STAHL 8579A Wall Mount Socket Installation Guide
- June 4, 2024
- STAHL
Table of Contents
STAHL 8579A Wall Mount Socket
Installation Equipment
Wall-mounting socket 63 A
8579/31-407 Art. No. 270906
- Reliable load disconnect switch with easily visible, lockable handle and switching position display
- An integrated auxiliary contact for control and signalling purposes, can optionally be enhanced with pluggable, easily retrofittable Ex e or Ex i auxiliary contacts
- Wide temperature range for use
- High mechanical impact and shock resistance
- Perfect protection against the ingress of liquids and dust
- 3D data available to download from the website
WebCode 8579A
R. STAHL Series 8579/ 31 sockets for Zone 1/ 21 in a 4- and 5- pole version have full AC- 3 switching capacity up to 63 A. The high degree of protection IP66 guarantees the highest level of protec-tion against the penetration of dust and water in any application position. Self- cleaning lamellar contacts provide optimum contact and the plugs can be inserted and removed in the zero position quickly and easily. The load disconnect switch, with mechanical locking device and a handle that can be locked in the 0 or I position, is an additional safety feature.
Technical Data
Explosion Protection
Scope of validity| European Union (ATEX) IECEx
China (CQST)
Application range (zones)| 1
2
21
22
IECEX gas certificate| IECEx PTB 06.0020
IECEx gas explosion protection| Ex db eb IIC T6 … T5 Gb
IECEX dust certificate| IECEx PTB 06.0020
IECEx dust explosion protection| Ex tb IIIC T60 °C / T75 °C Db
ATEX gas certificate| PTB 01 ATEX 1150
ATEX gas explosion protection| E II 2 G Ex db eb IIC T6 … T5 Gb
ATEX dust certificate| PTB 01 ATEX 1150
ATEX dust explosion protection| E II 2 D Ex tb IIIC T60 °C / T75 °C Db
Certificates| ATEX (PTB), Brazil (ULB), China (CQST), EAC (ENDCE), IECEx
(PTB), Korea (KGS),
Taiwan (ITRI)
Explosion protection note| Product label may vary. Series devices have
certification according to ATEX and IECEx.
Electrical Data
Rated operational voltage AC| 480 to 500 V AC
Rated operational current| max. 63 A
Electrical service life| > 2×104 switching cycles
Mechanical service life| > 2×104 switching cycles
Type of voltage| Low voltage
Electrical Data
Switching capacity main contacts| AC-3
690 V, 63 A
18.5 kW: 220 / 230 / 240 V
30 kW: 380 / 400 / 415 V
37 kW: 500 V
55 kW: 690 V
Auxiliary contacts| 2 (1 NO + 1 NC)
Frequency range| 50 / 60 Hz
Device Specific Data
Back-up fuse with thermal protection| 80 A gG
Back-up fuse without thermal protection| 63 A gG
Ambient Conditions
Ambient temperature| -45 °C … +40 °C (T6)
-45 °C … +55 °C (T5)
Ambient temperature| -49 °F … +104 °F (T60 °C)
-49 °F … +131 °F (T75 °C)
Mechanical Data
IP degree of protection (IEC 60529)| IP66
IP degree of protection (IEC 60079)| IP66
Enclosure material| Polyester, Glass fibre reinforced
Silicone-free| No
Multiple conductor connection| 2 x 16 mm²
Finely stranded connection cross-section| 1 x 16 mm² … 1 x 50 mm²
Connection cross-section AWG finely
stranded
| 1 x AWG 6 … 1 x AWG 1/0
Width| 180 mm
Width in inches| 7.09 in
Height| 212 mm
Height, inches| 8.36 in
Length| 413 mm
Length, inches| 16.27 in
Impact strength (IEC 60079)| 7 J
Impact strength (IEC 62262)| IK10
Colour code| Black
Coding (clock hour position)| 7
Lockable in| in 0- and I-position
Series| SolConeX
Detailed number of poles| 3 P + PE
Weight| 7.8 kg
Weight| 17.2 lb
Mounting / Installation
Connection| Screw terminal
Components
Cable entry note| Entry 1: Lower left
Entry 2: Lower right
Entry 1 model| 8161/7-M50-3516-LT
Components
Entry 1 type| Polyamide cable gland
Entry 1| M50 x 1.5
Entry 1 terminal area| 16 – 35 mm
Entry 1 clamping range, inch| 0.63 – 1.38 in
Metal entry possible 1| No
Entry 2 model| 8290/3-M25
Entry 2 type| Polyamide stopping plug
Entry 2| M25 x 1.5
Metal entry possible 2| No
Technical Drawings – Subject to Alterations
Position of clock hour position
Example: 6 h position
Dimensional Drawings (All Dimensions in mm [inches]) – Subject to Alterations
Wall-mounting socket
Accessories
| |
---|---|---
****| 2 NC contacts (8080/1-3)|
168356
250 V AC/DC|
max. 6 A|
1.5….. 2.5 mm² solid / finely stranded|
The switching function of the auxiliary contact depends on the installation
slot used.|
Left and right: synchronising|
1 NC contact + 1 NO contact (8080/1-1)|
168351
250 V AC/DC|
max. 6 A|
1.5….. 2.5 mm² solid / finely stranded|
The switching function of the auxiliary contact depends on the installation
slot used.|
Left: delayed (ON), leading (OFF)|
Right: synchronising|
2 NO contacts (8080/1-4)|
168353
250 V AC/DC|
max. 6 A|
1.5….. 2.5 mm² solid / finely stranded|
The switching function of the auxiliary contact depends on the installation
slot used.|
Left and right: synchronising|
Auxiliary contact key
****| for removing the mounted auxiliary contact|
201909
---|---|---
Cable gland made of plastic
****| 8161/7-M25-1707, Ex e
Plastic, M25 x 1.5, cable outer diameter 7 to 17 mm Lot size 50 pieces
| 239157
---|---|---
8161/7-M50-3516, Ex e
Plastic, M50 x 1.5, cable outer diameter 16 to 35 mm Batch size 4 pieces
| 239160
Ex i cover
****| Ex i cover for auxiliary contacts for use in Ex i circuits|
168855
---|---|---
Stopping plug
****| 8290/3-M25
Plastic, M25 x 1.5 Lot size 1 piece
| 143524
---|---|---
Switch insert
**** | 8544/1-31L | 167239 |
---|
Spare Parts
Repair kit for sockets | 63 A Series 8579 | Art. No. |
---|---|---|
**** | Repair kit 8579 hinged cover, black |
We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding.
R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG
Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email:
sales.de@r-stahl.com |
r-stahl.com
References
- R. STAHL | Explosion Hazard Systems | Industrial Explosion Protection
- You will find a little bit of Stahl chemistry everywhere | Stahl | Stahl
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>