Product Information
50 AMP Inlet
The 50 AMP Inlet is a device used for connecting electrical power to a
portable generator or other power source. It is designed to provide a safe and
secure connection for transferring power to your home or transfer switch.
Installation Instructions:
- Remove the wire insulation approximately 5/8″ from the end of the wire.
- Connect the wires to the inlet box plug.
- Secure the wires with the fastener using 20 pounds of torque.
- Connect the red 125 Volt leg to the terminal marked X.
- Connect the black 125 Volt leg to the terminal marked Y.
- Connect the white wire to the terminal marked W.
- Connect your home/transfer switch ground by stacking it on our ground pole.
Please ensure that all connections are secure and properly tightened. Improper installation may result in electrical hazards or damage to the product.
Still Have Questions?
If you have any questions or need further assistance, please contact our
Sales Engineer.
- Email: info@acconnectors.com
- Phone : 414-434-2220
- Text : 414-323-3240
- Website : www.ACWORKS.com
50 AMP INLET – INSTALLATION INSTRUCTIONS
IMPORTANT
-
Installation of your AC WORKS® brand temporary power inlet box and associated wiring must be performed by a licensed electrician in compliance with all applicable codes.
Mount the temporary power inlet box in a suitable loca?on using the holes provided in your AC WORKS® brand inlet box packaging. All wiring methods and materials must conform to NEMA prac?ces. Route the conduit or cable through one of the provided knockouts in the inlet box. Route the cable or conduit to the junc?on box. All conductors are to be at least 8 AWG for 40 Amp and 6 AWG for 50 Amp. Include a ground wire of the same gauge if not using conduit. -
Remove the wire insula?on approximately 5/8’’ from the end of the wire. Connect the wires to the inlet box plug and secure with the fastener using 20 pounds of torque.
-
Connect the red 125 Volt leg to the terminal marked X.
-
Connect the black 125 Volt leg to the terminal marked Y.
-
Connect the white wire to the terminal marked W.
-
Connect your home/transfer switch ground by stacking on our ground pole.