 or Broof (t2).
Appendix 2
Insulated roof connection G
-
Chimney 10) Extra insulation (pass-through) - Sheeting sealing plate + blue tape| 11) Ceiling
- Rubber flashing| 12) Vapour barrier
- Roofing| 13) Ceiling pass-through flange
- Roof batten| 14) Vapour barrier sealing flange and tape
- Roof batten| 14 a) Aluminium tape
- Sheeting| 14 b) Blue tape
- Load-bearing structure/insulation|
Note! The safety distance to combustibles is 70 mm (40 mm in open and ventilated spaces).
Uninsulated roof connection G (70)
- Roof batten
- Rubber flashing
- Sheeting
- Roofing
- Connection safety distance, 70 mm
- Chimney
- Load-bearing structure
- Chimney brace/sheeting passthrough + blue sealing tape
Ceiling connection G
-
Chimney
-
Insulation
-
Ceiling
-
Pass-through flange
-
Extra insulation (pass-through)
-
Vapour barrier sealing flange and tape
6 a) Aluminium tape
6 b) Blue tape -
Metal covering, prevents the base insulation material from touching the chimney’s shell
-
Support collar
Drop ceiling (steam room) ceiling connection G (70)
-
Chimney
-
Ceiling insulation
-
Surface material
-
Pass-through flange
-
Extra insulation (pass-through)
-
Vapour barrier sealing flange + tape
6 a) Aluminium tape
6 b) Blue tape -
Metal covering, prevents the base insulation material from touching the chimney’s shell
-
Support collar (sauna stove chimneys only!). The chimney must be supported while the stove is replaced, allowing the collar to be loosened and slid inside the chimney.
The stove can then be pulled away from the chimney.
- If the drop ceiling includes wool or SPU insulation, the gap between the chimney and the base insulation must be filled with extra insulation (optional extra). If no base insulation is present, no extra chimney insulation is installed. The drop ceiling mounting accessories/wool + vapour barrier are optional extras.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>