DXR1.E02PLZ-112 Pressure Sensor
User Manual

DXR1.E02PLZ-112 Pressure Sensor

Desigo™ Room Automation
Compact actuating room automation stations, BACnet/IP, AC 24 V (Actuating XDR)
DXR1.E02PLZ-112

Combination of room automation station and actuator for buildings with increasing demand on functionality and flexibility in Room Automation, VAV applications.

  • Combination of compact room automation station and actuator for VAV control
  • No room unit can be connected
  • BACnet IP communications (BTL certified)
  • 2-port Ethernet switch
  • USB interface
  • Operating voltage AC 24 V
  • Built-in 10 Nm actuator
  • Internal 0…500 Pa differential pressure sensor
  • Plug-in terminal blocks

Features

Compact series
The compact build allows direct mounting on the damper shaft.
Plug-in terminal blocks
Plug-in terminal blocks for easy exchange of room automation stations.
Integrated actuator
The actuator gear base is integrated into the housing of the actuating XDR. It supports dampers with up to 10 Nm torque.

Use

The Design Room Automation offers the highest level of flexibility for energy- optimized solutions while satisfying requirements for temperature control, ventilation, and comfort using standard tools and established workflows.
Pre-installed application types
Variable (VAV) and constant air volume flow control

Functions

The selected application and its parameters as well as input and output configuration determine the room automation station’s functionality. A detailed description of functionality is available in the ABT (Automation Building Tool) online help.
Communication

  • 2-port Ethernet switch for cost-effective cabling via line topology Note: DXR1 supports cabling based on daisy chain topology. The max. the number is 20 devices and in the event of a failed automation station, all other stations are no longer reachable. DXR1 can be cabled as ring topology if higher reliability is required. This requires support for layer 2 switches RSTP (Rapid Spanning Tree Protocol) as well as SNMP monitoring and that any loss of the superposed system is reported. In the event of a fault, switching the communication paths can take between 10 and 30 seconds. DXR1 routes the RSTP protocol for the switches. It does not actually process the RSTP protocol. Further information can be found in the Application Guide for BACnet Networks in Building Automation (A6V11159798).
  • USB connection for service and commissioning and firmware download

LED indication

LED Color Activity Function
Run Green Steady ON The device is ready for operation
Steady OFF The device is not powered
Regular flashing Start-up or the program is stopped
Red Steady OFF OK
Steady ON Program error Hardware fault
Rapid flashing Wrong or corrupt software No application loaded
Blinking per wink command Physical device identification

SIEMENS DXR1 E02PLZ 112 Pressure Sensor - Fig 1

Service button (SVC)
Physical identification on the network.

Technical / Mechanical design

SIEMENS DXR1 E02PLZ 112 Pressure Sensor - Fig 2

1 Service button (SVC) for sending device identification 2 Power supply
3 Status information LED (bi-color) 4 2-port Ethernet switch

Housing
The housing consists essentially of flame-retardant, non-brominated plastic.

Type summary

Product no.| Stock no.| Inputs| Outputs| Description| Quantity
---|---|---|---|---|---
DXR1.E02PLZ-112| S55499-D460| –| –| VAV application| Single package/ multiple packages (10)

Ordering
When ordering, indicate product number, stock number, and description.

Product documentation

Topic Title Document ID:
Installation, cable length, topology Design Room Automation installation
guide CM111043
Engineering and commissioning ABT online help N/A
Installation instruction Mounting instructions A6V11393918
Commissioning Quick guide A6V11526405
Product environmental declaration A6V11805930
EU declarations (CE) A6V11791489

Documents such as environmental declarations, CE declarations, etc., can be downloaded at the following Internet address: http://siemens.com/bt/download

Notes
Security

| CAUTION
---|---
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property damage.
● Observe national provisions and comply with the appropriate safety regulations.
● Use only properly trained technicians for mounting, commissioning, and servicing.

Engineering
Identification
Each device has a unique serial number to ensure efficient commissioning. It is provided on the adhesive barcode reader. The serial number can be read directly into the engineering tool using a barcode reader.
Wiring
Wiring must be sufficiently insulated to the available rated voltage. The sizing and fusing of the wiring depend on the connected load.

Mounting

The automation station is mounted directly on a damper shaft.

![SIEMENS DXR1 E02PLZ 112 Pressure SensSIEMENS DXR1 E02PLZ 112 Pressure Sensor

See the mounting instructions (document ID: A6V11393918) for detailed information.
Differential pressure sensor

  • Avoid bends and pressure when attaching the tube.

  • Connect the “+” connection on the side with the higher pressure and the “-” connection on the side with the lower pressure.

  • Connection tubes (interior diameter) of 4 mm.
    Air tube connection kit DXA.T50 for connection of tubes with 6.5 mm (interior diameter).

  • The maximum tube length is 2 m.

Maintenance

The automation station is maintenance-free.
Disposal

| The device is considered an electronic device for disposal in accordance with European Directive and may not be disposed of as domestic waste.
● Use only designated channels for disposing of the devices.
● Comply with all local and currently applicable laws and regulations.
---|---

**Technical data

**

Power data

Power supply

Operating voltage (SELV/PELV)| AC 24 V +/-20 %
Frequency| 50 or 60 Hz
Power consumption| 7 VA max.
Transformer requirements and recommended voltages

Type| Class 2, AC 24 V, 50 / 60 Hz, SELV, PELV

Functional data

Functional data

Nominal torque| 10 Nm
Nominal rotary angle| 90°
Maximum rotary angle| 95° ± 2°
Runtime for 90° rotary angle| 150 s
Shaft size| 8…16 mm, round
8…10 mm, round (with centering insert) 6…12.8 mm square
Minimum shaft length| 20 mm

Pressure sensor

Pressure sensor

Measurement range| 0…500 Pa
Sample rate| ≤ 500 ms
Overload range| 0…100 kPa
Measuring range accuracy Zero point accuracy Resolution| 3 %
0.2 Pa 12 Bit

Connections

Interfaces

Ethernet| Plugs: dual RJ45, 10M/100M fast Ethernet Interface type: IEEE 802.3 compliance Cable type: 100M STP CAT 5
USB (2.0)| Type Micro B

Conformity

Ambient conditions and protection classification

Classification per IEC/EN 60730
The function of automatic control devices
Pollution degree
Overvoltage category| Type 1
2
III
Design type| Device suited for use with equipment of safety classes I and II
Degree of protection of housing to IEC EN 60529 Room automation station| IP20
Climatic ambient conditions
Transport (packaged for transport) as per IEC EN 60721-3-2
Operation as per IEC/EN 60721-3-3| Class 2K3
Temperature -25…70 °C
Air humidity 5…95 % (non-condensing)
Class 3K5 Temperature -5…50 °C
Air humidity 5…95 % (non-condensing)
Mechanical ambient conditions
Transport as per IEC/EN 60721-3-2
Operation as per IEC/EN 60721-3-3| Class 2M2 Class 3M2
Standards, directives and approvals

Product standard| IEC/EN 60730-1
Automatic electronic controls for household and similar use
EU conformity (CE)| A6V11791489
RCM conformity| A6V11791498
EAC conformity| Eurasian conformity
UL Approbation
Federal Communications Commission| UL as per UL916, http://ul.com/database cUL as per CSA – C22.2 No. 205
FCC CFR 47 Part 15 Class B
ICES003| CAN ICES-3 (B)/NMB-3(B)
Environmental compatibility| The product environmental declaration (A6V11805930*) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).

FCC regulations
Modification of this device to receive cellular radiotelephone service signals is prohibited under FCC rules and federal law.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/TV technician for help.
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

General

General information

Color| Light gray
Dimensions| L × W × H = 137 × 143 × 82 mm
Weight| Net weight: 614.1 g
Gross weight: 817.3 g

Diagrams
Connection terminals

DXR1.E02PLZ-112SIEMENS DXR1 E02PLZ 112 Pressure Sensor - Fig
4

Pin

| Description|

Terminal

---|---|---
1, 2| IP connection|
USB| USB interface|

81, 82 power

24 V~

| Power supply AC 24 V| V~
System neutral (must always be grounded at the transformer)| ⏊
ΔP differential pressure

detector

| Connected to the higher pressure| P1+
Connected to the lower pressure| P1-
Service| Service button| SVC
Display| Operation LED| RUN

Dimensions
Dimensions in mmSIEMENS DXR1 E02PLZ 112 Pressure Sensor - Fig
5 Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies
Document ID ……………………A6V11393935_en–_d
Edition …………………2021-08-26
© Siemens Switzerland Ltd, 2021