TF43 Immersion Temperature Sensor
|
---|---
Operating Instructions, Mounting & Installation
Immersion ⁄ screw-in ⁄ duct temperature sensor with passive output
High-performance encapsulation against vibration, mechanical stress and
humidity
S+S REGELTECHNIK GMBH THURN-UND-TAXIS-STR. 22 90411 NÜRNBERG ⁄ GERMANY
FON +49 (0) 911 ⁄ 5 19 47-0
mail@SplusS.de
www.SplusS.de
Basic device with accessories
THERMASGARD®TF 43 ⁄ TF 65
Patented quality product (Immersion sensor patent no. DE 10 2012 017 500.0)
THERMASGARD® TF43 is a resistance thermometer with a passive output, housing
made from impact-resistant plastic with snap-on lid, and straight protective
tube. THERMASGARD® TF65 is a resistance thermometer with a passive output,
housing made from impact-resistant plastic with quick-locking screws, and
straight protective tube. These immersion ⁄ screw-in ⁄ duct temperature
sensors are electric contact thermometers for temperature measurement in
liquids and gases, which are installed for example in piping systems and
vessels. For aggressive media, stainless steel immersion sleeves must be used.
Applications of these temperature sensors in piping systems, in heating
technology, in storage tanks, in district heating compact stations, in hot and
cold-water systems, in oil and lubricant circulation systems, in mechanical,
apparatus and plant engineering as well as in the entire industrial sector.
| |
---|---|---
TECHNICAL DATA
Measuring range: | –30…+150 °C (Tmax NTC = +150 °C, Tmax LM235Z = +125 °C) |
---|---|
Sensors ⁄ output: | see table, passive (Perfect Sensor Protection) |
(optional also with two sensors)
Connection type:| 2-wire connection (4-wire connection on PT100 / PT1000A,
optional on other sensors)
Testing current:| < 0.6 mA (Pt1000)
< 1.0 mA (Pt100)
< 0.3 mA (Ni1000, Ni1000 TK5000)
< 2.0 mW (NTC xx)
400 μA…5 mA (LM235Z)
Insulating resistance:| ≥ 100 MΩ, at +20 °C (500 V DC)
Ambient temperature:| –20…+100 °C
Housing:| plastic, UV-resistant, material polyamide, 30 % glass-globe
reinforced, colour traffic white (similar to RAL 9016) TF 43 with snap-on lid
TF 65 with quick-locking screws (slotted ⁄ Phillips head combination)
Housing dimensions:| 72 x 64 x 37.8 mm (Tyr 1 ⁄ Tyr 01)
Cable connection:| cable gland, plastic (M 16 x 1.5; with strain relief,
exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Electrical connection:| 0.14 – 1.5 mm², via terminal screws
Protective tube:| stainless steel, V4A (1.4571), Ø = 6 mm, inserted length
(EL) = 50 – 400 mm (see table)
Permissible humidity:| < 95 % r. H., non-precipitating air
Protection class:| III (according to EN 60 730)
Protection type:| TF 43 IP 54 (according to EN 60 529) Housing tested,
TÜV SÜD, Report No. 713160960A (Tyr 01)
TF 65 IP 67 (according to EN 60 529) Housing tested, TÜV SÜD, Report
No. 713139052 (Tyr 1)
- Housing in the built-in state
ACCESSORIES
MF – 15 – K| Mounting flange, plastic, 56.8 x 84.3 mm, Ø = 15.2 mm tube gland, Tmax= +100 °C
TH 08 – ms ⁄ xx| Immersion sleeve, brass, nickel-plated, Ø = 8 mm, Tmax= +150 °C, pmax= 10 bar
TH 08 – VA ⁄ xx| Immersion sleeve, stainless steel, V4A (1.4571), Ø = 8 mm, Tmax= +600 °C, pmax= 40 bar
TH 08 – VA ⁄ xx ⁄ 90| Immersion sleeve, stainless steel, V4A (1.4571), with neck tube (90 mm), Ø = 8 mm, Tmax= +600 °C, pmax= 40 bar
Type ⁄ WG03| Sensor ⁄ Output
---|---
TF 43 ⁄ TF 65| other sensors on request
TF xx PT100 xx MM| Pt100 (according to DIN EN 60 751, class B)
TF xx PT1000 xx MM| Pt1000 (according to DIN EN 60 751, class B)
TF xx PT1000A xx MM| Pt1000 (according to VDI / VDE 3512, class A-TGA)
TF xx NI1000 xx MM| Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm ⁄ K)
TF xx NITK xx MM| Ni1000 TK5000 (TCR = 5000 ppm ⁄ K), LG – Ni1000
TF xx LM234Z xx MM| LM235Z (TCR = 10 mV ⁄ K; 2.73 V at O °C), KP10
TF xx NTC1,8K xx MM| NTC 1.8 K
TF xx NTC10K xx MM| NTC 10 K
TF xx NTC20K xx MM| NTC 20 K
Inserted Length:| xx MM = 50 mm, 100 mm, 150 mm, 200 mm, 250 mm, 300 mm, 350 mm, 400 mm
General notes
Measuring principle of HVAC temperature sensors in general:
The measuring principle of temperature sensors is based on an internal sensor
that outputs a temperature-dependent resistance signal.
The type of the internal sensor determines the output signal. The following
active ⁄ passive temperature sensors are distinguished:
a) Pt 100 measuring resistor (according to DIN EN 60 751)
b) Pt 1000 measuring resistor (according to DIN EN 60751)
c) Ni 1000 measuring resistor (according to DIN EN 43 760, TCR = 6180 ppm ⁄ K)
d) Ni 1000_TK 5000 measuring resistor (TCR = 5000 ppm ⁄ K)
e) LM235Z, semiconductor IC (10 mV ⁄ K, 2.73 V ⁄ °C). Ensure correct polarity
- ⁄– when connecting!
f) NTC (according to DIN 44070)
g) PTC
h) KTY silicon temperature sensors
The most important resistance characteristics are shown on the last page of these operating instructions. According to their characteristics, individual temperature sensors exhibit different slopes in the range between 0 °C and +100 °C (TK value). Maximum-possible measuring ranges also vary from sensor to sensor (for some examples to this see under technical data).
Design of HVAC temperature sensors in general:
Sensors are distinguished by shape type as follows: surface-contacting
sensors, cable temperature sensors, and housing-type and built-in temperature
sensors.
- On surface-contacting sensors, the temperature sensor has at least one contact area that must be brought in contact, e.g. with the surface of radiators or pipes. If the contact area is not positioned correctly relative to the surface to be measured, significant temperature measurement errors may occur. Good contact area and temperature conduction must be ensured, dirt and unevenness must be avoided, and heat-conductive paste is to be used where necessary.
- On cable temperature sensors, the temperature sensor is installed inside a sensor sleeve, from which a connecting cable is leading out. In addition to the standard insulating materials PVC, silicone, and fiberglass with stainless steel texture, other versions are also available that may allow a wider range of application.
- On housing-type sensors, the temperature sensor is embedded in a respective housing. Different designs of housing are available, e.g. with an external sensor sleeve (see outside temperature sensor ATF2). Housing-type sensors are normally distinguished into in-wall (FSTF) and on-wall (RTF, ATF) types and indoor and wet room versions. Connection terminals are placed on a plate inside the connecting housing.
- Duct and built-in temperature sensors are distinguished into temperature sensors with interchangeable measuring insert and without interchangeable measuring insert. Connection parts are placed inside a connecting head. Standard process connection for immersion sensors is a pipe thread (sizes in inches) and a mounting flange for duct sensors. However, it may be designed differently. When a built-in sensor has a neck tube, the application range is usually somewhat wider since ascending heat cannot flow directly and immediately into the connecting head. This is to be noted especially when transmitters are installed. The temperature sensor in built-in sensors is always placed inside the front part of the protective tube. On temperature sensors with short reaction times, protective tubes are stepped.
Note!
Select immersion depth for built-in sensors so that the error caused by heat
dissipation stays within the admissible error margins. A standard value is: 10
x diameter of protection tube + sensor length. In connection with housing-type
sensors, particularly with outdoor sensors, please consider the influence of
thermal radiation. For that purpose, a sunshade and radiation protector SS-02
can be attached. If the sensor is used in refrigeration circuits, it must be
insulated together with the housing to reduce the temperature potential
between the device and the medium to a minimum and thus prevent condensation
damage.
Maximum thermal load on components:
On principle, all temperature sensors shall be protected against unacceptable
overheating!
Standard values for individual components and materials selected are shown for
operation under neutral atmos phere and otherwise normal conditions (see table
to the right).
For combinations of different insulating materials, the lowest temperature
limit shall always apply.
Component ………………………………………………………………. max. thermal load
Connecting cable
PVC, normal ………………………………………………………………………………..+70 ° C
PVC, heat-stabilized ……………………………………………………………………. +105 °C
Silicone ……………………………………………………………………………………… +180 °C
PTFE ………………………………………………………………………………………….+200 °C
Fibreglass insulation with stainless steel texture …………………………….+400 °C
Housing ⁄ Sensor
see table “Technical Data”
Resistance characteristics of passive temperature sensors (see last page)
In order to avoid damages ⁄ errors, preferably shielded cables are to be used.
Laying measuring cables parallel with current-carrying cables must in any case
be avoided. EMC directives shall be observed!
These instruments must be installed by authorised specialists only!
Limiting deviation according to classes:
Tolerances at 0 °C:
Platinum sensors (Pt100, Pt1000):
DIN EN 60751, class B ……………………………………………………………… ± 0.3 K
1 ⁄ 3 DIN EN 60751, class B ………………………………………………………..± 0.1 K
Nickel sensors:
NI1000 DIN EN 43760, class B …………………………………………………….. ± 0.4 K
NI1000 1 ⁄ 2 DIN EN 43760, class B …………………………………………….. ± 0.2 K
NI1000 TK5000 ……………………………………………………………………….. ± 0.4 K
ATTENTION, NOTE ! Testing current influences the thermometer‘s measuring
accuracy due to intrinsic heating and therefore, should never be greater than
as specified below:
Sensor current, maximum …………………………………………. I max
Pt1000 (thin-layer) …………………………………………………………………… < 0.6 mA
Pt100 (thin-layer) …………………………………………………………………… < 1.0 mA
Ni1000 (DIN), Ni1000 TK5000 ………………………………………………. < 0.3 mA
NTC xx ………………………………………………………………………………………… < 2 mW
LM235Z …………………………………………………………………………… 400 µ A … 5 mA
KTY 81 – 210 ………………………………………………………………………………….< 2 mA
Installation and Commissioning
Devices are to be connected under dead-voltage condition. Devices must only be
connected to safety extra-low voltage. Consequential damages caused by a fault
in this device are excluded from warranty or liability. These devices must be
installed and commissioned by authorised specialists. The technical data and
connecting conditions shown on the device labels and in the mounting and
operating instructions delivered together with the device are exclusively
valid. Deviations from the catalogue representation are not explicitly
mentioned and are possible in terms of technical progress and continuous
improvement of our pro ducts. In case of any modifications made by the user,
all warranty claims are forfeited. Operating this device close to other
devices that do not comply with EMC directives may influence functionality.
This device must not be used for monitoring applications, which serve the
purpose of protecting persons against hazards or injury, or as an EMERGENCY
STOP switch for systems or machinery, or for any other similar safety-relevant
purposes.
Dimensions of housing or housing accessories may show slight tolerances on the
specifications provided in these instructions. Modifications of these records
are not permitted.
In case of a complaint, only complete devices returned in original packing
will be accepted.
Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions“.
Notes regarding mechanical mounting and attachment: Mounting shall take
place while observing all relevant regulations and standards applicable for
the place of measurement (e.g. such as welding instructions, etc.).
Particularly the following shall be regarded:
- VDE ⁄ VDI directive technical temperature measurements, measurement set – up for temperature measurements.
- The EMC directives must be adhered to.
- It is imperative to avoid parallel laying of current-carrying lines.
- We recommend to use shielded cables with the shielding being attached at one side to the DDC ⁄ PLC.
- If the sensor is used in refrigeration circuits, it must be insulated together with the housing to reduce the temperature potential between the device and the medium to a minimum and thus prevent condensation damage.
Before mounting, make sure that the existing thermometer‘s technical parameters comply with the actual conditions at the place of utilization, in particular in respect of:
- Measuring range
- Permissible maximum pressure, flow velocity
- Installation length, tube dimensions
- Oscillations, vibrations, shocks are to be avoided (< 0.5 g)
Attention! In any case, please observe the mechanical and thermal load limits of the protective tubes according to DIN 43763 or according to specific S+S standards!
Notes regarding process connection of built-in sensors:
If possible, select material of protective tube to match the material of
piping or tank wall, in which the thermometer will be installed!
Maximum temperatures Tmax and maximum pressures pmax are as follows: for TH –
MS brass sleeves Tmax = +150 °C, pmax = 10 bar and for TH – VA stainless steel
sleeves (standard) Tmax = +400 °C, pmax = 40 bar.
Screw-in threads:
Ensure appropriate support of the gasket or sealing material when mounting!
Permissible tightening torque standard values for screw – in threads, are as
follows:
M 18 x 1.5; M 20 x 1.5; pipe thread G ½ ” : 50 Nm
M 27 x 2.0; pipe thread G ¾ ” : 100 Nm
Flange mounting:
In case of flange mounting, screws in the flange part must be equally
tightened. The lateral pressure screw must clamp securely, otherwise the
feeler shaft might slip through.
Welding sleeves:
Specific welding instructions shall be observed.
On principle, unevenness or the like that might influence the system‘s ”CIP
ability“ must not develop at welds.
For high-pressure lines, pressure test certifications and inspections are
required.
Notes on commissioning:
This device was calibrated, adjusted and tested under standardized conditions.
When operating under deviating conditions, we recommend performing an initial
manual adjustment on-site during commissioning and subsequently at regular
intervals.
Commissioning is mandatory and may only be performed by qualified personnel!
Permissible approach velocities (flow rates) for crosswise approached
protective tubes in water.
The approaching flow causes protective tube to vibrate. If specified approach
velocity is exceeded even by a marginal amount, a negative impact on the
protective tube’s service life may result (material fatigue). Discharge of
gases and pressure surges must be avoided as they have a negative influence on
the service life and may damage the protective tubes irreparably.
Please observe maximum permissible approach velocities
for stainless steel protective tubes 8 x 0.75 mm (1.4571) (see graph TH 08 –
VA ⁄ xx, TH 08 – VA ⁄ xx ⁄ 90) as well as for brass protective tubes 8 x 0.75
mm (see graph TH 08 – ms ⁄ xx) :
© Copyright by S+S Regeltechnik GmbH
Reprint in full or in parts requires permission from S+S Regeltechnik GmbH.
Subject to errors and technical changes. All statements and data herein represent our best knowledge at date of publication. They are only meant to inform about our products and their application potential, but do not imply any warranty as to certain product characteristics. Since the devices are used under a wide range of different conditions and loads beyond our control, their particular suitability must be verified by each customer and/or end user themselves. Existing property rights must be observed. We warrant the faultless quality of our products as stated in our General Terms and Conditions.
Resistance characteristics of passive temperature sensors
ºC| PT 100
Ω| PT 1000
Ω| Ni1000
Ω| Ni 1000
TK 5000 Ω| FeT
(T1) Ω| KTY
81-210 Ω| LM235Z (KP10)
mV| ºC
---|---|---|---|---|---|---|---|---
– 50| 80.3| 803| 743| 790.8| –| 1030| –| – 50
– 40| 84.3| 843| 791| 826.8| –| 1135| 2330| – 40
– 30| 88.2| 882| 842| 871.7| 1935| 1247| 2430| – 30
– 20| 92.2| 922| 893| 913.4| 2031| 1367| 2530| – 20
– 10| 96.1| 961| 946| 956.2| 2128| 1495| 2630| – 10
0| 100.0| 1000| 1000| 1000.0| 2227| 1630| 2730| 0
+ 10| 103.9| 1039| 1056| 1044.8| 2328| 1772| 2830| + 10
+ 20| 107.8| 1078| 1112| 1090.7| 2429| 1922| 2930| + 20
+ 30| 1 11.7| 1 1 17| 11 71| 1 137.6| 2534| 2080| 3030| + 30
+ 40| 1 15.5| 1155| 1230| 1 185.7| 2639| 2245| 3130| + 40
+ 50| 1 19.4| 1194| 1291| 1235.0| 2746| 2417| 3230| + 50
+ 60| 123.2| 1232| 1353| 1285.4| 2856| 2597| 3330| + 60
+ 70| 127.1| 1271| 1417| 1337.1| 2967| 2785| 3430| + 70
+ 80| 130.9| 1309| 1483| 1390.1| 3079| 2980| 3530| + 80
+ 90| 134.7| 1347| 1549| 1444.4| 3195| 3182| 3630| + 90
+ 100| 138.5| 1385| 1618| 1 500.0| 3312| 3392| 3730| + 100
+ 110| 142.3| 1423| 1688| 1557.0| 3431| 3607| 3830| + 110
+ 120| 146.1| 1461| 1760| 1625.4| 3552| 3817| 3930| + 120
+ 130| 149.8| 1498| 1833| –| 3676| 4008| –| + 130
+ 140| 153.6| 1536| 1909| –| 3802| 4166| –| + 140
+ 150| 157.3| 1573| 1987| –| 3929| 4280| –| + 150
ºC| NTC
1.8 kOhm
Ω| NTC
2.2 k0hm
Ω| NTC
3 k0hm
Ω| NTC
5 kOhm
Ω| NTC
10 k0hm
Ω| NTC
10 kPRE
Ω| NTC
20k0hm
Ω| NTC
SO kOhm
Ω| ºC
---|---|---|---|---|---|---|---|---|---
– 50| –| –| –| –| –| –| –| –| – 50
– 40| 39073| –| –| –| –| –| 806800| 2017000| – 40
– 30| 22301| 27886| 53093| 88488| 175785| 135200| 413400| 1033500| – 30
– 20| 13196| 16502| 29125| 48541| 96597| 78910| 220600| 551500| – 20
– 10| 8069| 10070| 16599| 27664| 55142| 47540| 122260| 305650| – 10
0| 5085| 6452| 9795| 16325| 32590| 29490| 70140| 175350| 0
+ 10| 3294| 4138| 5971| 9951| 19880| 18790| 41540| 103850| + 10
+ 20| 2189| 2719| 3747| 6246| 12491| 12270| 25340| 63350| + 20
+ 30| 1489| 1812| 2417| 4028| 8058| 8196| 15886| 39715| + 30
+ 40| 1034| 1248| 1597| 2662| 5329| 5594| 10212| 25530| + 40
+ 50| 733| 876| 1081| 1801| 3605| 3893| 6718| 16795| + 50
+ 60| 529| 626| 746| 1244| 2489| 2760| 4518| 11295| + 60
+ 70| 389| 454| 526| 876| 1753| 1900| 3098| 7745| + 70
+ 80| 290| 335| 346| 627| 1256| 1457| 2166| 5415| + 80
+ 90| 220| 251| 275| 458| 915| 1084| 1541| 3852| + 90
+ 100| 169| 190| 204| 339| 678| 817| 1114| 2785| + 100
+ 110| 131| 146| 138| 255| 509| 624| 818| 2045| + 110
+ 120| 103| –| 105| 195| 389| 482| 609| 1 523| + 120
+ 130| –| –| 81| 151| 300| 377| 460| 1 149| + 130
+ 140| –| –| 64| 118| 234| 298| 351| 878| + 140
+ 150| –| –| 50| 93| 185| 238| 272| 679| + 150