Midea MDV-V42WDHN1 VRF Atom B Outdoor Unit Instructions
- June 4, 2024
- Midea
Table of Contents
VRF Atom B Outdoor Unit
MDV-V42WDHN1(AtB) – Heat Pump
1-phase, 220-240V, 50/60Hz
MDV-V42WDHN1 VRF Atom B Outdoor Unit
Submittal Data
Job name:
Location:
Tag:
Date:
MDV-V42WDHN1(AtB) Features:
- All flare connections, install in a flash
- 1 to 7 indoor units connection
- Long piping length
- Centralized control with other VRF systems, convenient for unified management
- Wide operation range: cooling – -5° C to 55°C; heating – -15° C to 27°C
Specifications:
Model | MDV-V42WDHN1(AtB) |
---|---|
Cooling1 | Capacity |
kW | 12 |
Input | kW |
HER | kW/ kW |
Heating2 | Capacity |
kW | 14 |
Input | kW |
COP | kW/ kW |
Connectable indoor unit | Total capacity |
Quantity | 1~7 |
Compressor
| Type| DC inverter
Quantity| 1
Fan motor| Type| DC motor
Quantity| 1
Outdoor airflow| m3/h| 5000
Sound pressure level3| dB(A)| 56
Net/Packed dimensions (W×H×D)| mm| 950×840×440
Packed dimensions (W×H×D)| mm| 1025×950×510
Net/Gross weight| kg| 63/70
Refrigerant type/factory charge| kg| R410A/2.4
Liquid/Gas pipe| mm| Ф9.53/Ф15.9
Minimum Circuit Amps (MCA)| A| 35
Recommended Fuse Size (MFA)| A| 40
Notes:
- Indoor temperature 27°CDB, 19°CWB; outdoor temperature 35°CDB; equivalent refrigerant piping length 7.5m with zero level difference.
- Indoor temperature 20°CDB; outdoor temperature 7°CDB, 6°CWB; equivalent refrigerant piping length 7.5m with zero level difference.
- The sound pressure level is measured at 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
Dimensional Drawing:
Unit (mm)
Product specifications change from time to time as product improvements and developments are released and may vary from those in this document.