HANYOUNG nuX T57N Analog Timer Instruction Manual

June 12, 2024
HANYOUNG NUX

HANYOUNG nuX T57N Analog Timer

Product Information

  • Product Name: Analog Timer Model
  • Number: T57N
  • Manufacturer: Hanyoungnux Co., Ltd Manufacturer
  • Address: 28, Gilpa-ro 71beon-gil, Nam-gu, Incheon,
  • Korea Telephone: (82-32)876-4697 Fax: (82-32)876-4696

Safety Information

The manual classifies alerts into Danger, Warning, and Caution based on their criticality. – Danger indicates an imminently hazardous situation that can result in death or serious injury. –
Warning indicates a potentially hazardous situation that can result in death or serious injury. – Caution indicates a potentially hazardous situation that can result in minor or moderate injury.


Specifications

  • Power Supply Voltage: 4.5 VA max (240 V AC 60 Hz), Approx. 1.5 W max (24 V DC) – Power Reset Time
  • Time Range: 1 sec, 1 min, or 1 hour max. selectable – Time Repeat Error Difference – Setting Error
  • Output Mode: POWER ON DELAY, INTERVAL (Option)
  • Control Contact Output Composition: A type (time-limit 1c + instantaneous 1a) / B type (time-limit 1c + instantaneous 1c) / C type (time-limit 2c)
  • Contact Capacity: 250 V AC 3 A resistive load
  • Relay Lifespan: Mechanical – 10 million times min / Electrical – 100 thousand times min
  • Dielectric Strength: 2000 V AC 60 Hz for 1 min (Between two different current carrying parts) – Noise Immunity
  • Insulation Resistance: 100 M min (500 V DC) – Shock Resistance (Durability)
  • Operating Ambient Temperature: -10 ~ 50°C (without condensation) – Operating Ambient Humidity: 30 ~ 85% R.H. – Storage Temperature: -20 ~ 65°C – Certification
  • Connection Diagram: – A type – B type – C type
  • Suffix Code: – Dimension: P – Mounting Structure: E – Panel Type: Exposure Type – Time Range: 01, 03, 06, 10, 30, 60, 12 – Control Output: A, B, C – Output Mode: None, On-Delay, S Interval (Option)
  • Part and Function: – UP LED: After time reaches Set Time, UP LED is ON when the time-limit output is operating. – ON LED: When the power is being supplied, ON LED is flashing. Also, ON LED is ON when the time-limit output is operating. – Time Setting: Time setting knob. Time can be changeable during operation. It has s(second), m(minute), and h(hour) and can be selected arbitrarily. (but, it can be changed only when the power is OFF.)
  • Appearance and Panel Cutout: (No information provided in the text-extract)

HANYOUNGNUX CO.,LTD
28, Gilpa-ro 71beon-gil, Nam-gu, Incheon, Korea TEL : (82-32)876-4697 FAX : (82-32)876-4696
PT. HANYOUNG ELECTRONIC INDONESIA
JL.CEMPAKA BLOK F 16 NO.02 DELTA SILICON II INDUSTRIAL PARK LIPPO CIKARANG CICAU,
CIKARANG PUSAT BEKASI 17550 INDONESIA TEL : 62-21-8911-8120~4 FAX : 62-21-8911-8126

Safety information

Alerts declared in the manual are classified to Danger, Warning and Caution by their criticality

DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury

WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury

CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury

DANGER
Do not touch or connect any undesirable conductive part to input/output terminal since there is a possibility of electric shock.

WARNING

  • Please install an appropriate protective circuit on the outside if malfunction, an incorrect operation or failure of the product may be a cause of leading to a serious accident and plan for preventing accidents.
  • After mounting the product onto a panel, please use a socket dedicated to the product when connecting with other units and do not turn on the power until completing wiring to prevent electric shock.
  • Please turn off the power when mounting/dismounting of the product. This is a cause of electric shock, malfunction, or failure.
  • If the product is used with methods other than specified by the manufacturer, then it may lead to injury or property damage.
  • In order to use this product properly and safely, we recommend periodic maintenance.
  • The warranty of this product (including accessories) is 1 year only when it is used for the purpose it was intended under normal condition.

CAUTION

  • Please do not set “Time” to “0”. This can be a cause of malfunction. Also, there could be a time difference in timer operation. Please use it after confirming the time difference.
  • Please set or change “Time Range” in the dip switch while the timer is OFF. If the “Time Range” has been changed to other value during the operation, please turn off the timer and turn it back on.
  • Since this is not explosion-proof structure, please use in a place where corrosive gas (such as harmful gas, ammonia, etc.), combustible or explosive gas does not occur.
  • Please use in a place where there is no direct vibration and a large physical impact to the product.
  • Please use in a place where there is no water, oil, chemicals, steam, dust, salt, iron or others
  • Please avoid using in a place where excessive amounts of inductive interference or electrostatic and magnetic noise occur.
  • Please avoid using in a place where heat accumulation occurs due to direct sunlight or radiant heat.
  • Please use in a place where the elevation is below 2,000 m.
  • Please make sure to inspect the product if exposed to water since there is a possibility of electric leakage or a risk of fire.
  • If there is a lot of noise from the power line, installing an insulated transformer or a noise filter is recommended.
  • When the power is being supplied there should be a preparation time for the contact output.
  • Please use a delay relay together when it is used as a signal on the outside of interlock circuit or others.

Specification

Power supply voltage 24 – 240 V AC 50 – 60 ㎐, 24 – 240 V DC
Allowable voltage Power supply voltage ±10 %
Power consumption 4.5 VA max (240 V AC 60 Hz), Approx. 1.5 W max (24 V DC)
Power reset time 0.1 s max
Time range ※ Refer to suffix code
Time difference Repeat error
Setting error ±5 % max (percentage of full scale)

Control output

| Output mode| POWER ON DELAY, INTERVAL (Option)
Contact composition| A type (time-limit 1c + instantaneous 1a) /

B type (time-limit 1c + instantaneous 1c) / C type (time-limit 2c)

Contact capacity| 250 V AC 3 A resistive load
Relay life span| Mechanical : 10 million times min / Electrical : 100 thousand times min
Dielectric strength| 2000 V AC 60 Hz for 1 min (Between two different current carrying parts)
Noise immunity| ±2 kV (between power terminal, pulse width ±1㎲,

square wave noise by noise simulator)

Insulation resistance| 100 MΩ min (500 V DC)
Vibration resistance (durability)| 10 – 55 Hz (for 1 min), amplitude 0.5 mm, for 3 direction for 2 hr
Shock resistance (durability)| 300 ㎨ for each 3 direction for 3 times
Operating ambient temperature| -10 ~ 50 ℃ (without condensation)
Operating ambient humidity| 30 ~ 85 % R.H.
Storage temperature| -20 ~ 65 ℃
Certification|

Connection diagram

HANYOUNG nuX T57N Analog Timer-fig1

Suffix code

Model Code Description
Dimension ☐-
T57N    
Mounting structure P  
E    

Time range

(set with dip witch)

| 01|  |  | 1 sec, 1 min or 1 hour max. selectable
03|  |  | 3 sec, 3 min or 3 hour max. selectable
06|  |  | 6 sec, 6 min or 6 hour max. selectable
10|  |  | 10 sec, 10 min or 10 hour max. selectable
30|  |  | 30 sec, 30 min or 30 hour max. selectable
60|  |  | 60 sec, 60 min or 60 hour max. selectable
12|  |  | 12 hour, 24 hour or 48 hour max. selectable

Control output

| A|  | Time-limit : contact 1c, instantaneous : contact 1a
B|  | Time-limit : contact 1c, time-limit : contact 1c
C|  | Time-limit : 2 x contact 1c
Output mode| None| On-Delay
S| Interval (Option)

Part and function.

①| UP LED| After time reaches “Set Time”, UP LED is

ON when the time-limit output is operating.

---|---|---

|

ON LED

| When the power is being supplied, ON LED is flashing Also, ON LED is ON when

the time-limit output is operating.

③| Time setting| Time setting knob. “Time” can be

changeable during operation

| | It has s(second), m(minute) and h(hour) and can be selected arbitrarily. (but, it can be changed only when the power is OFF.)

Appearance and Panel cutout

HANYOUNG nuX T57N Analog Timer-fig4

Output operation

HANYOUNG nuX T57N Analog Timer-fig5

Above charts are On-Delay operations. In the Interval operation, Time-limit operates conversely.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

HANYOUNG NUX User Manuals

Related Manuals