TOSHIBA BMS-IFMB1280U-E Modbus Interface Installation Guide

June 12, 2024
Toshiba

BMS-IFMB1280U-E Modbus Interface

Product Information

Model name: BMS-IFMB1280U-E
BMS-IFMB1280U-TR

Product Type: Modbus interface

For commercial use

Multilingual installation manuals:
https://www.toshiba-carrier.co.jp/global/manual/bms-ifmb1280u.htm

Applications: This Modbus interface is designed
for various applications.

Functions: The Modbus interface provides
multiple functions for communication.

Specifications:

  • Power supply
  • Power consumption
  • Operating temperature / humidity
  • Storage temperature
  • Chassis material
  • Dimensions
  • Mass

Note: Modbus is a registered trade mark of Schneider
Electric SA.

Product Usage Instructions

Precautions for Safety

The user manual provides important safety information that must
be followed to avoid serious bodily harm or damage to property. Pay
attention to the warning and caution indications in the manual.

Before Installation

Before starting the installation, check the package contents.
The package should include:

  • Modbus interface (quantity: 1)
  • Installation Manual (quantity: 1)
  • Screw (quantity: 4)
  • Cable clamp (quantity: 1)

Refer to the installation manual for the type and size of screws
required.

Ensure you have the necessary wiring materials to connect the
communication cables and power cables as specified in the design of
control wiring. The installation manual provides details on wire
size, length, and types required for each line.

Installation

There are multiple installation methods available for the Modbus
interface, including surface mount and wall mount options. Use the
provided screws for installation. Ensure proper installation space
and maintenance space is reserved before installation. Refer to the
installation manual for specific dimensions and requirements.

Connection of Power Cables / Earth Wires

The installation manual provides instructions on how to connect
power cables and earth wires. Follow the specified wire sizes,
lengths, and types for each type of connection. Ensure proper
grounding and electrical safety measures are taken during the
installation process.

Modbus interface
Model name:
BMS-IFMB1280U-E BMS-IFMB1280U-TR

Installation Manual Central Control Device
For commercial use

Multilingual installation manuals
[] / [Cesky] Stazení montázní pírucky / [Dansk] Installationsvejledning, Download / [Deutsch] Installationshandbuch Herunterladen / [] / [English] Installation manual Download / [Español] Descarga del Manual de instalación / [Eesti] Paigaldusjuhendi allalaadimine / [Suomi] Asennusohjeiden lataaminen / [Français] Manuel d’installation Téléchargement / [Hrvatski] Prirucnik za instalaciju Preuzimanje / [Magyar] Telepítési kézikönyv Letöltés / [Italiano] Manuale di installazione Scaricamento / [Latviesu] Uzstdsanas rokasgrmata Lejupieldt / [Norsk] Installasjonsveiledning Last ned / [Nederlands] Installatiehandleiding downloaden / [Polski] Pobieranie Instrukcji instalacyjnej / [Português] Tranferência do manual de instalação / [Român] Manual de instalare Descrcare / [] / [Slovensky] Montázna prírucka Stiahnutie / [Slovenscina] Prenos navodil za montazo / [Svenska] Installationshandbok Nedladdning / [Türkçe] Kurulum kilavuzu ndirme / [] https://www.toshiba- carrier.co.jp/global/manual/bms-ifmb1280u.htm

Modbus interface

Installation Manual

· Thank you very much for purchasing this TOSHIBA Modbus interface. · Please read this manual carefully beforehand for proper installation of the Modbus interface.
“AEEE Yönetmeligine Uygundur.”

Contents
1 Precautions for safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 Before installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 5 Connection of power cables / earth wires / communication cables . . . . . . . . . . . . . 5 6 Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 7 Test run check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

1-EN

Modbus interface

Installation Manual

1 Precautions for safety
· Read these “Precautions for Safety” carefully before installation. · The precautions described below include important items regarding safety. Observe them without fail.
Understand the following details (indications and symbols) before reading the body text, and follow the instructions. · After the installation work has been completed, perform a test run to check for any problems. Explain how to use and maintain the unit to the customer. · Ask customer to keep this Manual at accessible place for future reference.

Indication

Meaning of Indication

WARNING

Text set off in this manner indicates that failure to adhere to the directions in the warning could result in serious bodily harm (*1) or loss of life if the product is handled improperly.

CAUTION

Text set off in this manner indicates that failure to adhere to the directions in the caution could result in serious bodily injury (2) or damage (3) to property if the product is handled improperly.

1: Serious bodily harm indicates loss of eyesight, injury, burns, electric shock, bone fracture, poisoning, and other injuries which leave aftereffect and require hospitalization or long-term treatment as an outpatient.
2: Bodily injury indicates injury, burns, electric shock, and other injuries which do not require hospitalization or longterm treatment as an outpatient.
*3: Damage to property indicates damage extending to buildings, household effects, domestic livestock, and pets.

Symbols

Meaning of Symbols
” ” Indicates prohibited items. The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol.
” ” Indicates compulsory (mandatory) items. The actual contents of the obligation indicated by a picture or text placed inside or next to the graphic symbol.

WARNING
· Ask an authorized dealer or qualified installation professional to install or reinstall this unit. Inappropriate installation may result in electric shock or fire.
· Electrical work must be performed by a qualified electrician in accordance with this installation manual. The work must satisfy all local, national and international regulations. Inappropriate work may result in electric shock or fire.
· Be sure to turn off all main power supply switches before starting any electrical work. Failure to do so may result in electric shock.
· Do not modify the unit. A fire or an electric shock may occur.

CAUTION
· Do not install this unit where flammable gas may leak. If gas leaks and accumulates around the unit, it may cause a fire.
· Perform wiring correctly in accordance with specified the current capacity. Failure to do so may result in short-circuiting, overheating or fire.
· Use predefined cable and connect them certainly. Keep the connecting terminal free from external force. It may cause an exothermic or a fire.

2-EN

Modbus interface

Installation Manual

2 Introduction

Applications / Functions / Specifications

Applications
· The Modbus interface is used to connect air conditioners “with TU2C-LINK Uh Line (hereinafter, referred to as Uh Line) installed” and TCB-IFCG1TLE to Modbus* system.

Functions
· The Modbus interface converts signals between Uh Line and Modbus Master.

Specifications

Power supply Power consumption Operating temperature / humidity Storage temperature Chassis material Dimensions Mass

220 – 240 VAC, 50/60 Hz 3 W 0 to 40 °C, 10 to 90 % RH (no condensation) -20 to +60 °C Galvanized sheet metal 0.8 t (no coating) 66 (H) x 170 (W) x 200 (D) mm 1.1 kg

  • Note) “Modbus” is a registered trade mark of Schneider Electric SA.

External view

200

6-Ø5.5 mounting

holes

66

22

78

78

22

63.6

146.9 156 170

3-EN

22

78

78

22

Modbus interface

Installation Manual

3 Before installation

Check the following package contents.

No.

Item

1 Modbus interface

2 Installation Manual

3 Screw

4 Cable clamp

Quantity
1 1 4 1

Remarks
M4 x 12 mm tapping screws

Use the following wiring materials to connect the communication cables and power cables. (locally procured)

No.

Line

Description

Type

1

For Uh Line

Wire size

Refer to “Design of Control Wiring”(P.7 to P.11).

Length

Type

2-core shielded wires

2

For RS-485

Wire size

1.25 mm2, 500 m max.

Length

(total length)

3

For power

Type Wire size

H07 RN-F or 245IEC66 0.75 mm2, 50 m max.

4 Installation
Modbus interface installation method and orientation
There are five installation methods for this Modbus interface as shown below: surface mount and wall mounts. Use the attached screws.
No good

REQUIREMENT
Do not install the unit in any of the following places. · Humid or wet place · Dusty place · Place exposed to direct sunlight · Place where there is a TV set or radio within one meter · Place exposed to rain (outdoors, under eaves, etc.)
Installation space and maintenance space
A side space for connecting through cable inlets and an upper space for maintenance must be reserved before installation. The other sides can be adjacent to surrounding objects.

100 mm 100 mm

4-EN

Modbus interface

Installation Manual

5 Connection of power cables / earth wires /
communication cables

CAUTION
· The RS-485 communication cables have polarity. Connect A(+) to A(+), and B(-) to B(-). If connected with incorrect polarity, the unit will not work.
· The Uh Line communication cable have no polarity.

Connect power cables, earth wires, and communications cables to the specified terminals on the terminal block.

Length of stripped RS-485 communication cable (not shielded wire ends)

10

50 10

Length of stripped RS-485 (Shielded wire ends) and Uh Line communication cable
50 10

Length of stripped power cable
35 10 L N

Clamping RS-485 communication cable (address 1)

Clamping communication cable

55 10

The RS-485 communication cable must be earthed on address 1 (Modbus interface address SW=1) Modbus interface. Fix the shielded wire of RS-485 communication cable with metal cable clamp and screw it to the chassis to earth it.

Do not connect the shield wire to the earth. It should be open and insulated.

A(+) Shielded wires
B(-)
The shielded wires must be crimped with closed end connectors on interfaces with address of other than 1 and not shielded wire ends.

5-EN

Modbus interface

Installation Manual

Termination resistance setting
· TU2C-LINK / TCC-LINK termination resistance setting ………… Leave just 1 line of the termination resistance in the interface board of the outdoor unit (centre unit) ON, and turn all the others OFF. (Refer to the wiring diagram attached to the outdoor unit for the position of SW.) <For TU2C-LINK> For the central control wiring (Uh line), set the termination resistance that is farthest away on the wiring between this central controller and the other unit (VRF light commercial, air to air heat exchanger, general purpose control interface, air to water heat pump) to ON.
Refer to the manual of each model for the termination resistance setting method.

U3 U4 LINK (Uh)

U3 U4 LINK (Uh)

U3 U4 LINK (Uh)

U3 U4 LINK (Uh)

Termination resistance ON

Termination resistance OFF

Termination resistance ON

Shield grounding process
· Central control wiring shielded wire …………………………………….When using the central remote controller with one unit, open the shielded wire of the central control wiring and perform insulation processing. When using the central remote controller with multiple units, connect the shield of the central control wiring to the closed end and open the shield at the final end of the central remote controller to perform insulation processing. Perform the central control wiring shield grounding on the air conditioner side.
REQUIREMENT
· Be sure to install a circuit breaker or all-pole isolating switch (with a contact breaking distance of at least 3 mm) on the primary side of the power supply.
· Fasten the screws to the terminal block with torque of 0.5 N·m.

6-EN

Modbus interface

Installation Manual

Design of Control Wiring

Communication method and model name
The TU2C-LINK model (U series) can be used together with previous models (other than U series). For details of the model and communication method, see the following table.

Communication method

TU2C-LINK (U series)

TCC-LINK (other than U series)

Outdoor unit

MMY-M P***

U series model

Other than on the left (MMY-MAP, MCY-MAP, etc.)

Indoor unit

MM*- P***

U series model

Other than on the left (MM*-AP***, etc.)

Wired remote controller RBC-AMS **

U series model

Other than on the left

Wireless remote controller receiver

RBC-AXR TCB-AXR

U series model U series model

Other than on the left

Central control device

- **

U series model

Other than on the left

7-EN

Modbus interface

Installation Manual

When the connected outdoor unit is Super Multi u series (U series)

Follow the wiring specifications in the table below even when there is a mix of U series and non-U series in the connected indoor units or remote controllers.
Wiring specifications

Item
Wire diameter Wire type Wire types that can be used

Communication line Central control wiring (Uh line) 1.0 to 1.5 mm2 (up to 1000 m) 2.0 mm2 (up to 2000 m) 2-core, non-polar Shielded wire

REQUIREMENT
When wiring the control wiring between indoor and outdoor units (Uv line)/control wiring between outdoor units (Uc line) and the central control wiring (Uh line), use the same wire type and diameter for each line. Using a mixture of different wire types and diameters may cause a communication error.

System diagram
Central control device

LINK (Uh) U3 U4

Outdoor unit (Super Multi u series)

U3 U4 Uh

Uv U1 U2

Uc U5 U6

[Central control wiring (Uh line)] L1 = Up to 2000 m [Control wiring between indoor and outdoor units (Uv line)/Control wiring between outdoor units (Uc line)] L2 = Up to 1000 m (L3+L4) = Up to 1000 m

U3 U4 Uh

Uv U1 U2

Uc U5 U6

U3 U4 Uh

Uv U1 U2

Uc U5 U6

Indoor unit *

U 1 UU24 Uv

A UB6

U 1 UU24 Uv

A UB6

U 1 UU24 Uv

A UB6

U 1 UU24 Uv

A UB6

Remote controller *

  • The wiring specifications in the system diagram above are the same even when the indoor unit or remote controller are other than the U series.

8-EN

Modbus interface

Installation Manual

When the connected outdoor units are other than Super Multi u series (U series)

Wiring specifications
Item
Wire diameter Wire type Wire types that can be used

Communication line Control wiring between indoor and outdoor units and central control wiring 1.25 mm2 (up to 1000 m) 2.0 mm2 (up to 2000 m) 2-core, non- polar Shielded wire

REQUIREMENT
When wiring the control wiring between indoor and outdoor units/central control wiring and the control wiring between outdoor units, use the same wire type and diameter for each line. Using a mixture of different wire types and diameters may cause a communication error.

System diagram
Central control device

LINK (Uh) UU33 U U44

Outdoor unit (Super Module Multi i series · Super Multi mini)

U 3 U 4U4 U 1 UU22 U 5 U 6

[Central control wiring/Control wiring between indoor and outdoor units] (L1+L2+L3) = Up to 2000 m [Control wiring between indoor and outdoor units] L4 = Up to 100 m

U 3U3U 4

U3 U4

U 1 UU1 2 U 5 U 6

U1 U2 U5 U6

Indoor unit *

U 1 UU24 Uv

A UB6

U 1 UU24 Uv

A UB6

U 1 UU24 Uv

A UB6

U 1 UU24 Uv

A UB6

Remote controller *

  • The wiring specifications in the system diagram above are the same even when the indoor unit or remote controller are other than the U series.

9-EN

Modbus interface

Installation Manual

When connecting to a previous model light commercial, air to air heat exchanger, air to water heat pump, or general purpose equipment control interface

Follow the wiring specifications in the table below even when there is a mix of U series and non-U series in the connected indoor units or remote controllers.

Wiring specifications

Item
Wire diameter Wire type Wire types that can be used

Communication line Central control wiring (Uh line) 1.25 mm2 (up to 1000 m) 2.0 mm2 (up to 2000 m) 2-core, non-polar Shielded wire

REQUIREMENT
When wiring the control wiring between indoor and outdoor units (Uv line)/control wiring between outdoor units (Uc line) and the central control wiring (Uh line), use the same wire type and diameter for each line. Using a mixture of different wire types and diameters may cause a communication error.

System diagram

Central control device

LINK (Uh) UU33 UU44

[Central control wiring (Uh line)] L1 = Up to 2000 m [Control wiring between indoor and outdoor units (Uv line)/Control wiring between outdoor units (Uc line)] L2 = Up to 1000 m

Outdoor unit and Other

U3 UU44 U1 UU22 U5 U6

Light Commercial

Air to Water Heat Pump

U3 U4

U3 U4

Air to air heat exchanger

General purpose equipment control interface

Indoor unit * Hydro unit

U1 UU24 Uv

A UB6

TCC-LU4INK adapter

U4
A UB6

Uh 4 A UB6

Remote controller *

  • The wiring specifications in the system diagram above are the same even when the indoor unit or remote controller are other than the U series.

10-EN

Modbus interface

Installation Manual

To connect 2 cables, change the preset cable clamp to the provided one and fix the cables with the cable clamp as shown in the figure left.

The shielded wire of the Uh Line communication cable must be earthed on the air conditioner. Do not connect the shield wire to the terminal block. It should be open and insulated.

The shielded wire of the RS-485 communication cable must be earthed on address 1 (Modbus interface address SW=1) Modbus interface. The shielded wires must be crimped with closed end connectors on interfaces with address of other than 1. The shielded wire ends must be insulated and left open.

LINK(Uh)

U3 U4 FG A(+) B(-) SG

Air conditioner
Modbus Master
Connect the earth wire to the earth terminal on the chassis.
Power supply 220V-240 VAC
(50/60 Hz) Connect the power supply cable and earth wire to the terminals using ring terminals with insulation sleeve.

L N

RS-485

SW8 12

SW3

LED4 LED2 LED5 LED3 LED1

SW2

SW1

1234 SW5 SW6 SW7

SW4

REQUIREMENT
Disconnect the appliance from the main power supply. This appliance must be connected to the main power supply by a circuit breaker or switch with a contact separation of at least 3 mm. Fasten the screws to the terminal with torque of 0.5 Nm.
Wiring connection
The following describes a connection example when two or more Modbus interface units are used.
Termination resistance setting (See “6 Setting” for the setting method.)
· Set the RS-485 termination resistance to “120 ohm” for address1 (Modbus interface address SW1=1) Modbus interface unit, and set to “open” for other units.
· Set the Uh Line Termination resistance. Refer to “Termination resistance setting”(P.6)
Shield earthing
· The shielded wire of the RS-485 communication cable must be earthed on address 1 (Modbus interface address SW=1) Modbus interface. Fix the shielded wire of RS-485 communication cable with metal cable clamp and screw it to the chassis to earth it. The shielded wires must be crimped with closed end connectors on interfaces with address of other than 1. The shielded wire ends must be insulated and left open.
· Do not connect the shield wire to the terminal block. It should be open and insulated. The shielded wire of the Uh Line communication cable must be earthed on the air conditioner.

11-EN

Modbus interface

Installation Manual

Modbus-Master (Locally procured)
AB (+) (-)

Do not connect the shielded wire of Uh Line communication cable to the earth.

LINK(Uh) U3 and U4 have no polarity.

LINK(Uh)
SG B A FG U3 U4
RS-485

Set the RS-485 termination resistance on the address1 unit (Modbus interface address SW1=1) and host system. Do not set it here.

Uh Line termination resistance

SW1

Refer to “Termination resistance

4

setting”(P.6)

Outdoor unit

Outdoor unit

SW5

SW6

U4 U3 U2 U1 U2 U1

U2 U1

U4 U3 U2 U1 U2 U1

U4 U3

Central remote controller

Indoor unit Remote controller Indoor unit

Remote controller
Indoor unit

NL

Power supply

Indoor unit Central remote controller

The shielded wire of the RS-485 communication cable must be earthed on address 1
CAUTION: RS-485 communication cables A(+) and B(-) have polarity. Be careful when connecting the RS485 wires.

LINK(Uh)
SG B A FG U3 U4
RS-485

SW1
1
SW5 SW6

Outdoor unit

Outdoor unit

U4 U3 U2 U1 U2 U1

U2 U1

U4 U3 U2 U1 U2 U1

U4 U3

Indoor unit Indoor unit

Remot e controller

Remote controller

Power supply
NL

RS-485 termination resistance is set by Modbus interface of address setting switch SW1=1 only.

Set the Modbus interface address with SW1. Assign 1 to F(15) to each address to avoid duplication. CAUTION: The SW1 setting is read when the power is turned on. Push the reset switch SW7 after changing the address.

12-EN

Modbus interface

Installation Manual

6 Setting

The following settings are necessary to use Modbus interface. · SW1 Sets the Modbus slave addresses of the Modbus interface.
A single Modbus interface uses three Modbus slave addresses. (One address for the current interface and two addresses for potential interfaces.) When two or more Modbus interfaces are used for a single line RS-485 bus, set the addresses as indicated in the table below. Assign address numbers in ascending order, from smallest to largest.

Modbus interface No.1 No.2 No.3 No.4 No.5

Address 1 4 7 10 13

CAUTION

· For the Modbus interface whose address SW1=1, perform termination resistance setting. · When the SW1 setting has been changed, press the reset switch SW7. The new address setting is read. · When the setting of bit3 and bit4 of SW3 has been changed, press the reset switch SW7. The new set value is read.

· SW2 · SW3
· SW4 · SW5 · SW6 · SW7
· SW8

Test switch

Not used during operation. Set these switches to zero (0) or “all OFF”.

Test switch

Bit1: Central controller ID setting mode switch

Bit2: Switches the LED5 display for test runs.

Bit3, 4: RS-485 baud rate setting (9600/19200/38400) bps.

Test switch

Not used during operation.

RS-485 termination resistance select switch

Set “120 ohm” only when the Modbus interface address SW=1, and set “open” for other Modbus interfaces.

Uh Line termination resistance select switch

Refer to “Termination resistance setting”(P.6)

Reset switch

When performing an address setting with SW1, push this reset switch after the address setting to read

the set value.

Test switch (Not used during operation. All OFF usually)

13-EN

Modbus interface

Installation Manual

LINK(Uh)

RS-485

U3 U4 FG A

B

SW3

LED4 LED2 LED5 LED3 LED1

SW2

SW1

1234 SW5 SW6 SW7

SW4

SW8 12

SW1 SW2
SW3
SW4 SW5

Modbus interface address set switch

1-F

Modbus interface address

0

Not used

Test switch (0 usually)

Bit1: Uh Line communication setting mode switch.

OFF: Normal circumstance; ON: Central controller ID setting mode

Bit2: Switches the LED5 display for test runs.

OFF RS-485 communication status indicator.

ON Uh Line communication status indicator.

Bit3, 4: RS-485 baud rate setting (9600/19200/38400) bps.

3 OFF, 4 OFF 9600 bps, 3 ON, 4 OFF 19200 bps,

3 OFF, 4 ON 38400 bps, 3 ON, 4 ON 19200 bps.

Test switch

RS-485 termination resistance select switch

ON
120 ohm

ON
Open

SG

L

N

SW6

Uh Line termination resistance select switch

ON
100 ohm

ON
Open

SW7 Reset switch SW8 Test switch (all OFF usually) LED1 Power indicator LED2 RS-485 communication status indicator LED3 Uh Line communication status indicator LED4 Uh Line communication error indicator LED5 Test indicator

REQUIREMENT

· RS-485 termination resistance select switch SW5. Set “120 ohm” only when the Modbus interface address SW=1, and set “open” for other Modbus interfaces.
· The Uh Line termination resistance is set on the air conditioner side. Set SW6 to “open”.

14-EN

Modbus interface

Installation Manual

Central controller ID setting mode
The central controller ID setting mode changes the central controller ID of the Modbus interface. (central controller ID at the time of factory shipping is central controller ID 20.) The central controller ID number indicates the Uh Line address and communication priority for the Uh Line compatible central control device.

Change the central controller ID in the following cases. · If using Modbus interface with a central control device not compatible with Uh Line, set the central controller ID as “old controller.”
(1) Transition to central controller ID setting mode
· If setting the Modbus slave address with SW1, make a note of the SW1 value before performing central controller ID setting operations.
· Turn on bit1 of SW3. (2) Verification of central controller ID
· If SW1 is set to 0, central controller ID is displayed by LED2 to LED5.

=ON, =OFF

Central controller ID

LED5

LED4

LED3

LED2

Central controller ID7

Central controller ID8

Central controller ID9

Central controller ID10

Central controller ID11

Central controller ID12

Central controller ID13

Central controller ID14

Central controller ID15

Central controller ID16

Central controller ID17

Central controller ID18

Central controller ID19

Central controller ID20 (initial value)

Old controller

15-EN

Modbus interface

Installation Manual

(3) Change of central controller ID · Change SW1 to 1-F and press SW4. · If using Modbus interface with a central control device not compatible with Uh Line, set as “old controller.”

Central controller ID Central controller ID7 Central controller ID8 Central controller ID9 Central controller ID10 Central controller ID11 Central controller ID12 Central controller ID13 Central controller ID14 Central controller ID15 Central controller ID16 Central controller ID17 Central controller ID18 Central controller ID19 Central controller ID20 (initial value) Old controller

SW1 1 2 3 4 5 6 7 8 9 A B C D E F

NOTE
Because the Uh Line compatible central control device uses high-order central controller ID, setting of central controller ID1 to ID6 cannot be done with Modbus interface.

(4) Conclusion of central controller ID setting mode · Turn off bit1 of SW3. · Return the SW1 value to that of the Modbus slave address.
IMPORTANT Immediately after the power is turned on for the Modbus interface, the SW1 value is the Modbus slave address. When the power is turned on, if the SW1 value is that of the central controller ID or is 0, the Modbus interface will not operate properly. When concluding the central controller ID setting mode, be sure to return the SW1 value to that of the Modbus slave address.

16-EN

Modbus interface

Installation Manual

7 Test run check

Before starting test run
· Set the indoor unit central control address so that it does not match any other indoor unit addresses. · Be sure to press the reset switch SW7 on the Modbus interface when the indoor unit central control address
setting has been changed or added.

Test run

(1) Check the communication status between Modbus interface and indoor unit or TCB-IFCG1TLE with LED5. Check that the communication between Modbus interface and each indoor unit or TCB-IFCG1TLE connected is normally performed by selecting an indoor unit or TCB-IFCG1TLE using SW1 to SW3.
Confirming procedure: · Set bit2 of SW3 to “ON” during normal operation. · Set the central control address of the target indoor unit with SW1 and SW2. Set SW1 and SW2 according to
the “Indoor unit central control address and SW1/SW2 setting” table below. · Communication status is displayed by LED5.

Communication status with indoor unit Normal Error
Invalid indoor unit

LED5 Lighting Blinking
Light off

Remarks
Communication with the indoor unit was established previously, but is disabled currently. Communication with the indoor unit has never been established.

· The protocol for communication with an indoor unit is displayed by LED4.

Protocol for communication with indoor unit

LED4

Note

In communication via Uh Line

On

When Modbus interface is performing communication with the relevant indoor unit via Uh Line.

In communication based on old communication protocol

When Modbus interface is performing communication with Blinking the relevant indoor unit based on old communication
protocol.

(Example) Check the communication status of indoor unit with a central control address of 41. Set bit2 of SW3 to “ON”, SW2 to “2” and SW1 to “8”.

Indoor unit or TCB-IFCG1TLE central control address and SW1/SW2 setting

Indoor unit

Indoor unit

Indoor unit

Indoor unit

central control SW2 SW1 central control SW2 SW1 central control SW2 SW1 central control SW2 SW1

address

address

address

address

1

00

17

10

33

20

49

30

2

01

18

11

34

21

50

31

3

02

19

12

35

22

51

32

4

03

20

13

36

23

52

33

5

04

21

14

37

24

53

34

6

05

22

15

38

25

54

35

7

06

23

16

39

26

55

36

8

07

24

17

40

27

56

37

9

08

25

18

41

28

57

38

10

09

26

19

42

29

58

39

11

0A

27

1A

43

2A

59

3A

12

0B

28

1B

44

2B

60

3B

17-EN

Modbus interface

Installation Manual

Indoor unit

Indoor unit

Indoor unit

Indoor unit

central control SW2 SW1 central control SW2 SW1 central control SW2 SW1 central control SW2 SW1

address

address

address

address

13

0C

29

1C

45

2C

61

3C

14

0D

30

1D

46

2D

62

3D

15

0E

31

1E

47

2E

63

3E

16

0F

32

1F

48

2F

64

3F

65

40

81

50

97

60

113

70

66

41

82

51

98

61

114

71

67

42

83

52

99

62

115

72

68

43

84

53

100

63

116

73

69

44

85

54

101

64

117

74

70

45

86

55

102

65

118

75

71

46

87

56

103

66

119

76

72

47

88

57

104

67

120

77

73

48

89

58

105

68

121

78

74

49

90

59

106

69

122

79

75

4A

91

5A

107

6A

123

7A

76

4B

92

5B

108

6B

124

7B

77

4C

93

5C

109

6C

125

7C

78

4D

94

5D

110

6D

126

7D

79

4E

95

5E

111

6E

127

7E

80

4F

96

5F

112

6F

128

7F

(2) Check the communication status between Modbus Interface and outdoor unit with LED5. Check that the communication between Modbus Interface and each outdoor unit connected is normally performed by selecting an outdoor unit using SW1 to SW3.

Confirming procedure: · Set bit2 of SW3 to “ON” during normal operation. · Set the line address of the target outdoor unit with SW1 and SW2.
Set SW1 and SW2 according to the table below, titled “Line address of outdoor unit and SW1/SW2 setting”. · Communication status is displayed by LED5.

Communication status with outdoor unit Normal Error
Invalid outdoor unit

LED5 Lighting Blinking
Light off

Remarks
Modbus interface is in communication with the outdoor unit.
Communication with the outdoor unit was established previously, but is disabled currently.
Communication with the outdoor unit has never been established.

· The protocol for communication with an outdoor unit is displayed by LED4.

Protocol for communication with outdoor unit

LED4

Note

In communication via Uh Line

On

When Modbus interface is performing communication with the relevant outdoor unit via Uh Line.

In communication based on old communication protocol

When Modbus interface is performing communication with Blinking the relevant outdoor unit based on old communication
protocol.

(Example) Check the communication status of outdoor unit with line address of 10. Set bit1 of SW3 to “ON”, SW2 to “8” and SW1 to “9”.

18-EN

Modbus interface

Installation Manual

Line address of outdoor unit and SW1/SW2 setting

Line address of outdoor unit 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

SW2 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8

SW1 0 1 2 3 4 5 6 7 8 9 A B C D E F

Line address of outdoor unit 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

SW2 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9

SW1 0 1 2 3 4 5 6 7 8 9 A B C D E F

NOTE For air conditioner (multi type), the line addresses of outdoor unit 29 to 32 are not used.

(3) Perform the communication status checking between Modbus interface and Modbus Master. Check that the communication with Modbus Master is normally performed. When bit2 of SW3 is set to “OFF”, the communication status with the Modbus Master is displayed by LED5.

Communication status with Modbus Master Normal reception
Error

LED5 Lighting
Light off

Remarks
Lights for one second
A communication error occurred or no data has been received.

LED indication during normal operation

LED1 LED2 LED3 LED4 LED5

LED Power indicator RS-485 communication status indicator Uh Line communication status indicator Uh Line communication error indicator TEST indicator

Description Lights while the power is on. Blinks during RS-485 communication. Blinks during Uh Line communication. Lights temporarily when Uh Line is busy. Used in the test mode.

19-EN

Modbus interface
Manufacturer / Importer

Installation Manual

20-EN

Klimaniza ilikin daha ayrintili bilgiler için ürün tanitim broürlerine, gerektiinde Alarko Carrier Yetkili Satici ve Servislerine ulaabilmek için 444 0 128 numarali
Müteri Danima Hattimiza bavurabilirsiniz.
DEC0309101-1

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>