HUAWEI UPS5000-H-800 kVA 100 kVA Power Modules Three Phase Three Wire User Guide

June 12, 2024
Huawei

UPS5000-H-800 kVA Quick Guide
(100 kVA Power Modules, Three-Phase Three-Wire)
Issue: 02
Date: 2022-12-29

Installing Cabinets

NOTICE

  1. Before installation, read the user manual carefully to get familiar with product information and safety precautions.
  2. Use insulated tools when installing the equipment.
  3. Only qualified professionals or trained personnel are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the caused UPS damage is not covered under any warranty or service agreement.
  4. This document describes the operation procedure for a single UPS. For details about how to operate a parallel system, see the user manual.

Space PlanningHUAWEI UPS5000 H 800 kVA 100 kVA Power Modules Three Phase
Three Wire - Space Planning UnpackingHUAWEI UPS5000 H 800 kVA 100 kVA Power Modules
Three Phase Three Wire - Unpacking

Recommended Power Cables

Item 800 kVA
Mains input Mains input current (A)
Recommended cross- sectional area (mm2) L1/L2/L3
PE 240
Bypass input Bypass input current (A)
Recommended cross- sectional area (mm2) L1/L2/L3
PE 240
Output Output current (A)
Recommended cross- sectional area (mm2) U/V/W
PE 240
Battery input (lead acidbattery) Nominal battery discharge current (A)
Maximum battery discharge current (A) 2123
Recommended cross-sectional area (mm2) +/-
PE 240
Battery input (SmartLi) Nominal battery discharge current (A)
Maximum battery discharge current (A) 2086
Recommended cross-sectional area (mm2) For details, see the IEC-60364- 5-52

specifications and SmartLi User Manual.
Equipotential ground point| Recommended cross-sectional area (mm2)| 16
Connection method: Crimped DT terminal
Bolt specifications: L1/L2/L3/U/V/W/+/-:M16 x 55 mm (120 N•m) PE: M12 x 30 mm (47 N•m)
Equipotential ground point: M6 x 12 mm (4.5 N•m)
NOTE: The currents listed in the table are measured at a rated voltage of 380 V.

Cabinet DescriptionHUAWEI UPS5000 H 800 kVA 100 kVA Power Modules Three
Phase Three Wire - Cabinet Description

Model Weight Dimensions (H x W x D)
UPS5000-H-800K-NTN < 1300 kg 2000 mm x 1600 mm x 1000 mm
Inductor cabinet < 550 kg 2000 mm x 400 mm x 1000 mm

Securing the Cabinets

HUAWEI UPS5000 H 800 kVA 100 kVA Power Modules Three Phase Three Wire -
Cabinets

Installing Rectifiers and Cables

NOTICE

  • Cables have been preinstalled and bound in the inductor cabinet.
  • The cables from the inductor cabinet to the UPS are configured based on the longest cable length before delivery. If short cables are needed in the actual installation scenario, you can cut the excess cables and crimp terminals.
  • Cables must be bound to the nearest beam or cable bridge according to the route shown in the figure.
  • Do not bind signal cables and power cables together.
  • The number and colors of cables in the figures are for reference only.

HUAWEI UPS5000 H 800 kVA 100 kVA Power Modules Three Phase Three Wire -
Rectifiers and Cables

Verifying the Installation

  1. Check that there is no foreign matter in the cabinets.
  2. After routing cables and verifying cable connections, seal the gap between cables and the cabinets using sealing putty. (Remove the paper protective film from the sealing putty and retain the transparent film. When using the putty, ensure that the transparent film faces upward.)
  3. After verifying the installation, reinstall all the covers.
  4. Do not remove the dustproof cover before power-on to prevent dust from entering the UPS.

NOTICE
Sealing putty must be used as a whole and the gap can be sealed only from the top.

HUAWEI UPS5000 H 800 kVA 100 kVA Power Modules Three Phase Three Wire -
Installation

Power-On Commissioning

NOTICE

  1. Before powering on the UPS5000, ensure that the check items in the UPS5000 Startup Service Report and the post-installation check items are verified.
  2. Measure the voltage and frequency of the UPS upstream input switch. The line voltage range is 138–485 V AC, and the frequency range is 40–70 Hz.

4.1 Powering On the UPS
HUAWEI UPS5000 H 800 kVA 100 kVA Power Modules Three Phase Three Wire -
Powering On the UPS 4.2 Initial Startup

  1. Obtain the startup password through the app. After the application is approved, enter the password on the service authorization screen of the device to complete device authorization.
    NOTICE
    Technical support engineers can obtain the service authorization code through the app. For details, see the Data Center Facility Deployment Guide.

  2. Set the language, time, date, network parameters, and system parameters on the Settings Wizard screen.HUAWEI UPS5000 H 800 kVA 100 kVA Power Modules Three Phase Three Wire - network parameters NOTICE
    Set all battery parameters according to the actual situation: Assume that the battery specifications are 150 Ah/12 V, 40 batteries are connected in series, and two battery strings are connected to the UPS in parallel. Set Single battery voltage(V) to 12, Single battery capacity(Ah) to 150, Battery in a battery string to 40, and Number of battery strings to 2.

  3. After you perform the settings, the Bypass mode and No battery alarms are reported by the MDU and do not need to be cleared. If there is any other alarm, you need to rectify the fault.

  4. If the system has connected to the remote EPO switch, you need to choose Monitoring > UPS System > Running Parameter > System Settings on the WebUI and set EPO detection to Enable.

  5. View the system running status diagram on the MDU to check that the UPS is working in bypass mode.

4.3 Starting the Inverter

  1. On the main menu, choose Common Functions and tap Inv. ON.
  2. In the displayed login window, enter the user name and password, and tap .
  3. In the displayed dialog box, tap Yes to start the inverter.
System User LCD Preset Password WebUI Preset Password
admin (system administrator) 1 Changeme
operator (common user) 1 Changeme

NOTE
To ensure system security, change the LCD and WebUI passwords after the first login.
4.4 Powering On Loads

  1. After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears from the MDU.
  2. After confirming that the battery strings are properly connected, switch on the battery string input circuit breaker. If there are multiple battery strings, switch on the circuit breaker for each battery string and then switch on the general circuit breaker between battery strings and the UPS. The No battery alarm disappears from the MDU.
  3. Turn on the UPS downstream output switch to supply power to the loads.

Shutting Down the UPS

5.1 Shutting Down the Inverter to Transfer the UPS to Bypass Mode
After you shut down the inverter, the UPS transfers to bypass mode if the bypass is normal; the UPS supplies no power if the bypass is abnormal. Before shutting down the UPS, ensure that all loads have been shut down.

  1. On the main menu of the LCD, choose Common Functions and tap Inv. OFF.
  2. In the displayed login window, enter the user name and password, and tap .
  3. In the displayed dialog box, tap Yes to shut down the inverter.

5.2 Powering Off a Single UPS

HUAWEI UPS5000 H 800 kVA 100 kVA Power Modules Three Phase Three Wire -
Single UPS Huawei Digital Power Technologies Co., Ltd.
Huawei Digital Power Antuoshan Headquarters
Futian, Shenzhen 518043
People’s Republic of China
www.huawei.com

Documents / Resources

| HUAWEI UPS5000-H-800 kVA 100 kVA Power Modules Three Phase Three Wire [pdf] User Guide
UPS5000-H-800 kVA 100 kVA Power Modules Three Phase Three Wire, UPS5000-H-800 kVA, 100 kVA Power Modules Three Phase Three Wire, Modules Three Phase Three Wire, Three Phase Three Wire, Three Wire
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals