EMERSON 4426R0 Refrigerant Leak Sensor Instruction Manual

June 12, 2024
Emerson

EMERSON logo SC-Series Refrigerant Leak Sensor
Wiring and Controller Setup

General

The SC refrigerant leak sensor is a series of transmitters for measuring concentration of different gases. The transmitter is available in the Standard Room Type. The sensor heads are semi-conductive, which provides a long lifetime and stability, but with limited selectivity.
The transmitter gives a non-linear output signal (4 to 20mA or 0 to 10V DC) proportional to the gas concentration. For long wiring installations, it is recommended to use the current output signal to minimize the risk of interference. Output signal mode is set by jumper (JP1).EMERSON 4426R0
Refrigerant Leak Sensor

Technical Data

Sensor Type Semiconductor
Response Time (T90) < 10 seconds
Operating Temperature -40°F to 122°F (-40°C to 50°C)
Operating Humidity 10 to 90% Rh (non condensing)
Dimensions 130x82x56 mm
Housing Polycarbonate / ABS
Output Signal 4 to 2OmA (max 500 ohm) or 0 to 10V DC
Calibration Zero/span ? once per year
Lifetime Sensor > 5 years (replacement recommended every 5th year or when

unit cannot be calibrated)
Power Supply| 12 to 30V DC (24V DC is recommended)
Cable gland| 1 x M16

Table 1 – Sensor Technical Specs
*Specifications subject to change

Leak Sensor Setup (4-20 mA to 1-5 VDC) Connected to MultiFlex Boards

250-ohm Resistor RequiredEMERSON 4426R0 Refrigerant Leak Sensor - fig
1

Part Number| Refrigerant| Low End Point – High End Point| Low End EU – High End EU| Voltage -1000 PPM
---|---|---|---|---
809-1201| R404a| 0-5| 0-2000| 2.5 V = 1000 PPM
809-1202| R407a| 1-5| 0-2000| 3.0 V = 1000 PPM
809-1203| R448a| .5-6.5| 0-2000| 3.5 V = 1000 PPM

Supervisor Controller Setup

In your E3 or Site Supervisor, add a 16AI Board and go to the application page to set up the leak sensor settings.EMERSON 4426R0 Refrigerant Leak Sensor -
fig 2Set up the leak sensor settings as they appear on this screen:EMERSON 4426R0 Refrigerant Leak Sensor - fig
3EMERSON 4426R0 Refrigerant Leak Sensor - fig
4

UltraSite Setup

  1. To set up the leak detector using UltraSite, open and login:EMERSON 4426R0 Refrigerant Leak Sensor - fig 5
  2. Right-click on the site and choose Connect:EMERSON 4426R0 Refrigerant Leak Sensor - fig 6
  3. Or right-click on E2 and select Offline Programming:EMERSON 4426R0 Refrigerant Leak Sensor - fig 7
  4. Right-click on E2 and select Add New Application:EMERSON 4426R0 Refrigerant Leak Sensor - fig 8
  5. Select Hardware AI for Cell Type, enter How Many, name the point and click Add:EMERSON 4426R0 Refrigerant Leak Sensor - fig 9
  6. The point is now added. Next, highlight the point and click OK:EMERSON 4426R0 Refrigerant Leak Sensor - fig 10
  7. Assign the point to the MultiFlex Board (this is the point you connect the sensor to). Highlight the point and click OK:
  8. Select Linear as the Point Type and click OK:
  9. Once this message appears, click OK:
  10. When the confirmation message appears that confirms the application has been added successfully, click Close:
  11. The point is now visible in the tree:
  12. Right-click on the point and select Edit Application:EMERSON 4426R0 Refrigerant Leak Sensor - fig 16
  13. In the Setup tab, select PPM as the Eng Units and Sensor Units:EMERSON 4426R0 Refrigerant Leak Sensor - fig 17
  14. In the Scaling tab, set up points based on the following chart:
    Part Number| Refrigerant| Low End Point –
    High End Point| Low End EU – High End EU| Voltage – 1000 PPM
    ---|---|---|---|---
    809-1201| R404a| 0-5| 0-2000| 2.5 V = 1000 PPM
    809-1202| R407a| 1-5| 0-2000| 3.0 V = 1000 PPM
    809-1203| R448a| .5-6.5| 0-2000| 3.5 V = 1000 PPM

EMERSON 4426R0 Refrigerant Leak Sensor - fig 18

E2 Setup

  1. Log into the E2 and press (Input Status screen).

  2. Highlight the input point the sensor is connected to, and press (Setup).
    EMERSON 4426R0 Refrigerant Leak Sensor - fig 19

  3. In the Analog Input setup screen, enter the following information in the fields listed below:
    • Name: A description of the sensor’s function and/or location (LEAK DET .01).
    • Sensor Type: Linear
    • Eng. Unit: PPM
    • Low End Point: 1.0 Low End Limit: -0.50
    • High End Point: 5.0 HighEnd Limit: 2200.0

  4. Press to save changes and exit the Analog Input setup screen.EMERSON 4426R0 Refrigerant Leak Sensor - fig 20

EMERSON logo Document Part # 026-4426 Rev 0
©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use.
This document may be photocopied for personal use.
Visit our website at www.climate.emerson.com for the latest technical documentation and updates.
Join Emerson Technical Support on Facebook. http://on.fb.me/WUQRnt
For Technical Support call 833-409-7505 or email ColdChain.TechnicalServices@Emerson.com
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees,
express or implied, regarding the products or services described herein or their use or applicability.
Emerson reserves the right to modify the designs or specifications of such products at any time without notice.
Responsibility for proper selection, use and maintenance of any product
remains solely with the purchaser and end-user. ©2022 Emerson is a trademark of Emerson Electric Co.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Emerson User Manuals

Related Manuals