CPS 1 HP Commercial Refrigerant Recovery System Instruction Manual
- June 7, 2024
- CPS
Table of Contents
CPS 1 HP Commercial Refrigerant Recovery System
SPECIFICATIONS
Models|
**CR700/CR700JUK***
| CR700E| CR700J|
CR700S
---|---|---|---|---
Compressor Type|
1 HP Oil-less Reciprocating Compressor
Dimensions|
20cm (8”) wide x 37cm (14.5”) long x 30.5cm (12”) high
Weight|
15.3 kg (34 lbs.)
Operating Temperature Range|
0°C (32°F) to 49°C (120°)
Power Source|
115 V 50/60Hz 1 Ph
| 220-240 V 50/60 Hz 1 Ph| 100 V 50/60 Hz 1 Ph|
230 V 50/60 Hz 1 Ph
Power Consumption|
850 W
Suction Pressure Gauge|
-30” hg to 350 psig -76 cm hg to 35 kg/cm
| -1 to 34.5 bar -100 kPa to 3450 kPa| -.1 to 3.5 MPa|
-30” hg to 350 psig -76 cm hg to 35 kg/cm
Discharge Pressure Gauge|
0 to 800 psig
0 to 55 kg/cm
|
0 to 55 bar
0 to 5500 kPa
| 0 to 5.5 MPa| 0 to 800 psig
0 to 55 kg/cm
Filtration|
Cleanable 100-mesh screen integrated into Suction Port
Shut-Off Valves|
Both Suction and Discharge piston manifold valves
Construction|
Heavy gauge aluminum chassis with High Density Polyethylene Case
Overload Protection|
15 amp
| 8 amp| 15 amp|
8 amp
High Pressure Shut-Off|
38 bar (550 psig)
Refrigerants|
R-12, R-134a, R-401C, R-406A, R-500, R-401A
R-409A, R-401B, R-412A, R-411A, R-407D, R-22
R-411B, R-502, R-407C, R-402B, R408A, R-509
R-407A, R-404A, R-402A, R-507, R-407B, R-410A
Flow Rate (at 60hz, reduce 15% for 50hz) Direct Vapor
Direct Liquid Push-Pull Liquid|
Up to 43 kg/hr Up to 1.6 lb/min
Up to 271 kg/hr Up to 10 lb/min
Up to 542 kg/hr Up to 20 lb/min
INTRODUCTION
Thank you for purchasing the CPS PROSET CR700 series unit. CPS is dedicated to
give you the fastest and most reliable equipment to meet all your commercial
refrigerant recovery requirements. In doing this CPS has integrated its latest
technology and incorporated state of the art features while improving
reliability and speed. The CR700 incorporates an Exclusive CPS Designed Patent
Pending compressor that maximizes speed in both direct liquid and direct vapor
recovery. The unit is equipped with a high airflow and high efficiency
condensing system to maximize vapor recovery speed. The CR700 also
incorporates an automatic Low
Pressure shut off switch.
The CR700 is designed for servicing commercial and residential refrigeration
systems. Simply follow the quick start guide and turn it on. Once the recovery
is complete, simply turn the center valve to the SELFCLEARING position. Now
the unit is ready for the next type of refrigerant.
The PROSET CR700 series utilizes a 1 hp (0.85kW) patent pending oil-less
compressor, non-restrictive piston manifold valves, and high capacity
condensing system.
The following are additional features:
- “On the Run” SELF-CLEARING valve. No need to turn off the unit when switching from recovery to self-clearing.
- On board SUCTION and DISCHARGE gauges.
- 0 to 55 bar (800-psig) discharge gauge to handle R-410A.
- Small physical size.
- Automatic Low Pressure cutout switch.
- Integrated easy to use carrying handle and Safety bar.
- 550 psig High Pressure cutout switch
- Easy and secure filter accesses. No dangling filters to be damaged.
- Replaceable or cleanable filter cartridge.
- The Suction and Discharge shut-off valves. Easy to service if replacement required.
- Heavy-duty powder coated aluminum chassis surrounded by a tough High-Density Polyethylene case.
- Maintenance free Oil-less compressor
- Optional tank overfill sensor cord kit.
- patent pending
Low Pressure override switch to allow for continuous operation. To help you get a good start, please continue to carefully read the balance of this manual. This manual contains important information on the proper procedures for operating this equipment. Please pay close attention to the safety information, WARNING and CAUTIONS provided throughout this manual. Always remember “SAFETY FIRST”.
GENERAL SAFETY INSTRUCTIONS
Only qualified service personnel should operate this unit. Most states,
countries, etc… may require the user to be licensed. Please check with your
local government agency.
DANGER- the recovery tank used with this contains liquid refrigerant.
Overfilling of the recovery tank may cause a violent explosion resulting in
severe injury or even death. As a minimum, please use a scale to continuously
monitor the recovery tank weight.
DANGER- Avoid breathing refrigerant vapors and lubricant vapor or mist.
Breathing high concentration levels may cause heart arrhythmia, loss of
consciousness, or even cause suffocation.
DANGER- ELECTRICAL SHOCK HAZARD-Always disconnect power source when
servicing this equipment.
DANGER- EXPLOSION RISK. Do not recovery flammable refrigerants
CAUTION- all hoses may contain liquid refrigerant under pressure. Contact
with refrigerant may cause frostbite or other related injuries. Wear proper
personal protective equipment such as safety goggles and gloves. When
disconnecting any hose, please use extreme caution.
CAUTION- avoid breathing refrigerant vapors and/or lubricant mist.
Exposure may irritate eyes, nose, throat, and skin. Please read the
manufacturers Material Safety Data Sheet for further safety information on
refrigerants and lubricants.
CAUTION- to reduce the risk of fire, avoid the use of extension cords
thinner than NO. 14 awg. (1,5mm) to prevent the overheating of this cord
please keep length to a minimum.
CAUTION- do not use this equipment in the vicinity of spilled or open
containers of gasoline or other flammable substances. Make certain that all
safety devices are functioning properly before operating the equipment.
This equipment is intended for use of one refrigerant at a time until the Self
Clearing feature is used. Mixing of different refrigerants will cause your
recovered supply of refrigerant to become contaminated.
Note: It is very expensive to destroy mixed or damaged refrigerants
DIRECT LIQUID OR VAPOR OPERATION
-
Connect the unit as shown in Diagram 1.
Note: The recovery tank must be rated for 38 bar. -
Open the vapor valve on the Recovery Tank.
-
Open DISCHARGE valve on CR700.
Note: The Suction valve should be closed at this time. -
Rotate the center valve to the “RECOVERY” position.
-
Push the Main Power Switch “ON”.
Note: If the unit fails to start, make sure there is no suction pressure on the suction side of the unit. The compressor is designed to start against high differential pressures. Pressure on the suction side will reduce this differential. Reset Circuit Breaker if tripped. Push the LP Override Switch to the “ON” position. -
Once unit has started, open the SUCTION valve on the CR700 to start the refrigerant flow.
-
The CR700 is designed to directly recover large amounts of liquid refrigerant. If during liquid recovery the compressor begins to make a slugging or hammering noise, meter the incoming liquid by closing the suction valve until the noise subsides.
-
The CR700 will automatically shut off* when a 10”hg vacuum is achieved. If the pressure rises (due to boiling liquid refrigerant) the CR700 will resume operation.
-
After the CR700 has shut off, rotate the center valve to the SELF CLEARING position. The CR700 will resume operation automatically. The CR700 is now clearing out the condenser. The CR700 will automatically shut off* when a 10”hg vacuum is achieved.
Note: If the LP override switch is set to “ON” position the unit will run continuously.
RECOVERY AND SELF-CLEARING ARE COMPLETE
LIQUID PUSH-PULL OPERATION
-
Connect the unit as shown in Diagram 2.
Note: The recovery tank must be rated for 38 bar. -
Open the liquid and vapor valve on the Recovery Tank.
Note: The Suction valve should be closed at this time. -
Open the DISCHARGE valve on CR700.
-
Rotate the center valve to the “SELF-CLEARING” position.
-
Push the Main Power Switch “ON”
Note: If the unit fails to start, make sure there is no suction pressure on the suction side of the unit. The compressor is designed to start against high differential pressures. Pressure on the section side will reduce this differential. Reset Circuit Breaker if tripped. Push the LP Override Switch to the “ON” position. -
Once unit has started, open the SUCTION valve on the CR700 to start the vapor refrigerant flow.
-
Monitor the optional inline sight glass for liquid refrigerant movement.
-
Once the liquid refrigerant is no longer present, close SUCTION valve. The CR700 will automatically shut off* when a 10”hg vacuum is achieved.
-
Proceed to Direct Vapor Recovery Operation. (prior page)
Note: If the LP override switch is set to “ON” position the unit will run continuously.
ROUTINE MAINTENANCE
Filter Maintenance- the CR700 is equipped with a 100-mesh screen filter. This filter should be checked periodically. A partially clogged filter will slow down the recovery rate of this unit.
Check the filter cartridge as follows:
-
Use a 5/8” socket or boxed end wrench to loosen the suction port as shown in Figure 1.
-
Once loose, remove the suction port- filter cartridge as shown in Figure 2.
-
Either clean the current cartridge or replace with new cartridge.
-
Inspect O-ring. Re-lubricate with compressor oil or equivalent.
-
Place filter cartridge back into suction port fitting.
-
Hand tighten this assembly back onto the CR700.
-
Use a 5/8” socket or boxed end wrench to tighten 1/8 of a turn.
Do not over tighten, damage to the O-ring may occur. -
Check the connection for leaks.