APC BR650 Back-UPS Pro User Replaceable Battery User Manual
- June 12, 2024
- APC
Table of Contents
- **APC BR650 Back-UPS Pro User Replaceable Battery
- IMPORTANT SAFETY INSTRUCTIONS
- Inventory
- Connect the Battery
- Install PowerChute™ Personal Edition Software
- Connect the Equipment
- Operation
- Alerts and System Errors
- Function Button Quick Reference
- Troubleshooting
- Specifications
- Battery Replacement
- Warranty
- APC by Schneider Electric IT Customer Support Worldwide
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
**APC BR650 Back-UPS Pro User Replaceable Battery
**
IMPORTANT SAFETY INSTRUCTIONS
Inspect the package contents upon receipt. Notify the carrier and dealer if
there is any damage.
SAVE THESE INSTRUCTIONS – This section contains important instructions
that should be followed during installation and maintenance of the UPS and
batteries.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
- This UPS is intended for indoor use only.
- Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
- Connect the UPS power cable directly to a wall outlet.
- Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
- Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and required precautions.
- A battery can present a risk of electric shock and burns by high short-circuit current.
- Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces.
Failure to follow these instructions will result in death or serious injury.
Inventory
Connect the Battery
The UPS is shipped with the battery disconnected.
BR650MI /BR900MI
-
Remove the battery door.
-
Remove the battery. Connect the wire.
-
Push the battery into the unit.
-
Replace the battery door.
BR1300MI / BR1600MI
-
Remove the battery door.
-
Remove the battery.
-
Flip or turn the battery 180 degrees upward/downward to let green side of the label face up.
-
Push the battery into the unit.
-
Replace the battery door.
Install PowerChute™ Personal Edition Software
Use PowerChute Personal Edition software to configure the UPS settings. During
a power outage, PowerChute will save any open files on your computer and shut
it down.
When power is restored, it will restart the computer.
Note: PowerChute is only compatible with a Windows operating system. If
you are using Mac OSX, use the native shutdown feature to help protect your
system. See the documentation provided with your computer.
Installation
Use the cable supplied with the Back-UPS to connect the data port on the Back-
UPS to the USB port on your computer. On the computer, go to
www.apc.com Search for “PowerChute Personal Edition”
then click on “View Details” to download the latest version of PCPE software.
Click the download link and select Software product. Select the appropriate
operating system. Follow directions to download the software.
Connect the Equipment
Battery backup and surge protected outlets
When the Back-UPS is receiving input power, the Battery Backup with Surge
Protection outlets will supply power to connected equipment. During a power
outage or other AC problems, the Battery Backup outlets receive power for a
limited time from the Back-UPS.
Connect equipment such as printers, fax machines, scanners, or other
peripherals that do not need battery backup power to the Surge Protection Only
outlets. These outlets provide full-time protection from surges even if the
Back-UPS is switched OFF.
-
USB and Serial Data port
To use PowerChute Personal Edition, connect the supplied USB cable or an optional serial cable (not supplied). -
Telephone Cable Surge Protected ports
Connect a telephone cable to the IN port, and connect a modem to the OUT port. -
AC Power Input
Use a power cable to connect the unit to AC power. -
Battery Backup outlets with Surge Protection
During a power outage or other AC problems, the Battery Backup outlets receive power for a limited time from the Back-UPS. Connect critical equipment such as desktop computer, computer monitor, modem or other data sensitive devices into these outlets. -
Circuit Breaker
Use to reset the system after an overload condition has occurred causing the circuit breaker to trip. -
In/Out Ethernet surge-protected ports
Use an Ethernet cable to connect a cable modem to the IN port, and connect a computer to the port. -
Surge Protected outlets
These outlets provide full-time protection from surges, even if the Back-UPS is off. Connect equipment such as printers and scanners that do not require battery backup protection.
Operation
Power saving display
The display interface can be configured to be continuously illuminated, or to save energy, it can be configured to darken after a period of inactivity.
- Full Time Mode: Press and hold DISPLAY for two seconds. The display will illuminate and the Back-UPS will beep to confirm the Full Time mode.
- Power Saving Mode: Press and hold DISPLAY for two seconds. The display will darken and the Back-UPS will beep to confirm the Power Saving mode. While in Power Saving Mode, the display will illuminate if a button is pressed, it then darkens after 60 seconds of no activity.
Unit sensitivity
Adjust the sensitivity of the Back-UPS to control when it will switch to battery power; the higher the sensitivity, the more often the Back-UPS will switch to battery power.
- Ensure the Back-UPS is connected to AC power, but is OFF.
- Press and hold the POWER button for six seconds. The Load Capacity bar will flash on and off, indicating that the Back-UPS is in programming mode.
- Press POWER again to rotate through the menu options. Stop at selected sensitivity. The Back-UPS will beep to confirm the selection.
- Generator Sensitivity
Input voltage is extremely low or high. (Not recommended for computer loads.)
- Default
The Back-UPS frequently switches to battery power.
- Sensitive Loads
The connected equipment is sensitive to voltage fluctuations.
Front panel buttons and display interface
Use the three buttons on the front panel of the Back-UPS and the display
interface to configure the Back-UPS.
Front panel
- MUTE button
- POWER On/Off button
- DISPLAY button
- Display interface
-
On Line: The Back-UPS is supplying conditioned AC power to connected equipment
-
Load Capacity: The load is indicated by the number of sections illuminated, one to five. Each bar represents 20% of the load.
-
Battery Charge: The battery charge level is indicated by the number of sections illuminated. When all five blocks are illuminated, the Back-UPS is at full charge. When one block is filled, the Back-UPS is near the end of its battery capacity, the indicator will flash and the Back-UPS will beep continuously.
-
Overload: The power demand from the load has exceeded the capacity of the Back-UPS.
-
Event: The event counter shows the number of events that occurred that caused the Back-UPS to switch to on-battery operation.
-
Automatic Voltage Regulation:
When illuminated, the Back-UPS is compensating for low input voltage
When illuminated, the Back-UPS is compensating for high input voltage. -
In: Input voltage.
Out: Output voltage. -
Detected System Error: The system has detected an error. The error number will illuminate on the display interface. See “Detected System errors” on page 7.
-
Mute: If the line through the speaker icon is illuminated, the audible alarm has been turned off.
-
Replace Battery: The battery is nearing the end of its useful life. Replace the battery as early as possible.
-
On Battery: The Back-UPS is supplying battery backup power to the connected equipment, it will beep four times every 30 seconds.
Alerts and System Errors
Audible indicators
Four Beeps Every 30 Seconds| Back-UPS is running on battery. You should
consider saving any work in progress.
---|---
Continuous Beeping| Low battery condition and battery run-time is very low.
Promptly save any work in progress, exit all open applications, and shut down
the operating system.
Continuous tone| Battery Backup outputs are overloaded.
Chirps every 2 Seconds with the Load Capacity Bar flashing| Battery is
disconnected.
Continuous chirping with the Load Capacity Bar and Replace Battery icon
alternately flashing| Battery did not pass the automatic diagnostic test and
should be replaced as early as possible. Pressing the MUTE button pauses the
chirping.
Alert icons
If these icons are illuminated… | This may be the problem. |
---|---|
**** | The Back-UPS is operating on AC power, but is overloaded. Disconnect |
one of the items connected to the Back-UPS. If the Overload icon stops
flashing, the Back-UPS is no longer overloaded and will continue to operate
normally.
| The Back-UPS is operating on battery power, but is overloaded.
Disconnect one of the items connected to the Back-UPS. If the Overload icon
stops flashing, the Back-UPS is no longer overloaded and will continue to
operate normally.
| The Back-UPS is operating on AC power, but the battery is not
functioning properly. Contact Schneider Electric IT (SEIT) Customer Service to
order a replacement battery. See “Battery Replacement” on page 11.
****| The Back-UPS is operating on battery power and the battery power is
getting low. Shut down all connected equipment to avoid losing an unsaved
data. When possible, connect the Back-UPS to AC power to recharge the battery.
Detected System errors
The Back-UPS will display these error messages. Except for errors F01 and F02, contact SEIT Technical Support.
F01 On-Battery Overload| Turn off the Back-UPS. Disconnect non-essential
equipment from the Battery Backup outlets and then turn on the Back-UPS.
---|---
F02 On-Battery Output Short| Turn off the Back-UPS. Disconnect all
equipment from the Battery Backup outlets and then on the turn Back-UPS.
Re-connect equipment one item at a time. If the output is tripped again, disconnect the device that caused the error.
F03 On-Battery Xcap
Overload
|
Errors F03-F09 cannot be corrected by the user, contact SEIT Technical Support for assistance.
F04 Clamp Short
F05 Charge Status
F06 Relay Welding
F07 Temperature
F08 Fan Condition (for BR1600MI only)
F09 Internal Error
Function Button Quick Reference
Function| Button| Timing
(seconds)| UPS
Status| Description
---|---|---|---|---
Power| | | |
Power On| | 0.2| Off| Press Power to start receiving input AC power.
If AC input power is not available, the Back-UPS will run on battery power.
Power Off| | 2| On| The Back-UPS is not receiving input AC power, but is
providing surge protection.
Display| | | |
Status Inquiry| | 0.2| On| Verify the status or condition of the Back-
UPS. The LCD will illuminate for 60 seconds. Press the button the toggle into
various information.
Full-Time/ Power- Saving mode| | 2| On| The LCD will illuminate and the
Back-UPS will beep to confirm the Full-Time mode. The LCD will darken and the
Back-UPS will beep to confirm the Power-Saving mode. While in Power-Saving
Mode, the LCD will illuminate if a button is pressed, then darkens after 60
seconds of no activity.
Mute
General Status Enable/ Disable
| ****| 2| On| Enable or disable the audible alarms. The Mute icon will illuminate and the Back-UPS will beep one time. –
The Mute function will not activate unless the
Back-UPS is operating on battery power.
Sensitivity| | 6| Off| The Load Capacity icon will blink, indicating
that the Back-UPS is in programming mode. Use the POWER button to scroll
through Low, Medium, and High, stop at selected sensitivity. The Back-UPS will
beep to confirm selection. See “Unit sensitivity” for details.
Self-Test (manual)| | 6| On| The Back-UPS will perform a test of the
internal battery. Note: This will happen automatically when the Back-UPS is
turned ON or when the Back-UPS previously detected a bad battery.
Event Reset| **| 0.2| On| When the Event screen is visible, press and hold
DISPLAY, then press POWER, to clear the detected error event counter.
Status Reset| **| 2| Error| After an error has been detected and
identified, press POWER to remove the visual indication and return to standby
status.
Troubleshooting
Problem | Possible Cause | Corrective Action |
---|---|---|
Back-UPS will not switch on. | The Back-UPS is not connected to AC | |
power. | Ensure that the Back-UPS is securely connected to an AC outlet. | |
The circuit breaker has been tripped. | Disconnect non-essential equipment from |
the Back-UPS. Reset the circuit breaker. Re-connect equipment one item at a
time. If the circuit breaker is tripped again, disconnect the device that
caused the trip.
The internal battery is not connected.| Connect the battery.
The AC input voltage is out of range.| Adjust the transfer voltage and
sensitivity range.
The Back-UPS does not provide power during a AC power outage.|
Ensure that essential equipment is not plugged into a Surge Only
outlet.| Disconnect equipment from the Surge Only outlet and re-connect to a
Battery Backup outlet
The Back-UPS is operating on battery power, while connected to AC power.|
The plug has partially pulled out of the wall outlet, the wall outlet is no
longer receiving AC power, or the circuit breaker has been tripped.| Ensure
that the plug is fully inserted into the wall outlet. Ensure that the wall
outlet is receiving AC power by checking it with another device.
The Back-UPS is performing an automatic self test.| No action is necessary.
The AC input voltage is out of range, the frequency is out of range, or the
waveform is distorted.| Adjust the transfer voltage and sensitivity range.
The Back-UPS does not provide the expected amount of backup
time.| Battery Backup outlets may be fully or improperly loaded.
outlets.
| Disconnect non-essential equipment from the Battery Backup outlets and
connect the equipment to Surge
The battery was recently
discharged due to a power outage and has not fully recharged.
| Charge the battery cartridge for 16 hours.
The battery has reached the end of its useful life.| Replace the battery.
The Replace Battery indicator is illuminated.| The battery
has reached the end of its useful life.| Replace the battery as early as
possible.
The Overload indicator is illuminated.| The equipment connected
to the Back-UPS is drawing more power than the Back-UPS can provide.|
Disconnect non-essential equipment from the Battery Backup outlets and
connect the equipment to Surge outlets.
The System Error icon is illuminated, other icons in the
front panel are flashing.| There is an internal detected error.|
Determine which internal error message is displayed by matching the
number displayed on the LCD with the corresponding Error Message (see
“Detected System errors”) and contact SEIT Technical Support.
Specifications
Model | BR650MI | BR900MI | BR1300MI | BR1600MI |
---|---|---|---|---|
VA | 650 VA | 900 VA | 1300 VA | 1600 VA |
Maximum Load | 390 W | 540 W | 780 W | 960 W |
Nominal Input Voltage | 220 – 240 Vac | |||
Online Input Voltage Range | 176 – 294 Vac | |||
Automatic Voltage Regulation | Boost by +11.5% when input voltage |
drops below limit
Trim by -11.5% when input voltage exceeds limit
Frequency Range| 50/60 Hz ± 3 Hz
Battery Type| Lead acid, 12V with 1 battery| Lead acid, 12V with 2
batteries
On-battery Waveshape| Step-approximated sine-wave
Typical Recharge Time| 12 hours| 16 hours
Transfer Time| 8 ms (typical), 10 ms (maximum)
On Battery Runtime| Go to: www.apc.com
Interface| USB
Operating Temperature| 08 to 408 C (328 to 1048 F)
Storage Temperature| -58 to 458 C (238 to 1138 F)
IP Rating| IP20
Unit Dimensions| 19 x 9.1 x 31 cm
(7.5 x 3.6 x 12.2 in)
| 25 x 10 x 38.2 cm
(9.8 x 3.9 x 15 in)
Unit Weight| 6.8 kg (15 lbs)| 7.2 kg (15.9 lbs)| 10.2 kg (22.5 lbs)|
11.0 kg (24.3 lbs)
Humidity| 0 to 95% relative humidity, non-condensing
Pollution degree| 2
Overvoltage category| II
Applicable power grid power distribution system| TN Power System
International Protection Code| IP20
Applicable standard| IEC 62040-1
Battery Replacement
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
- Replace the battery at least every 5 years or at the end of its service life, whichever is earlier.
- Replace the battery immediately when the UPS indicates battery replacement is necessary.
- Replace batteries with the same number and type of batteries as originally installed in the equipment.
- Replace the battery immediately when the UPS indicates a battery over-temperature condition, or when there is evidence of electrolyte leakage. Power off the UPS, unplug it from the AC input, and disconnect the batteries. Do not operate the UPS until the batteries have been replaced.
Failure to follow these instructions can result in minor or moderate injury and equipment damage.
The battery typically lasts for 3 to 5 years, a shorter period if subjected to frequent outages or elevated temperatures. Battery replacement parts for Back- UPS BR650MI is APCRBC110, for BR900MI is APCRBC164, for BR1300MI is APCRBC165, and for BR1600MI is APCRBC166. Delaying the replacement of parts may corrode the batteries in the cartridge. Recycle spent battery cartridges.
Warranty
The standard warranty is three (3) years from the date of purchase, valid in European Community. For all other regions, the standard warranty is two (2) years from the date of purchase. Schneider Electric IT (SEIT) standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an SEIT Technical Support representative. SEIT will ship the replacement unit once the defective unit has been received by the repair department, or cross-ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to SEIT. SEIT pays ground freight transportation costs to ship the replacement unit to the customer.
APC by Schneider Electric IT Customer Support Worldwide
For country specific customer support, go to the APC by Schneider Electric Web site, www.apc.com.
© 2022 APC by Schneider Electric. APC, the APC logo, Back-UPS, and
PowerChute are owned by Schneider Electric Industries S.A.S. or their
affiliated companies. All other trademarks are property of their respective
owners.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>