MITSUBISHI ELECTRIC WT09757X01 Air Conditioners Instruction Manual

June 12, 2024
Mitsubishi Electric

MITSUBISHI ELECTRIC WT09757X01 Air Conditioners

MITSUBISHI-ELECTRIC-WT09757X01-Air-Conditioners-
PRODUCT

Product Information

The product is an air-conditioner unit designed for building applications. The model numbers for the indoor unit are CMB-WP108NU-AA, CMB-WP1016NU-AA, CMB- WP108NU-AB, and CMB-WP1016NU-AB. This installation manual provides instructions for safe and correct use of the air-conditioner unit.

Safety Precautions
Before installation and electric work, it is important to read and follow the safety precautions provided in the manual. These precautions include important points regarding safety to prevent injury or damage to the unit.

Precautions for Devices that Use R410A Refrigerant
When handling devices that use R410A refrigerant, it is cautioned to prevent dust, dirt, or water from entering the refrigerant cycle as it may deteriorate the refrigerant.

Product Usage Instructions

Installing the HBC Controller
To install the HBC controller, follow these steps:

  1. Check the accessories that come with the HBC controller.
  2. Install the HBC controllers according to the provided instructions.

Connecting Refrigerant Pipes and Drain Pipes
When connecting refrigerant pipes and drain pipes, follow these steps:

  1. Connect the refrigerant pipes according to the provided instructions.

Selecting an Installation Site
Before selecting an installation site, consider the following:

  • The product is suitable for specific installation sites.
  • Avoid installing near heat sources, naked flames, or other ignition sources.

Securing Installation and Service Space
To secure installation and service space, follow the provided dimensions and instructions. The manual provides diagrams and measurements for different installation scenarios.

Checking the Installation Site
Before installation, check that the difference of elevation between indoor and outdoor units and the length of refrigerant piping are within the specified limitations.

INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.

Safety precautions

Before installation and electric work

  • Before installing the unit, make sure you read all the “Safety precautions”.
  • The “Safety precautions” provide very important points regarding safety. Make sure you follow them.

Symbols used in the text

Warning:
Describes precautions that should be observed to prevent danger of injury or death to the user.

Caution:
Describes precautions that should be observed to prevent damage to the unit.

Symbols used in the illustrations

  • Indicates an action that must be avoided.
  • Indicates that important instructions must be followed.
  • Indicates a part which must be grounded.
  • Beware of electric shock. (This symbol is displayed on the main unit label.)

Warning:
Carefully read the labels affixed to the main unit.

HIGH VOLTAGE WARNING:

  • Control box houses high-voltage parts.
  • When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
  • Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes.

Warning:

  • Ask the dealer or an authorized technician to install the air conditioner.
  • Improper installation by the user may result in water leakage, electric shock, or fire.
  • Install the unit at a place that can withstand its weight.
  • Failure to do so may cause the unit to fall down, resulting in injuries and damage to the unit.
  • Use the specified cables for wiring. Make the connections securely so that the outside force of the cable is not applied to the terminals.
  • Inadequate connection and fastening may generate heat and cause a fire.
  • Prepare for earthquakes and install the unit at the specified place.
  • Improper installation may cause the unit to fall down and result in injury and damage to the unit.
  • Always use accessories specified by Mitsubishi Electric.
  • Ask an authorized technician to install the accessories. Improper installation by the user may result in water leakage, electric shock, or fire.
  • Never repair the unit. If the air conditioner must be repaired, consult the dealer.
  • If the unit is repaired improperly, water leakage, electric shock, or fire may result.
  • If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
  • If refrigerant gas leaks during installation work or service, ventilate the room.
  • If the refrigerant gas comes into contact with a flame, poisonous gases will be released.
  • Install the air conditioner according to this Installation Manual.
  • If the unit is installed improperly, water leakage, electric shock, or fire may result.
  • Do not modify or adjust safety protection devices.
  • Shorting of pressure or temperature switches to force operation may lead to damage, fire, explosions etc…
  • Do not change the set values as this may lead to damage, fire, explosions etc…
  • Use of any product except that specified by this company may lead to damage, fire, explosions etc…
  • Do not spray water on electrical parts.
  • This could lead to shorting, fire, smoke, electrical shock, unit failure etc…
  • Do not create a situation where the refrigeration circuit is sealed yet incomplete with oil or refrigerant in the system.
  • This may result in an explosion.
  • Do not touch electrical components during or directly after operation.
  • This may lead to burns.
  • Put covers on control and terminal boxes.
  • Shock due to ingress of dust, water, smoke, fire etc. may result.
  • During refrigerant recovery or purge, fire may result.
  • Do not operate with guards or panels removed.
  • Injury due to rotating parts, electric shock due to high voltage or burns due to high temperatures may result.
  • Do no sit, ride or place objects on the unit.
  • Injury due to the unit falling may result.
  • Use the appropriate safety gear.
  • High voltages may result in electric shock.
  • Hot parts may result in burns.
  • Recover the refrigerant in the unit.
  • Reuse the refrigerant or have it disposed of by a specialist.
  • Release of refrigerant may damage the environment.
  • Clear the pipework of remnant gas and oil.
  • Failure to do so could lead to an eruption of flames and burns if the pipework is heated.
  • Vacuum dry the refrigerant pipework. Do not replace with a refrigerant that has not been specified.
  • This could lead to explosions, fire.
  • Do not touch the onsite pipework ends.
  • This could damage the pipework leading to refrigerant leaks and oxygen deficiency.
  • Have all electric work done by a licensed electrician according to “Electric Facility Engineering Standard” and “Interior Wire Regulations” and the instructions given in this manual and always use a dedicated power supply.
  • If the power source capacity is inadequate or electric work is performed improperly, electric shock and fire may result.
  • Securely install the cover of control box.
  • If the cover is not installed properly, dust or water may enter the outdoor unit and fire or electric shock may result.
  • When installing and moving the air conditioner to another site, do not charge it with a refrigerant different from the refrigerant specified on the unit.
  • If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
  • If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit if the refrigerant should leak.
  • Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
  • When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
  • If the air conditioner is installed improperly, water leakage, electric shock, or fire may result.
  • After completing installation work, make sure that refrigerant gas is not leaking.
  • If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or other heat source, it may generate noxious gases.
  • Do not reconstruct or change the settings of the protection devices.
  • If the pressure switch, thermal switch, or other protection device is shorted or operated forcibly, or parts other than those specified by Mitsubishi Electric are used, fire or explosion may result.
  • To dispose of this product, consult your dealer.
  • The installer and system specialist shall secure safety against leakage according to local regulation or standards.
  • Choose the appropriate wire size and the switch capacities for the main power supply described in this manual if local regulations are not available.
  • Pay special attention to the place of installation, such as basement, etc. where refrigeration gas can accumulate, since refrigerant is heavier than the air.
  • This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
  • Children should be supervised to ensure that they do not play with the appliance.
  • This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.

Precautions for devices that use R410A refrigerant

Caution:

  • Do not use existing refrigerant piping.
  • The old refrigerant and refrigerant oil in the existing piping contain a large amount of chlorine which may cause the refrigerant oil of the new unit to deteriorate.
  • R410A is high-pressure refrigerant and can cause the existing piping to burst.
  • Use refrigerant piping made of phosphorus deoxidized copper and copper alloy seamless pipes and tubes. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.
  • Contaminants on the inside of the refrigerant piping may cause the refrigerant residual oil to deteriorate.
  • Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
  • If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor failure may result.
  • Apply a small amount of ester oil, ether oil, or alkyl benzene to flares. (for indoor unit)
  • Infiltration of a large amount of mineral oil may cause the refrigerant oil to deteriorate.
  • Do not use a refrigerant other than R410A.
  • If another refrigerant (R22, etc.) is mixed with R410A, the chlorine in the refrigerant may cause the refrigerant oil to deteriorate.
  • Use a vacuum pump with a reverse flow check valve.
  • The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerant oil to deteriorate.
  • Do not use the following tools that are used with conventional refrigerants.(Gauge manifold, charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, refrigerant recovery equipment)
  • If the conventional refrigerant and refrigerant oil are mixed in the R410A, the refrigerant may deteriorate.
  • If water is mixed in the R410A, the refrigerant oil may deteriorate.
  • Since R410A does not contain any chlorine, gas leak detectors for conventional refrigerants will not react to it.
  • Do not use a charging cylinder.
  • Using a charging cylinder may cause the refrigerant to deteriorate.
  • Do not use antioxidant or leak-detection additive.
  • Be especially careful when managing the tools.
  • If dust, dirt, or water gets into the refrigerant cycle, the refrigerant may deteriorate.

Before installation

Caution:

  • Do not install the unit where combustible gas may leak.
  • If the gas leaks and accumulates around the unit, an explosion may result.
  • This product is not designed to assist in the preservation of food, provide conditions to maintain plants or animals, or stabilize environments for the preservation of precision equipment or art objects. To prevent loss of quality, do not use the product for purposes other than those it is designed for.
  • Do not use the air conditioner in special environments.
  • Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of the air conditioner or damage its parts.
  • When installing the unit in a hospital, communication station, or similar place, provide sufficient protection against noise.
  • Sound pressure level does not exceed 70 dB(A). However, inverter equipment, private power generator, high-frequency medical equipment, or radio communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
  • Do not install the unit on or over things that are subject to water damage.
  • When the room humidity exceeds 80 % or when the drain pipe is clogged, condensation may drip from the indoor unit or HBC controller. Perform collective drainage work together with the outdoor unit, as required.
  • Do not install the unit where corrosive gas may be generated.
  • Doing so can corrode the pipes, resulting in refrigerant leakage and fire.
  • Check that markings of the unit are not illegible.
  • Illegible warning or caution markings may cause damage to the unit, resulting in injury.

Before installation (relocation) – electrical work

Caution:

  • Ground the unit.
  • Do not connect the ground wire to gas or water pipes, lightning rods, or telephone ground lines. Improper grounding may result in electric shock.
  • Install the power cable so that tension is not applied to the cable.
  • Tension may cause the cable to break and generate heat and cause a fire.
  • Install a leak circuit breaker, as required.
  • If a leak circuit breaker is not installed, electric shock may result.
  • Use power line cables of sufficient current carrying capacity and rating.
  • Cables that are too small may leak, generate heat, and cause a fire.
  • Use only a circuit breaker and fuse of the specified capacity.
  • A fuse or circuit breaker of a larger capacity, or the use of substitute simple steel or copper wire may result in a general unit failure or fire.
  • Do not wash the air conditioner units.
  • Washing them may cause an electric shock.
  • Be careful that the installation base is not damaged by long use.
  • If the damage is left uncorrected, the unit may fall and cause personal injury or property damage.
  • Install the drain piping according to this Installation Manual to ensure proper drainage. Wrap thermal insulation around the pipes to prevent condensation.
  • Improper drain piping may cause water leakage causing damage to furniture and other possessions.
  • Be very careful about transporting the product.
  • One person should not carry the product. Its weight is in excess of 20 kg.
  • Some products use PP bands for packaging. Do not use any PP bands as a means of transportation. It is dangerous.
  • Safely dispose of the packing materials.
  • Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
  • Tear apart and throw away plastic packaging bags so that children will not play with them. If children play with a plastic bag which has not been torn apart, they face the risk of suffocation.

Before starting the test run

Caution:

  • Turn on the power at least 12 hours before starting operation.
  • Starting operation immediately after turning on the main power switch can result in irreversible damage to internal parts. Keep the power switch turned on during the operational season.
  • Do not touch the switches with wet fingers.
  • Touching a switch with wet fingers can result in an electric shock.
  • Do not touch the refrigerant pipes during and immediately after operation.
  • During and immediately after operation, the refrigerant pipes may be hot or cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes.
  • Do not operate the air conditioner with the panels and guards removed.
  • Rotating, hot, or high-voltage parts can cause injuries.
  • Do not turn off the power immediately after stopping operation.
  • Always wait at least 5 minutes before turning off the power. Otherwise, drainage water leakage or mechanical failure of sensitive parts may occur.
  • Check for refrigerant leaks before service.
  • If the refrigerant leaks, fire may result.

Selecting an installation site

  • This unit uses R410A-type refrigerant.
  • Indoor units that are all WL models are connectable to the HBC controller.
  • Piping for systems using R410A may be different from that for systems using conventional refrigerant because the design pressure in systems using R410A is higher. Refer to the Data Book for more information.
  • Some of the tools and equipment used for installation with systems that use other types of refrigerant cannot be used with the systems using R410A. Refer to the Data Book for more information.
  • Do not use the existing piping, as it contains chlorine, which is found in conventional refrigerating machine oil and refrigerant. This chlorine will deteriorate the refrigerant machine oil in the new equipment. The existing piping must not be used as the design pressure in systems using R410A is higher than that in the systems using other types of refrigerant and the existing pipes may burst.

Installation site

  • Install the unit in a place not exposed to rain. The HBC controller is designed to be installed indoors.
  • Install the unit with adequate space around it for servicing.
  • Do not install the unit in a place that would result in the piping length restrictions being exceeded.
  • Check for refrigerant leaks before service.
  • If the refrigerant leaks, fire may result.
  • Install or store the unit in a place not exposed to direct radiant heat from other heat sources or naked flame or other ignition sources.
  • Do not install the unit in any oily steamy place or near any machine that generates high frequencies. Doing so may cause a risk of fire, erroneous operation or condensation.
  • Depending on the operation conditions, HBC controller generates noise caused by valve actuation, refrigerant flow, and pressure changes even when operating normally. Therefore install the unit in places such as ceilings of corridor, restrooms and plant rooms.
  • Install indoor unit and HBC controller at least 5 m [16-3/8 ft] away from each other when installed in a space with low background noise, e.g., hotel rooms.
  • Allow enough space and access to ensure water piping, refrigerant piping and electrical wiring can be easily connected.
  • Avoid places exposed to the generation, inflow, accumulation or leakage of flammable and sulfuric gases.
  • Ensure a downward gradient of at least 1/100 for drain piping.
  • Properly install the unit on a stable, load-bearing surface.

For hanging from the ceiling

  • Provide 2 inspection holes 450 mm [17-3/4 in] square in the ceiling surface as shown in [Fig. 2.3.1]. [Fig. 2.2.1]
  • Install the unit in a suitable location (such as in the ceiling of a corridor or in the bathroom etc) away from places regularly occupied. Avoid installing in the center of a room.
  • Ensure hanging bolts are of sufficient pull out strength.

Warning:

  • Be sure to install the unit in a place that can sustain the entire weight.
  • If there is a lack of strength, it may cause the unit to fall down, resulting in an injury.

Caution:

  • Be sure to install the unit horizontally. Install the HBC controller level (less than 1° tilt), so that the drain pan can function correctly.
  • Install the HBC controller in an environment where the temperature in always above 0°C [32°F].

Securing installation and service space

For hanging from the ceiling
(This is a reference view showing the least installation space.) [Fig. 2.3.1]

  • A Inspection hole
  • B Side of outdoor unit piping
  • C Control box
  • D Side of indoor unit piping
  • E Water inlet
  • F Service space
  • G Indoor unit side

1 Dimensions with which pipe connection can be handled at site

Model name A B
CMB-WP108NU-AA 1520 [59-7/8] 160 [6-5/16]
CMB-WP1016NU-AA 1800 [70-7/8] 300 [11-13/16]
CMB-WP108NU-AB 1520 [59-7/8] 160 [6-5/16]
CMB-WP1016NU-AB 1520 [59-7/8] 160 [6-5/16]

Checking the installation site
Check that the difference of elevation between indoor and outdoor units and the length of refrigerant piping are within the following limitations.

CMB-WP108NU-AA + CMB-WP108NU-AB (CMB-WP1016NU-AA) (CMB-WP1016NU-AB) [Fig. 2.4.1]

  • A Outdoor unit
  • B Main-HBC controller
  • C Sub-HBC controller
  • D Indoor unit
  • E Less than H=50 m [164 ft] (when the outdoor unit is higher than the HBC controller)
  • F Less than H1=40 m [131 ft] (when the outdoor unit is lower than the HBC controller)
  • G Branch joint (field supply)
  • H Less than 110 m [360 ft]
  • I Less than 60 m [196 ft]
  • J Up to three units for 1 branch port Total capacity: less than 30 (but in same mode, cooling/heating)
  • K Less than 15 m [49 ft]
  • L Less than 15 m [49 ft]

(Unit: m [ft])

  Item Piping portion Allowable value

Pipe Lengths

| Between outdoor unit and HBC controller (refrigerant pipework)| A| 110 [360] or less
Water pipework between indoor units and HBC controller| f + g| 60 [196] or less

Difference of elevation

| Between indoor and outdoor units| Above outdoor unit| H| 50 [164] or less
Below outdoor unit| H1| 40 [131] or less
Between indoor units and HBC controller| h1| 15 [49] or less
Between indoor units| h2| 15 [49] or less

Notes:

  1. Indoor units that are connected to the same branch joint cannot be simultaneously operated in different operation modes.
  2. CMB-WP108NU-AA + CMB-WP108NU-AB (CMB-WP1016NU-AA) (CMB-WP1016NU-AB) [Fig. 2.4.2]
  • A Outdoor unit
  • B Main-HBC controller
  • C Sub-HBC controller
  • D Indoor unit
  • E Less than H=50 m [164 ft] (when the outdoor unit is higher than the indoor unit)
  • F Less than H1=40 m [131 ft] (when the outdoor unit is lower than the indoor unit)
  • G Twinning pipe (field supply)
  • H Less than 110 m [360 ft]
  • I Less than 60 m [196 ft]
  • J Up to three units for 1 branch port Total capacity: less than 30 (but in same mode, cooling/heating)
  • K Less than 15 m [49 ft]
  • L Less than 15 m [49 ft]
  • M Less than 15 m [49 ft]
  • N Branch joint (field supply)

(Unit: m [ft])

  Item Piping portion Allowable value

Pipe Lengths

| Between outdoor unit and

HBC controller (refrigerant pipe- work)

|

A1 + A2 + A3

|

110 [360] or less

Water pipework between indoor units and HBC controller| f + g| 60 [196] or less
Between HBC controllers| B| 40 [131] or less

Difference of elevation

| Between indoor and outdoor units| Above outdoor unit| H| 50 [164] or less
Below outdoor unit| H1| 40 [131] or less
Between indoor units and HBC controller| h1| 15 [49] or less
Between indoor units| h2| 15 [49] or less
Between HBC controllers| h3| 15 [49] or less

Installing the HBC controller

Checking the accessories with the HBC controller

The following items are supplied with each HBC controller.

  Model name

CMB-WP108NU-AA CMB-WP1016NU-AA
 | Item| Qty
1| Installation manual| 1
2| Wrench| 1
 | Model name
---|---
CMB-WP108NU-AB CMB-WP1016NU-AB
 | Item| Qty
1| Installation manual| 1

Installing HBC controllers

Installing hanging bolts

  • Install locally procured hanging bolts (threaded rod) following the procedure given in the figure. The hanging bolt size is ø10 mm [13/32 in] (M10 screw).
  • To hang the unit, use a lifting machine to lift and pass it through the hanging bolts. The suspension bracket has an oval hole. Use a large diameter washer. [Fig. 3.2.1]
  1. Hanging method
    • A: Min.30 mm [1-3/16 in]
    • A. Hanging bolt ø10 mm [13/32 in] (field supply)
    • B. Washer (field supply)MITSUBISHI-ELECTRIC-WT09757X01-Air-Conditioners-fig- \(6\)
  • A Within 1.0º
  • B Drain socket
  • C Viewed from the front of the control box
  • D Viewed from the drain socket side

Be sure to install the HBC controller horizontally. Check using a level. If the controller is installed at an angle, drain water may leak out. If the unit is slanted, loosen the fixing nuts on the hanging brackets to adjust its position. Install the HBC controller level (less than 1° tilt), so that the drain pan can function correctly.

Caution:

  • Be sure to install the unit horizontally. Install the HBC controller level (less than 1° tilt), so that the drain pan can function correctly.
  • Install the HBC controllers with the hanging length within 200 mm [7-7/8 in] or shorter.

Connecting refrigerant pipes and drain pipes

Connecting refrigerant pipes

  1. Be sure to use non-oxidative brazing where necessary. If you do not use non-oxi-dative brazing, it may clog the pipes. When brazing the outdoor unit connecting port of HBC controller, supply nitrogen gas into the pipe between the outdoor unit and HBC controller.
  2. After completing pipe connection, support the pipes to ensure that load is not imparted to the HBC controller’s end connections.
  3. When using mechanical couplings, use the ones that meet ISO14903.
  4. Support the on-site pipes near the HBC controller at 0.5-meter [19-11/16 in] inter-vals or less, and at 2-meter [78-3/4 in] intervals or less in other areas.

Warning:
When installing and moving the unit, do not charge it with refrigerant other than the refrigerant (R410A) specified on the unit.

  • Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to malfunction and result in severe damage.

Caution:

  • Use refrigerant piping made of phosphorus deoxidized copper and copper alloy seamless pipes and tubes. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, swarf, oils, moisture, or any other contaminants.
  • R410A is high-pressure refrigerant and can cause the existing piping to burst.
  • Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
    • If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor failure may result.
    • Infiltration of a large amount of mineral oil may cause the refrigerant oil to deteriorate.
  • Do not vent R410A into the atmosphere.

Size of HBC controller’s end connection piping [Fig. 4.1.2]

Use of one HBC controller

(Unit: mm [in])

  HBC controller
Unit model Model name

Outdoor unit side

| PURY-(E)P72T/

YNU

|

(HBC controller) CMB-WP108NU-AA

CMB-WP-1016NU-AA *2

| ø15.88 [5/8] (Brazing)| ø19.05 [3/4] (Brazing)
PURY-(E)P96T/

YNU

| ø19.05 [3/4] (Brazing)| ø22.2 [7/8] (Brazing)
PURY-(E)P120T/

YNU

| ø19.05 [3/4] (Brazing)| ø28.58 [1-1/8] (Brazing)

Use of two HBC controllers

  HBC controller
Unit model Model name

twinning pipe and HBC controller
High pressure side| Low pressure side| High pressure side| Low pressure side





Outdoor unit side

| PURY-(E)P72T/

YNU

| ****



(HBC controller) CMB-WP108NU-AA

CMB-WP-1016NU-AA *2

| ø15.88 [5/8] (Brazing)| ø19.05 [3/4] (Brazing)| ø15.88 [5/8] (Brazing)

for each HBC controller

| ø19.05 [3/4] (Brazing)

for each HBC controller

PURY-(E)P96T/

YNU

| ø19.05 [3/4] (Brazing)| ø22.2 [7/8] (Brazing)| ø15.88 [5/8] (Brazing)

for each HBC controller

| ø19.05 [3/4] (Brazing)

for each HBC controller

PURY-(E)P120T/

YNU

| ø19.05 [3/4] (Brazing)| ø28.58 [1-1/8] (Brazing)| ø15.88 [5/8] (Brazing)

for each HBC controller

| ø19.05 [3/4] (Brazing)

for each HBC controller

PURY-(E)P144T/

YNU

| ø22.2 [7/8] (Brazing)| ø28.58 [1-1/8] (Brazing)| ø15.88 [5/8] (Brazing)

for each HBC controller

| ø19.05 [3/4] (Brazing)

for each HBC controller

PURY-(E)P168T/

YNU

| ø22.2 [7/8] (Brazing)| ø28.58 [1-1/8] (Brazing)| ø19.05 [3/4] (Brazing)

for each HBC controller

| ø22.2 [7/8] (Brazing)

for each HBC controller

  • A To outdoor unit
  • B End connection (brazing)
  • C Main-HBC controller
  • D Sub-HBC controller
  • E Indoor unit
  • F Branch joint (field supply)
  • G Up to three units for 1 branch hole; total capacity: below 30 (but in same mode, cooling/heating)

Note:

  • Be sure to use non-oxidative brazing.
    1. To connect multiple indoor units to a port
  • Maximum total capacity of connected indoor units: WL30
  • Maximum number of connectable indoor units: 3 units
  • Branch joints are field-supplied.
    1. PURY-(E)P-120T/YNU model or larger requires a connection of two main- HBC controllers in parallel.
  • For the connection with outdoor units other than those listed in the table, refer to the Databook of the HBC controller.  [Fig. 4.2.1]
  • A Main-HBC controller
  • B Twinning pipe (field supply)

(Unit: mm [in])

  Pipe size
HBC controller 1 HBC controller 2

Slope of twinning pipes (high-pressure side and low-pressure side)
When using twinning pipes on the high-pressure piping and the low-pressure piping, connect them horizontally.

If the slope exceeds the specified angle, it may cause lack of capacity.

Notes:

  • Have a fire extinguisher nearby before brazing work.
  • Provide no-smoking signs at the brazing workplace.
  • After pipe connection, be sure to check that there is no gas leakage, using a leak detector or soap-and-water solution.
  • Before brazing the refrigerant piping, always wrap the piping on the main body, and the thermal insulation piping, with damp cloths to prevent heat shrinkage and burning the thermal insulation tubing. Take care to ensure that the flame does not come into contact with the main body itself.
  • Do not use leak-detection additives.
  • Straight run of pipe connecting twinning pipe is 500 mm [19-11/16 in] or more.
  • Piping work shall be kept to a minimum.
  • The pipes shall be protected from physical damage.

Warning:
Do not mix anything other than the specified refrigerant (R410A) into the refrigerating cycle when installing or moving. Mixing air may cause the refrigerating cycle to reach abnormally high temperature, resulting in burst pipes.

Caution:
Cut the tip of the outdoor unit piping, remove the gas, and then remove the brazed cap.  [Fig. 4.2.2]

Insulating pipes
Be sure to add insulation work to piping by covering high-temperature pipe and low-temperature pipe separately with enough thickness heat-resistant polyethylene foam, so that no gap is observed in the joint between the HBC controller and insulating material, and insulating materials themselves. When insulation work is insufficient, there is a possibility of condensation. Pay special attention to insulation work in the ceiling plenum.  [Fig. 4.3.1]

  • A Locally procured insulating material for pipes
  • B Bind here using band or tape.
  • C Do not leave any opening.
  • D Lap margin: more than 40 mm [1-5/8 in]
  • E Insulating material (field supply)
  • F Unit side insulating material

Insulation materials for the pipes to be added on site must meet the following specifications:

Outdoor unit

-HBC controller

| High-pressure pipe| 10 mm [13/32 in] or more
---|---|---
Low-pressure pipe| 20 mm [13/16 in] or more
Temperature Resistance| 100°C [212°F] min.

  • Installation of pipes in a high-temperature high-humidity environment, such as the top floor of a building, may require the use of insulation materials thicker than the ones specified in the chart above.
  • When certain specifications presented by the client must be met, ensure that they also meet the specifications on the chart above.
  • The brazed connections must be covered with insulation, with its seam facing upward and fastened with the bands.

Additional refrigerant charge

Notes:

  • Charge refrigerant in a liquid state.
  • Charging refrigerant in the gaseous state will change the composition of the refrigerant and lead to a performance drop.
  • Do not use a charging cylinder when charging refrigerant.
  • The use of a charging cylinder may change the composition of the refrigerant and lead to a performance drop.
  • For the connection with outdoor units other than those listed in the table, refer to the Databook of the HBC controller.

The table below summarizes the factory-charged amount of refrigerant, the maximum amount of refrigerant to be added on site, and the maximum total amount of refrigerant in the system. The amount of refrigerant that is shown in the table below is factory-charged in the outdoor units. The amount necessary for extended piping is not included and needs to be added on site.

Unit model| Factory-charged

amount [kg (oz)]

---|---
PURY-P72T/YNU| 5.2 (184)
PURY-P96T/YNU| 8.0 (283)
PURY-P120T/YNU| 8.0 (283)
PURY-P144T/YNU| 10.8 (381)
PURY-P168T/YNU| 10.8 (381)
Unit model| Factory-charged

amount [kg (oz)]

---|---
PURY-EP72T/YNU| 5.2 (184)
PURY-EP96T/YNU| 8.0 (283)
PURY-EP120T/YNU| 8.0 (283)
PURY-EP144T/YNU| 10.8 (381)
PURY-EP168T/YNU| 10.8 (381)

The amount of refrigerant that is shown in the table below is the maximum amount to be added on site.

Unit model

| Maximum amount to be added [kg (oz)]
---|---
PURY-P72T/YNU| 21 (741)
PURY-P96T/YNU| 25.4 (896)
PURY-P120T/YNU| 25.4 (896)
PURY-P144T/YNU| 33.1 (1168)
PURY-P168T/YNU| 33.1 (1168)

Unit model

| Maximum amount to be added [kg (oz)]
---|---
PURY-EP72T/YNU| 21 (741)
PURY-EP96T/YNU| 25.4 (896)
PURY-EP120T/YNU| 25.4 (896)
PURY-EP144T/YNU| 33.1 (1168)
PURY-EP168T/YNU| 33.1 (1168)

Both refrigerant overcharge and undercharge will cause problems. Charge the system with the proper amount of refrigerant. Record the added refrigerant amount on the label attached to the control box panel for future servicing.

Calculation of the amount of additional refrigerant

  • The amount of refrigerant to be added depends on the size and the total length of the high-pressure piping and liquid piping.
  • Calculate the amount of refrigerant to be charged according to the formula below.
  • Round up the calculation result to the nearest 0.1 kg (0.1 oz).
  • The refrigerant does not need to be added for the indoor units in a Hybrid City Multi system.

(E)P72 to 168T/YNU (R410A refrigerant)

  1. Units “m” and “kg”

(2) Units “ft” and “oz”

  • When the piping length from the outdoor unit to the farthest HBC controller is 30.5 m (100 ft) or shorterMITSUBISHI-ELECTRIC-WT09757X01-Air-Conditioners-fig- \(14\)
  • Amount of refrigerant to be charged for single-module units
  • In the case all connected indoor unit models are Case 1, do Not add the refrigerant listed in table . Instead, add the following amount of refrigerant. Case 1: PEFY-WL06/24NMAU-A**
    • Add 20 oz per PEFY-WL06/24NMAU-A**.
  • When the piping length from the outdoor unit to the farthest HBC controller is longer than 30.5 m (100 ft)MITSUBISHI-ELECTRIC-WT09757X01-Air-Conditioners-fig- \(15\)
  • Amount of refrigerant to be charged for single-module units
  • In the case all connected indoor unit models are Case 1, add the following amount of refrigerant. Case 1: PEFY-WL06/24NMAU-A**
    • Add 20 oz per PEFY-WL06/24NMAU-A**.

Drain piping work

Drain piping work

  • Tilt the drain pan so that the water will flow toward the drain socket. [Fig. 4.5.1]
  1. Unscrew the two screws that are holding the side panel on the right side of the control box.
  2. Tilt the drain pan.
  3. Screw down the screws with the drain pan tilted.
  • Ensure that the drain piping is downward (sloped gradient of more than 1/100) to the outdoor (discharge) side. If it is impossible to take any downward pitch, use an optionally available drain-up mechanism to obtain a downward pitch of more than 1/100.

  • Ensure that any cross-wise drain piping is less than 20 m [65 ft]. If the drain piping is long, support it with metal brackets to prevent it from bending, warping, or vibrating.

  • Use a hard vinyl chloride pipe for drain piping.

  • Ensure that collected pipes are 10 cm [3-15/16 in] lower than the unit body’s drain port.

  • Do not provide any odor trap at the drain discharge port.

  • Put the end of the drain piping in a position where no odor is generated.

  • Do not put the end of the drain piping in any drain where ionic gases are generated.

  • When connecting the drain pipe to only one drain socket, use the drain socket at the bottom, and cover the top one. [Fig. 4.5.2]

  • Correct piping

  • × Wrong piping

  • A Insulation (9 mm [6/16 in] or more)

  • B Downward slope (1/100 or more)

  • C Support metal

  • K Air bleeder

  • L Raised

  • M Odor trap
    Grouped piping

  • D PVC TUBE

  • E Make it as large as possible. About 10 cm [3-15/16 in].

  • F Indoor unit

  • G Make the piping size large for grouped piping.

  • H Downward slope (1/100 or more)

  • I O.D. ø38 mm [1-8/16 in] PVC TUBE for grouped piping. (9 mm [6/16 in] or more insulation)

  • J HBC controller

  1. Insert the adapter (not supplied) into the drain port.
    • Apply wraps overlapping of sealing tape (2 times)
    • Torque the drain pan adapter to 2.5 Nm+/–0.5 [22 in-lb]
  2. Attach the drain pipe (PVC TUBE, not supplied). (Attach the pipe with glue.)
  3. Perform insulation work on the drain pipe (PVC TUBE) and on the socket (includ-ing elbow).
  4. Check the drainage.
  5. Attach the insulating material, and fix it with the band (not supplied) to insulate the drain port.
    • A HBC controller
    • B Tie band (not supplied)
    • C Drain socket NPT 3/4 in
    • D Adapter (not supplied)
    • E Drain pipe (not supplied)
    • F Insulating material (not supplied)

Discharge test
After completing drain piping work, open the HBC controller panel, and test drain discharge using a small amount of water. Also, check to see that there is no water leakage from the connections.

Insulating drain pipes
Provide sufficient insulation to the drain pipes just as for refrigerant pipes.

Caution:
Be sure to provide drain piping with heat insulation in order to prevent excess condensation. Without drain piping, water may leak from the unit causing damage to your property.

Connecting water pipework

Please observe the following precautions during installation.

Important notes on water pipework installation

  • The design pressure of the HBC controller water system is 0.6 MPa [87 psi].
  • Use water pipe-work with a design pressure of at least 1.0 MPa [145 psi].
  • When performing a water leak check, please do not allow the water pressure to go above 0.3 MPa [44 psi].
  • Perform a pressure test on the field-installed water pipes at a pressure equal to 1.5 times the design pressure. Before performing a pressure test, isolate the pipes from HBC controller and indoor units.
  • Please connect the water pipework of each indoor unit to the connect port on the HBC controller. Failure to do so will result in incorrect running.
  • Please list the indoor units on the naming plate in the HBC controller with addresses and end connection numbers.
  • Use the reverse-return method to insure proper pipe resistance to each unit.
  • Provide some joints and valves around inlet/outlet of each unit for easy maintenance, checkup, and replacement.
  • Install a suitable air vent on the water pipe. After flowing water through the pipe, vent any excess air.
  • Secure the pipes with metal fitting, positioning them in locations to protect pipes against breakage and bending.
  • Do not confuse the water intake and outlet piping especially when connecting the HBC controller and the Sub-HBC controller. (Error code 5102 will appear on the remote controller if a test run is performed with the pipe-work installed incorrectly (inlet connected to outlet and vice versa).)
  • This unit doesn’t include a heater to prevent freezing within tubes. If the water flow is stopped on low ambient, drain the water out.
  • The unused knockout holes should be closed and the refrigerant pipes, water pipes, power source and transmission wires access holes should be filled with putty.
  • Install water pipe so that the water flow rate will be maintained.
  • Wrap sealing tape as follows.
    • Wrap the joint with sealing tape following the direction of the threads (clock-wise), do not wrap the tape over the edge.
    • Overlap the sealing tape by two-thirds to three-fourths of its width on each turn. Press the tape with your fingers so that it is tight against each thread. 3 Do not wrap the 1.5th through 2nd farthest threads away from the pipe end.
  • Hold the pipe on the unit side in place with a spanner when installing the pipes or strainer. Tighten screws to a torque of 40 N·m.
  • If there is a risk of freezing, carry out a procedure to prevent it.
  • When connecting heat source unit water piping and on site water piping, apply liquid sealing material for water piping over the sealing tape before connection.
  • Please use copper or plastic pipes for the water circuit. Do not use steel or stainless steel pipework. Furthermore, when using copper pipe-work, use a non-oxidative brazing method. Oxidation of the pipe-work will reduce the pump life.
  • Add water pressure gauge to see if the water pressure in HBC controller is correct or not.
  • Be sure to braze the water pipes after covering a wet cloth to the insulation pipes of the units in order to prevent them from burning and shrinking by heat. (There are some plastic parts in HBC controller.)
  • Install the unit so that external force is not applied to the water pipes.
  • After filling the pipes with water, immediately perform debris removal operation and air vent operation.
  • If you use a hose for water supply, use a new hose-set.

Example of HBC controller installation [Fig. 5.1.1]

  • A Expansion vessel (field supply)
  • B Shutoff valve (field supply)
  • C Strainer (field supply)
  • D Pressure reducing valve (field supply)
  • E Water inlet
  • F Refrigerant pipes
  • G Drain pipe
  • H Pressure gauge (field supply)
  • I Check valve (field supply)

Note:
Connect the pipes to the water pipes according to the local regulations. [Fig. 5.1.2]

  • A Indoor unit connection
  • B Cutting point
  • C Cut the piping at the cutting point
  • D Field pipe connection (field supply)
  • E Field pipe
  • F Pipe connection (field supply)
  • G Indoor unit and Sub-HBC controller connecting port
  • H Water inlet (EXP. VESSEL)

Note:
Remove burr after cutting the piping to prevent entering the pipe connection. Prevent the particles that are generated during pipe cutting or cut edge treatment from entering the pipes. Check that there is no crack at the edge of the piping.

  • A HBC controller
  • B Sub-HBC controller
  • C To Sub-HBC controller (Hot water)
  • D From Sub-HBC controller (Hot water)
  • E To Sub-HBC controller (Cold water)
  • F From Sub-HBC controller (Cold water)

Water pipe insulation

  1. Connect the water pipes of each indoor unit to the same (correct) end connection numbers as indicated on the indoor unit connection section of each HBC controller. If connected to wrong end connection numbers, there will be no normal operation.

  2. List indoor unit model names in the name plate on the HBC controller control box (for identification purposes), and HBC controller end connection numbers and address numbers in the name plate on the indoor unit side.
    In case of using cover caps for unused end connections, please use dezincification resist-ant brass (DZR) (field supply). Not using the rubber end caps will lead to water leakage.

  3. Be sure to add insulation work to water piping by covering water pipework sepa-rately with enough thickness heat-resistant polyethylene, so that no gap is observed in the joint between indoor unit and insulating material, and insulating materials themselves. When insulation work is insufficient, there is a possibility of condensation, etc. Pay special attention to insulation work in the ceiling plenum.[Fig. 5.2.1]

    • A Locally procured insulating material for pipes
    • B Bind here using band or tape.
    • C Do not leave any opening.
    • D Lap margin: more than 40 mm [1-5/8 in]
    • E Insulating material (field supply)
    • F Unit side insulating material

Insulation materials for the pipes to be added on site must meet the following specifications:

HBC controller

-indoor unit

| 20 mm [13/16 in] or more
---|---
HBC controller

-Sub-HBC controller

| 20 mm [13/16 in] or more

  • This specification is based on copper for water piping. When using plastic pipework, choose a thickness based on the plastic pipe performance.
  • Installation of pipes in a high-temperature high-humidity environment, such as the top floor of a building, may require the use of insulation materials thicker than the ones specified in the chart above.
  • When certain specifications presented by the client must be met, ensure that they also meet the specifications on the chart above.

Expansion vessel

  • Install an expansion vessel to accommodate expanded water.
  • Please install expansion vessel at same height level of HBC controller. Expansion vessel selection criteria:
  • The water containment volume of the HBC controller and the indoor unit.

(Unit: L)

Unit model Water volume
HBC controller 10
PEFY-WL06NMAU

0.9

PEFY-WL08NMAU
PEFY-WL12NMAU
PEFY-WL15NMAU| 1.2
PEFY-WL18NMAU|

2.1

PEFY-WL24NMAU
PEFY-WL27NMAU
PEFY-WL30NMAU
PEFY-WL36NMAU| 2.7
PEFY-WL48NMAU| 3.7

  • For other indoor units, refer to the installation manual for each.
  • The maximum water temperature is 60°C [140°F].
  • The minimum water temperature is 5°C [41°F].
  • The circuit protection valve set pressure is 370-490kPa.
  • The circulation pump head pressure is 0.24MPa.
  • The design pressure of the expansion vessel is the charged water pressure (the reading of the pressure gauge).
  • Tank volume of expansion vessel is as follows:
    • Tank volume = ε × G/(1 – (Psupply + 0.1)/0.29) × 1.2
    • ε = The expansion coefficient of water (= 0.0171)
  • Please choose ε for using antifreeze solution on the type and temperature range used.
    • ε = Max density/Min density – 1
    • G [L] = (HBC controller [L] + Indoor unit [L] + Pipe [L]) × 1.1
    • Psupply: Water supply pressure [MPa]
  1. Leakproof the water pipework, valves and drain pipework. Leakproof all the way to, and include pipe ends so that condensation cannot enter the insulated pipe-work.
  2. Apply caulking around the ends of the insulation to prevent condensation getting between the pipework and insulation.
  3. Add a drain valve so that the unit and pipework can be drained.
  4. Ensure there are no gaps in the pipework insulation. Insulate the pipework right up to the unit.
  5. Ensure that the gradient of the drain pan pipework is such that discharge can only blow out.
  6. HBC controller water pipe connection sizes and pipe sizes. [Fig. 5.2.2]
Model name Connection size Pipe size
Water inlet Water outlet Water out
PEFY-WL06-18 NMAU-A ****

O.D. 22 mm

| ****

O.D. 22 mm

| I.D. ≥ 20 mm [13/16 in]| I.D. ≥ 20 mm [13/16 in]
PEFY-WL24-48 NMAU-A| I.D. ≥ 30 mm [1-3/16 in]| I.D. ≥ 30 mm [1-3/16 in]

  • For other indoor units, refer to the indoor unit installation manual.
  • The pipe diameter depends on the capacity of indoor units. Refer to the indoor unit installation manual for details.

[Fig. 5.2.3]

Total down-stream indoor unit capacity Pipe size between Main-HBC and Sub-HBC
WL06 – WL36 I.D. ≥ 20.0 mm
WL37 – WL72 I.D. ≥ 25.8 mm
WL73 – WL108 I.D. ≥ 30.0 mm
WL109 – WL144 I.D. ≥ 33.3 mm
WL145 – WL180 I.D. ≥ 36.2 mm
WL181 – WL200 I.D. ≥ 36.8 mm
  • A To outdoor unit
  • B End connection (brazing)
  • C Main-HBC controller
  • D Sub-HBC controller
  • E Indoor unit
  • F Branch joint (field supply)
  • G Up to three units for 1 branch hole; total capacity: below 30 (but in same mode, cooling/heating)
  • H Shutoff valve (field supply)
  • I Pressure control valve (field supply)
  • J Auto air vent valve (Highest point on the water pipe for each branch) (field supply)
  • K Water pipework
  • L Pump 1 circuit
  • M Pump 2 circuit

Note:

To connect multiple indoor units to a port

  • Maximum total capacity of connected indoor units: WL30
  • Maximum number of connectable indoor units: 3 units
  • Branch joints are field-supplied.
  • All the indoor units that are connected to the same port must be in the same group and perform the Thermo-ON/OFF operation simultaneously.
  • The room temperatures of all the indoor units in the group need to be monitored via the connected remote controller.
  • Selection of water piping Select the size according to the total capacity of indoor units to be installed down-stream.
  • Do not connect multiple indoor units to the same port when operating each of them in different modes (cooling, heating, stop, and thermo-OFF). The indoor units connected to the same port must be set to operate in the same mode. Set them to the same group to make them run/stop in the same mode all together. Alternatively, enable the thermo setting on the remote controller, or set the common thermostat (optional) to run/stop the units in the same mode based on the representative temperature.
  • When multiple indoor units are connected to a single port, install a pressure control valve in the pipe to equalize the pressure of all indoor units.

Connecting WL36 or 48 indoor units to an HBC controller
When connecting WL36 or 48 indoor units to an HBC controller, connect each unit to two sets of two ports on the HBC controller, using two junction pipes (Y-joints).

  • Connect an increaser (20A-to-32A) to the merged side of each junction pipe.
  • When the junction pipes are connected to 16 HBC controller ports, the branched sides of the junction pipes cannot be connected to the ports “4 and 5” “8 and 9” or “12 and 13” at the same time. (See Fig. A.)
  • When the junction pipes are connected to 8 HBC controller ports, the branched sides of the junction pipes cannot be connected to the ports “4 and 5” at the same time. (See Fig. B.)
  • When a WL36 or a 48 model indoor unit is connected to an HBC controller, the pipes that connect the unit to the same set of HBC controller ports cannot be branched out to connect additional units.

Maximum capacity of indoor units connectable to an HBC controller for obtaining the rated performance

  • An HBC controller has two pumps. Each pump can accommodate the capacity equivalent to WL67 indoor units.
  • When connecting the pipe to 16 HBC controller ports, make sure that the total capacity of the indoor units connected to ports “1 through 4 and 9 through 12” or “5 through 8 and 13 through 16” will not exceed WL67 and will be equal as much as possible. (See Fig. A.)
  • When connecting the pipe to 8 HBC controller ports, make sure that the total capacity of the indoor units connected to ports “1 through 4” or “5 through 8” will not exceed WL67 and will be equal as much as possible. (See Fig. B.)
    If the total capacity exceeds WL67, the performance will be degraded.

Please refer to the [Fig. 5.2.4] when connecting the water supply.  [Fig. 5.2.4]

  • A HBC controller
  • B Water pipe
  • C Pressure gauge (field supply)
  • D Check valve (field supply)
  • E Shutoff valve (field supply)
  • F Pressure reducing valve (field supply)
  • G Strainer (field supply)
  1. Use formula 0.1 MPa [15 psi] < 0.01 + 0.01 x A < 0.16 MPa [23 psi] for the supply pressure range to be used.
    (A: Head pressure (m) between the HBC controller and the highest indoor unit) If the supply pressure is greater than 0.16 MPa [23 psi], use a pressure reducing valve to keep the pressure within the range.
    If the head pressure is unknown, set it to 0.16 MPa [23 psi].

  2. Before performing a pressure test on the pipes in the water circuit, be sure to install a shutoff valve on the inlet/outlet water pipes of the indoor units. Also, install a strainer on the field-installed water pipes for easy operation and mainte-nance.

  3. Apply insulation to the indoor unit pipework, strainer, shutoff valve, and pressure reducing valve.

  4. Please do not use a corrosion inhibitor in the water system.

  5. When installing the HBC controller in an environment which may drop below 0°C [32°F], please add antifreeze solution (Propylene Glycol only) to the circulating water according to the local regulations.

Water treatment and quality control
To preserve water quality, use the closed type of water circuit. When the circulating water quality is poor, the water heat exchanger can develop scale, leading to a reduction in heat-exchange power and possible corrosion. Pay careful attention to water processing and water quality control when installing the water circulation system.

  • Removing of foreign objects or impurities within the pipes. During installation, make sure that foreign objects, such as welding fragments, sealant particles, or rust, do not enter the pipes.
  • Water Quality Processing
  1. Depending on the quality of the cold-temperature water used in the airconditioner, the copper piping of the heat exchanger may corrode. Regular water quality processing is recommended. If a water supply tank is installed, keep air contact to a minimum, and keep the level of dissolved oxygen in the water no higher than 1mg/ℓ.
  2. Water quality standard

Items

| Low to mid-range temperature water system| Tendency
---|---|---
Recirculating water [20<T<60°C] [68<T<140°F]|

Make-up water

|

Corrosive

|

Scale- forming

Standard items| pH (25°C) [77°F]| 7.0 ~ 8.0| 7.0 ~ 8.0| |
Electric conductivity        (mS/m) (25°C) [77°F]

(µ s/cm) (25°C) [77°F]

| 30 or less [300 or less]| 30 or less [300 or less]| |
Chloride ion                              (mg Cl-/ℓ)| 50 or less| 50 or less| |
Sulfate ion                             (mg SO42-/ℓ)| 50 or less| 50 or less| |
Acid consumption (pH4.8)

(mg CaCO3/ℓ)

| 50 or less| 50 or less|  |
Total hardness                       (mg CaCO3/ℓ)| 70 or less| 70 or less|  |
Calcium hardness                   (mg CaCO3/ℓ)| 50 or less| 50 or less|  |
Ionic silica                              (mg SiO2/ℓ)| 30 or less| 30 or less| |
Reference items| Iron                                        (mg Fe/ℓ)| 1.0 or less| 0.3 or less| |
Copper                                    (mg Cu/ℓ)| 1.0 or less| 0.1 or less| |
Sulfide ion                                (mg S2-/ℓ)| not to be detected| not to be detected| |

Ammonium ion                       (mg NH +/ℓ) 4

| 0.3 or less| 0.1 or less| |
Residual chlorine                          (mg Cl/ℓ)| 0.25 or less| 0.3 or less| |
Free carbon dioxide                    (mg CO2/ℓ)| 0.4 or less| 4.0 or less| |
Ryzner stability index| 6.0 ~ 7.0| –| |

  • Reference: Guideline of Water Quality for Refrigeration and Air Conditioning Equipment. (JRA GL02E-1994)
  1. Consult with a specialist about water quality control methods and calculations before using anti-corrosive solutions.

Electrical work

  • Consult all related regulations and power companies beforehand.

Warning:
Electrical work should be handled by qualified electrical engineers in accordance with all related regulations and attached instruction manuals. Special circuits should also be used. If there is a lack of power capacity or a deficiency in electrical work, it may cause a risk of electric shock or fire.

Open knockout holes.
(Recommend to use a screwdriver or the like for this work.)

Connect all wires securely.
Fix power source wiring to control box by using buffer bushing for tensile force. (Conduit or the like.) Connect transmission wiring to transmission terminal bed through the knockout hole of control box using ordinary bushing. [Fig. 6.0.1]

MITSUBISHI-ELECTRIC-WT09757X01-Air-Conditioners-fig-
\(27\)

  • CMB-WP108NU-AA,CMB-WP1016NU-AA
  • CMB-WP108NU-AB, CMB-WP1016NU-AB
  • A Control box
  • B Knockout hole
  • C Remove
  • D Power source wiring
  • E Use conduit to keep the weight of the cable and external force from being applied to the power supply terminal connector.
  • F Transmission wiring
  • G Use ordinary bushing
  • H Clip cables here
  • I Side frame
  • J Knockout hole (for power source wiring)
  • K Conduit

Never connect the power cable to the terminal board for control cables. (Otherwise it may be broken.) Be sure to wire between the control wire terminal boards for indoor unit, outdoor unit and HBC controller/Sub-HBC controller.

  • Use non-polarized 2-wire as transmission cables.
  • Use 2-core shielding cables (CVVS, CPEVS) of more than 1.25 mm2 [AWG 16] in diameter as transmission cables.

The switch capacity of the main power to HBC controller/Sub-HBC controllers and the wire size are as follows:

Switch (A) Molded case circuit breaker Earth leakage breaker Wire size
Capacity Fuse
16 16 20 A 20 A 30 mA

0.1 s or less

| 1.5 mm2 [AWG 15]

  • For other detailed information, refer to the outdoor unit installation manual.
  • Power supply cords of appliances shall not be lighter than design 245 IEC 53 or 227 IEC 53.
  • A switch with at least 3 mm [1/8 in] contact separation in each pole shall be provided by the Air conditioner installation that should be in accordance with local and national codes.

Caution:

  • Do not use anything other than the correct capacity fuse and breaker. Using fuse, conductor or copper wire with too large capacity may cause a risk of malfunction or fire.
  • Ensure that the outdoor units are put to the ground. Do not connect the earth cable to any gas pipe, water pipe, lightening rod or telephone earth cable. Incomplete grounding may cause a risk of electric shock.

Electrical characteristics

Model HBC controller Pump motor
Hz Volts MCA (A)
CMB-WP108NU-AA 60 208/230 V
CMB-WP1016NU-AA 60 208/230 V
CMB-WP108NU-AB 60 208/230 V
CMB-WP1016NU-AB 60 208/230 V

Setting addresses and operating units

The address switch of each HBC controller/Sub-HBC controller is set to “000” when shipped from the factory.

  • Set the address switch to an address that equals the lowest address of the indoor units that are connected to the HBC controller/Sub-HBC controller plus 50.
  • Assign the HBC controller address that equals the lowest address of the indoor units that are connected to the HBC controller/Sub-HBC controller plus 50. However, if the address overlaps any other units’ addresses, assign the address that equals the next lowest address plus 50.
  • Please refer to the outdoor unit installation manual.

Test run

Before commencing a test run please check the following:

  • After installing, piping and wiring the indoor units and HBC controllers, check to see again that there is no refrigerant leakage, water leakage, the indoor unit inlet and outlet piped backwards, and no slack on power and control cables.
  • Use a 500 V tester to check that there is an insulation resistance of more than 1.0 MΩ between the power terminal block and the ground. If it is less than 1.0 MΩ, do not operate the unit.
  • When water has been supplied to the water pipework, purge the system of air. The details of air purging can be found separately in the water circuit maintenance manual.

Caution:

  • Never measure the insulation resistance of the terminal block for any control cables.
  • Incomplete purging of the air in the system, closing of the valves upstream or down stream of the pump etc. may cause the pump to operate with no water flow and thus lead to pump failure.
  • Ensure that the power is off when replacing a pump. Do not remove or attach the pump connector with the power on. Otherwise pump will break. After turning off the power, wait 10 minutes before commencing work.

Instructions for debris removal operation
This operation removes the debris that may have been introduced during installation from the water circuit.

Perform this operation after completion of water- and refrigerant-piping work, air tightness test, evacuation of refrigerant circuits, refrigerant charging, and electrical work.

  1. Preparation for debris removal operation
  2. Set DIP SW 5-1 (valve opening when stopped), DIP SW 5-2 (nullification of drain over-flow error for 9 hours) from off to on.
  3. Turn on the breaker, and then open the air vent valves on the HBC controller and the indoor units. Refer to the Installation Manual for the location of air vent valves. (If there are air vent valves on the field-installed pipes, open the valves as well.)
  4. Supply water from the suction pipe on the HBC controller.MITSUBISHI-ELECTRIC-WT09757X01-Air-Conditioners-fig- \(29\)
  5. Check that water comes from each air vent valve, and perform the debris removal operation.
  6. Debris removal operation
  7. If there are a large amount of debris in the water in the field-installed pipes, set DIPSW4-1 from OFF to ON.(Refer to the flowchart for debris removal operation for details.) Perform the debris removal operation. (Each air vent valve should stay open.)
  8. Forty minutes after the completion of debris removal operation, the LED will indicate “Air0.” The LED indication will change to “Air1,” “Air2,” and “AirE” in order. Then, the water pump will stop.
  9. Stop the water supply, and check that no water is coming out of the air vent valves. Then, set the dipswitch 4-1 from ON to OFF.
  10. Set DIP SW4-6 to on, and switch off the HBC controller. Open the air-vent valve and the water-vent valve. Slowly open the strainer closest to the water supply to the HBC controller. (Note that if it is opened fast, water may blast out.) Remove the strainer, clean its inside, and refit it.MITSUBISHI-ELECTRIC-WT09757X01-Air-Conditioners-fig- \(31\)
  11. Slowly open the other strainer which is the furthest from the water supply.(After the cleaning, set DIPSW4-6 to OFF.)
  12. Make sure the strainers are re-installed.MITSUBISHI-ELECTRIC-WT09757X01-Air-Conditioners-fig- \(36\)
  13. End processing
    Set the dipswitches 5-1 and 5-2 to OFF after completion of debris removal operation.

Instructions for the air vent operation
This operation removes the air that remains after water is supplied to the water circuit. Perform this operation after completion of water- and refrigerant-piping work, air tightness test, evacuation of refrigerant circuits, and refrigerant charging (and debris removal, if performed).

When main-HBC controllers are connected in parallel, please do not operate them at the same time.

  1. Preparation for the air vent operation
  2. Set DIP SW 5-1 (valve opening when stopped), DIP SW 5-2 (nullification of drain over-flow error for 9 hours) from off to on.
  3. Turn on the breaker, and then open the air vent valves on the HBC controller and the indoor units. Refer to the Installation Manual for the location of air vent valves. (If there are air vent valves on the field-installed pipes, open the valves as well.)
  4. Supply water from the suction pipe on the HBC controller.MITSUBISHI-ELECTRIC-WT09757X01-Air-Conditioners-fig- \(33\)
  5. Check that water comes from each air vent valve, and perform the air vent operation.
  6. Air vent operation
  7. Set DIPSW4-3 from OFF to ON.
  8. The LED will indicate “Air1” “Air2” “Air3” “Air4” and “AirE” in order over a period of up to 140~380 minutes, and after 140~380 minutes have passed, the water pump will stop.
  9. Set the dipswitch 4-3 from ON to OFF.
  10. Close the all air vent valves.
  11. Stop the water supply.
  12. Checking for the presence of residual air
  13. Set DIPSW4-5 from OFF to ON, and operate the water pump.
  14. If there is residual air in the circuit, it will be noisy. Check for water leaks from the pipe, and then, perform the air vent operation again.MITSUBISHI-ELECTRIC-WT09757X01-Air-Conditioners-fig- \(35\)
  15. End processing
    Set the dipswitches 5-1 and 5-2 to OFF after completion of air vent operation.

Please be sure to put the contact address/telephone number on this manual before handing it to the customer.

MITSUBISHI ELECTRIC CORPORATION

HEAD OFFICE:
TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN.

Printed in Japan.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Mitsubishi Electric User Manuals

Related Manuals