nVent HOFFMAN Operator Adapter GEV Instruction Manual
- June 12, 2024
- nVent HOFFMAN
Table of Contents
OPERATOR ADAPTER GEV
Installation Instructions for General Electric Types STDA Variable Depth
Operating Mechanisms
(For parts list, see Page 2)
Operator Adapter GEV
| |
---|---|---
For floor-mounted enclosures with the disconnect on the right flange| For one-
through six-door free-standing enclosures with the disconnect the the right
flange| For floor-mounted enclosures with the disconnect on the centerpost
WARNING
The functions, fits and clearances of the installation described hereon are
calculated from information supplied by the manufacturers of the equipment to
be installed. Be certain to check the function, fits and clearances of all
equipment both before and after installation to assure that it operates
properly and safely and meets all applicable codes, standards and regulations.
In the event the completed installation does not function properly or fails to
meet any such codes, standards or regulations, do not attempt to make
alterations or operate the equipment. Report such facts immediately to:
Hoffman Customer Service
2100 Hoffman Way
Anoka, MN 55303
763.422.2211
http://hoffman.nvent.com/contact-us
Parts List
Operator Adapter, Catalog Number GEV, for General Electric Disconnects
Item No. | Description | Part No. | Qty. |
---|---|---|---|
1 | ADAPTER PLATE, VARIABLE DEPTH | 89112746 | 1 |
2 | PLATE GASKET | 89109613 | 1 |
3 | SCREW, 1/4-20X1/2 PAN HEAD | 99401031 | 4 |
4 | SLIDE ARM | 26250001 | 1 |
5 | SHOULDER COLLAR | 26149001 | 1 |
6 | SCREW, 1/4-20X7/8, HEX HEAD | 99401030 | 1 |
7 | LOCKWASHER, 1/4 SPRING | 99401318 | 1 |
8 | WASHER, FLAT | 22101003 | 2 |
9 | LOCKWASHER, 1/4 INTERNAL TEETH | 99401300 | 2 |
10 | NUT, 1/4-20 HEX | 99401406 | 2 |
11 | DOOR CATCH | 23101002 | 1 |
12 | SCREW, 10-32X3/8 PAN HEAD | 99401007 | 2 |
13 | LOCKWASHER, #10 INTERNAL TEETH | 99401307 | 2 |
14 | NYLON WASHER | 26132003 | 4 |
15 | INSTALLATION INSTRUCTIONS | 89114664 | 1 |
INTRODUCTION
This installation instruction is for General Electric (variable depth) mechanisms. These mechanisms are for disconnect switches and circuit breakers mounted in Hoffman wo-door, floor-mounted, enclosures with the disconnect on the right flange.
INSTALLATION STEPS
Step 1
Install operating plate (item1) and plate gasket (item 2) on the inside of the
enclosure, behind the rectangular opening provided. Gasket side with PSA
should be attached to the adapter plate. Secure in place with four screws
(item 3) and four nylon washers (item 14).
Step 2
Assemble the General Electric G.E. STDA operating handle to the mounting plate
which was installed in the enclosure in step 1. Omit cap screw and lock washer
which fits into bottom hole of G.E. operating andle. Also omit G.E. stiffening
bracket, which is not
required.
Step 3
Install the slide arm (item 4) over the interlock part of the G.E. operating
handle as shown. Note the the notch in the slide arm is positioned toward the
door opening. Place the smaller diameter end of the shoulder collar (item 5)
through the oval slot in the slide arm. Install long cap screw (item 6) with
lock washer (item 7) through shoulder collar into the bottom mounting hole of
the G.E. operating handle and tighten. The slide arm should move up and down
smoothly. Install G.E. interlock blade per G.E. instructions.
Step 4
Attach the bottom of the slide arm (item 4) to the offset arm of the lock
release mechanism. Use two flat washer (item 8), two lock washers (item 9),
and two hex nuts (item 10). Do not tighten until parts are adjusted (see step
5B).
Step 5
The handle safety lock release mechanism is adjustable.
(A) Check the adjustment of the factory installed roller bracket. The door
latch should hit against the latch stop portion of the roller bracket when the
door is closed and latched. Adjust up or down if necessary. The attached
mechanism will then provide the necessary up−down motion required to operate
the release mechanism in the G.E. operating handle.
(B) Adjust the length of the slide arm assembly. With proper adjustment of the
slide arm, the safety lock (in G.E. opating handle) should release just before
the master door is fully latched. Lengthen slide arm if safety lock releases
too soon. Shorten slide arm if safety lock releases too late.
Step 6
Attach the door catch (item 11), provided by Hoffman, to the tapped spacer on
the door using the bottom set of mounting holes. Use two screws (item 12) and
lock washers (item 13). The door catch prevents the door from being opened
when the G.E. operating handle is in the “ON” position.
Step 7
Drill and tap holes in panel per General Electric instructions. See General
Electric instructions for locating holes for fuse blocks for 200 AMP switches.
Step 8
Install panel in enclosure.
Step 9
Mount disconnect switch or circuit breaker and operating mechanism on panel
using General Electric instructions and parts. Attach G.E. handle return
spring between drive link on G.E. operating handle and hole provided in
Hoffman adapter plate as shown.
For Floor-Mounted, Two-Door Enclosures with Disconnect on Right Flange
INTRODUCTION
This installation instruction is for General Electric (variable depth)
mechanisms. These mechanisms are for disconnect switches and circuit breakers
mounted in Hoffman one through six door, free−standing enclosures with the
disconnect on the right flange.
INSTALLATION STEPS
Step 1
Install adapter plate (item 1) and plate gasket (item 2) on the inside of the
enclosure, behind the rectangular opening provided. Gasket side with PSA
should be attached to adapter plate. Secure in place with four screws (item 3)
and four nylon washers (item14).
Step 2
Assemble the G.E. STDA operating handle to the mounting plate which was
installed the enclosure in tep 1. Omit cap screw and lock washer which fits
into bottom hole of G.E. operating handle. Also omit G.E. stiffening bracket
which is not required.
Step 3
Install the slide arm (item 4) over the interlock part of the G.E. operating
handle as shown. Note that he notch in the slide arm is positioned toward the
door opening. Place the smaller diameter end of the shoulder collar (item 5)
through the oval slot in the slide arm. Install long cap screw (item 6) with
lock washer (item 7) through shoulder collar into the bottom mounting hole of
the G.E. operating handle and tighten. The slide arm should move up and down
smoothly. Install G.E. interlock blade per G.E. instructions
Step 4
Attach the bottom of the slide arm (item 4) to the offset arm of the lock
release mechanism. Use two flat washers (item 8), two lock washers (item 9),
and two hex nuts (item 10). Do not tighten until parts are adjusted (see step
5B)
Step 5
The handle safety lock release mechanism is adjustable in two places.
A) Check the adjustment of the factory installed roller bracket. The door
latch should hit against the latch stop portion of the roller bracket when the
door is closed and latched. Adjust up or down if necessary. The attached
mechanism will then provide the necessary up−down motion required to operate
the release mechanism in the G.E. operating handle.
B) Adjust the length of the slide arm assembly. With proper adjustment of the
slide arm, the safety lock (in G.E. operating handle) should release just
before the master door is fully latched. Lengthen slide arm if safety lock
releases too soon. Shorten slide arm if safety lock releases too late.
Step 6
Attach the door catch (item 11) provided by Hoffman to the tapped spacer on
the door using the bottom et of mounting holes. Use two screws (item 12) and
lockwashers (item 13). The door catch prevents the door from being opened when
the G.E. operating handle is in the “ON” position.
Step 7
Drill and tap holes in panel per General Electric instructions. See General
Electric instructions for locating holes for fuse blocks for 200 AMP.
switches.
Step 8
Install panel in enclosure.
Step 9
Mount disconnect switch or circuit breaker and operating mechanism on panel
using General Electric instructions and parts. Install and adjust G.E. drive
rod per G.E. instructions. Attach G.E. handle return spring between drive link
on G.E. operating handle and hole provided in Hoffman adapter plate as shown.
INTRODUCTION
This installation instruction is for General Electric variable depth)
mechanisms. These mechanisms are for disconnect switches and circuit breakers
mounted in Hoffman two door, floor−mounted enclosures with the disconnect on
the center post.
INSTALLATION STEPS
Step 1
Install adapter plate (item 1) and plate gasket (item 2) on the inside of the
enclosure, behind the rectangular opening provided in the center post. Gasket
side with PSA should be attached to the adapter plate. Secure in place with
four screws (item 3), and four nylon washers (item14).
Step 2
Assemble the G.E. type STDA operating handle to the mounting plate which was
installed in the enclosure in step1. Omit cap screw and lock washer which fits
into bottom hole of G.E. operating handle. Also omit G.E. stiffening bracket
which is not required. Step 3
Cut 2 1/2 inches off bottom end of slide arm (item 4). (bottom end of slide
arm has rectangular holes only)
Step 4
Install the slide arm (item 4) over the interlock part of the G.E. operating
handle as shown. Note that the otch in the slide arm is positioned toward the
door opening. Place the smaller diameter end of the shoulder collar (item 5)
through the oval slot in the slide arm. Install long cap screw (item 6) with
lock washer (item 7) through shoulder collar into the bottom mounting hole of
the G.E. operating handle and tighten. The slide arm should move up and down
smoothly. Install G.E. interlock blade per G.E. instructions.
Step 5
Attach the bottom of the slide arm (item 4) to the offset arm as shown. Use
two flat washers (item 8), two lock washers (item 9), and two hex nuts (item
10). Do not tighten until parts are adjusted.
Step 6
Adjust the length of the slide arm assembly. With proper adjustment of the
slide arm, the safety lock (in G.E. operating handle) should release just
before the master door is fully latched. Lengthen slide arm if safety lock
releases too soon. Shorten slide arm if safety lock releases too late.
Step 7
Attach the door catch (item 11) provided by Hoffman to the tapped space on the
door using the bottom set of mounting holes. Use two screws (item 12) and two
lock washers (item 13). The door catch prevents the door from being opened
when the G.E. operating handle is in the “ON” position.
Step 8
Drill and tap holes in panel per General Electric instructions. See General
Electric instructions for locating holes for fuse blocks for 200 AMP.
switches.
Step 9
Install panel on collar studs in enclosure.
Step 10
Mount disconnect switch or circuit breaker and operating mechanism on panel
using General Electric instructions and parts. Install and adjust G.E. drive
rod per G.E. instructions. Attach G.E. handle return spring between drive link
on G.E. operating handle and hole provided in Hoffman adapter plate as shown.
- NOTE: An optional General Electric flange stiffener kit (catalog number TDSR) is recommended when General Electric type STDA devices are installed in 72.12 inch high enclosures with operating handle mounted on centerpost. Use with TDOM1,2,3 operating mechanisms.