EATON AN904 MTL Surge Protection Installation Guide
- June 12, 2024
- EATON
Table of Contents
AN904 MTL Surge Protection
Installation Guide
LIGHTNING AND SURGE PROTECTION — BASIC PRINCIPLES
INTRODUCTION
Rarely does the power of nature strike an observer more forcibly than the
sight for the first time of a tropical thunderstorm in full flow. Most people,
even those not frightened by thunderstorms as children, can appreciate that
forces of great magnitude are unleashed and that some means of protection
against the effects of lightning must be highly desirable. It is the intention
of this application note to discuss suitable techniques to protect electronic
circuits and equipment from high voltages and surge currents induced by
lightning and other forms of transients.
1.1 The need for surge protection
Most process control or telemetry installations are interconnected by power
and signal cables which run on trays, in ducting or via overhead poles.
Lightning strikes, static discharges and induction from power cabling are
typical sources of transient voltages which can be coupled into signal cables
and hence transmitted to electronic equipment. Field transmitters, computer
terminals, etc. containing low-power semiconductor devices can be damaged by
over voltages of only tens of volts. The longer the cables, the more frequent
the occurrence of high voltage transients through shifts in ground potential,
so devices controlling or monitoring events in remote locations are more
likely to suffer from over voltages and consequent component failures.
Significant damage can also be found in equipment connected by relatively
short cables if the circuits or components are particularly sensitive – as is
the case for computer data communication ports.
As an illustration, consider the effects of a lightning strike to a building,
housing control and telemetry equipment, of which the fabric is protected from
a direct strike by lightning conductors and ground rods as shown in figure 1.
The conductor carries the very large strike current into the earth termination
and dissipates the charge transfer into the mass of the earth. The effect of
this current is to elevate the reference potential at the building. For
example, if the strike current is 100kA and the conductor/ground impedance,
Re, is 10W, then the potential above ground is 1 million volts. Exposed
metalwork within the building is bonded to the same reference potential and so
only small voltage differences exist – to pose little risk to personnel.
The field transmitter is pole-mounted away from the control building but
connected to the telemetry electronics by signal cabling. Most transmitters
incorporate some level of isolation from structural earth, typically 500V.
This level of isolation now has to withstand the transient voltage between the
new building reference potential and its local earth potential. Many
transmitters can be destroyed in this way, even though the actual lightning
strike was to a protected building.
1.2 Surge protection devices (SPDs)
Electronic equipment can be protected from the potentially destructive effects
of high-voltage transients. Protective devices, known by a variety of names
(including ‘lightning barriers’, ‘surge arrestors ‘, ‘lightning protection
units’, etc.) are available. The ‘correct’ name (accepted internationally) is
‘surge protection devices’ or ‘SPDs’ – and this nomenclature is used
throughout this publication.
Surge protection devices should ideally operate instantaneously to divert a
surge current to ground with no residual common-mode voltage presented at the
equipment terminals. Once the surge current has subsided, the SPD should
automatically restore normal operation and reset to a state ready to receive
the next surge.
We specialised in the design and manufacture of SPDs. The range of products
available includes models for virtually all applications. They are based on
gas discharge tubes (GDTs), voltage-clamping diodes, and metal-oxide varistors
(MOVs) which feature rapid operation, accurate voltage control and automatic
resetting once the overvoltage has ceased.
LIGHTNING
2.1 Introduction
This section describes the mechanism by which lightning is generated and the
ways by which high voltages produced by lightning discharges find their way
into instrumentation and communications systems. Other sources of highvoltage
transients are also described, such as static electricity and induction or
direct contact with power cables.
2.2 Generation of atmospheric discharges
Updraughts and downdraughts of air are fairly common events experienced by
most of us and, indeed, used by glider pilots and balloonists to further their
flights or bring them to a premature end. Such movements of air may be
generated by heat coming from hillsides in full sun or by cold air masses
pushing
underneath warmer air in a frontal weather system. As the warm air rises, it progressively cools and forms a cloud consisting of water droplets and, at greater heights, ice crystals. A ‘thunder cloud’ is a system of this type in which the air velocities are much greater than normal. Figure 2 shows the wind, temperature and ice/water distribution in a thundercloud. The violent updraughts and downdraughts in the cloud centre generate static charges, the exact mechanism by which this occurs being still unknown. The observed result, however, is that the cloud accumulates positively charged ice crystals in the upper region and negatively charged water droplets in the lower region.
In undisturbed fine weather, the earth carries a negative charge with the
corresponding positive charge in the upper atmosphere. By convention, this
results in a positive (downwards) field V of typically 100V/m. Immediately
below the thundercloud charge centre, the electric field may exceed 20kV/m.
Fields of such magnitude can lead to point discharges taking place from sharp
objects such as the tips of radio masts and flagpoles. These objects are
essentially conductors short-circuiting part of the vertical field and hence
producing an intense field concentration at the tip. In maritime terminology
these discharges are called ‘St. Elmo’s Fire’ when they are seen on ships’
masts, etc. Natural objects can also promote point discharges, particularly in
mountainous areas where physical elevation further intensifies the field.
Climbers often experience the phenomenon of hair standing on end in
thunderstorm conditions and point discharges from the tips of outstretched
hands have been reported. The discharges themselves are of no great magnitude
and are thus relatively harmless, but they serve as a timely reminder that
true lightning discharges may be imminent.
No means are known for directly measuring the potential of the cloud charge
centres with respect to ground. Indeed, people have been killed in the attempt
(emulating Benjamin Franklin by flying a kite in a storm with a multimeter
attached is not recommended!), but it is estimated to be of the order of 107
to 108 volts, i.e. 10 million to 100 million volts. The intense field which is
generated between the charge centres causes ionization of air molecules to
take place and a conducting channel is opened which permits charge
neutralization to occur, i.e. a lightning stroke.
Most lightning is within the cloud or cloud system. Something like 15% are
cloud-to-ground discharges, these being responsible for the bulk of damaging
effects. Cloud-to-cloud discharges can generate radio interference often heard
as clicks and bangs from nearby storms, or whistles and howls from storms on
the other side of the planet.
This publication is solely concerned with cloud-to-ground discharges and the
effects on cable-connected equipment. The importance of this is emphasised by
evidence which suggests that the frequency of thunderstorms and related
lightning strikes is currently on the increase globally.
The magnitude of lightning discharges around the world have been measured from
2000A to more than 200kA, with rise times to peak current of less than 10µs.
The variation in magnitude and rise times follows the ‘log-normal’
distribution typical of many natural phenomena. BS6651 gives the following
data:–
1% of strokes exceed 200kA
10% of strokes exceed 80kA
50% of strokes exceed 28kA
90% of strokes exceed 8kA
99% of strokes exceed 3kA
Lightning discharges rarely consist of one stroke only, although the human eye
‘runs together’ multiple strokes into one persistent image. The process begins
with a stepped leader discharge making its way to ground via pockets of charge
in the atmosphere, giving rise to the typical strongly branched appearance. As
it nears the ground, local charge concentrations tend to be greatest at high
or sharp points so the initial stroke is most likely to hit tall objects such
as masts, towers, trees, etc. Often a point discharge from the tall object
reaches up to make contact with the downward travelling leader stroke. Once
the ionized channel between cloud and ground is complete, a conducting path is
formed, short-circuiting the charge centres. The main current or return stroke
can flow so as to neutralize the charge imbalance. Thunderclouds are normally
positive at the top and negative at the bottom with a positive charge ‘shadow’
induced on the ground. Thus, the negative charge close to the ground moves
down the channel to be neutralized by the positive charge in the earth. By
convention, the current therefore moves upward and this initial return stroke
has usually the highest magnitude of the multiple stroke series. The heating
effect of this current on the atmosphere produces the violent air expansion
which we recognize as a thunder-clap.
The initial leader stroke and main return stroke are generally followed by
subsequent leaders and return strokes in rapid succession. Up to 42 separate
strokes have been recorded as forming one discharge. Stroke spacing is in tens
of milliseconds and, physically, each follows the initial leader track unless
heavy winds or other disturbances can move the channel.
Some 95% of ground strokes are negative strokes with respect to ground. When
positive strokes do occur, they are usually at the end of the active life of a
particular thundercloud, and a single stroke may discharge the whole of the
upper positive cloud charge centre in a stroke of exceptional severity.
2.3 Lightning conductors and buildings
The idea of protecting buildings and other structures from the effects of
direct lightning strikes by the use of protective conductors was first
suggested by Benjamin Franklin. The lightning rods visible at the tops of
protected structures are only the start of networks of conductive paths
leading down to ground electrodes. The system of air termination, copper tape
and ground electrodes is designed to present a low impedance path to the
lightning current in order to divert that current away from the structural
parts of the building. Modern buildings of reinforced concrete or brick-clad
steel frames may use the structural steelwork as part or all of the down
conductor network. There is also a wide variety of other structural metal in
buildings which may be used as part of the protection network or as air
terminators (e.g. window cleaning rails).
National standards around the world give guidance on the protection of
buildings from lightning damage, e.g. BS6651:1999 (UK), NFPA780 (USA),
AS1768-1991 (Australia). The various suppliers of protective hardware also
publish a range of manuals on the incorporation of their products into
building design. It is important to remember that not only structural
protection but also protection for electronic and telemetry equipment within
the structure should be considered as part of the overall concern of
electrical, instrument and building design engineering. This document
concentrates on the protection of equipment, however, some aspects of
structural protection are considered in this section.
A brief appreciation of the operational aspects of lightning conductors is
very valuable in demonstrating how very high potentials can be generated and
in emphasizing the risk of side flashing through a building structure onto
unprotected metalwork or cabling.
Since lightning currents and voltages are of very short duration, the current
flows largely in the outer skin of the conductor and its cross-sectional area
is relatively unimportant by comparison with its surface area; hence the
preference for flat tape down conductors. These are also more aesthetically
pleasing to building designers and are easily worked to follow building
contours, parapets, etc.
A vertical lightning conductor AB (figure 3), 10m in length, can be considered
to have an inductance of L and negligible resistance compared to earth
resistance Re (say, 10W). If the conductor is struck by lightning with current
i then the voltage at A with respect to remote ground is Va.
Va = iR + L di/dt
Most standard down conductors have inductance of the order of 1.5µH/m. BS6651
proposes that for design purposes lightning should be considered to be of
magnitude 200kA with a leading edge rate of rise of 200kA/µs. The voltage peak
at the top of the lightning conductor is approximately 5 x 10 6 V and the
voltage at the bottom of the conductor is of the order of 2 x 10 6 V (‘ground’
does have a complex impedance but its form is so widely variable and
unpredictable that it is conventionally ignored). The voltages generated along
a down conductor in this way are high enough to arc over to earthed metalwork
inside the building, i.e. side-flashing (see figure 3). This arcing can take
place through concrete to the reinforcing bars or through brickwork to water
pipes, etc. generally with damaging effects to the structural fabric of the
building or its services. Any metalwork within arcing distance (BS6651
specifies 2m from down conductors) must be bonded to the down conductors so as
to provide a path for potential equalisation. Modern buildings often use the
steel framework or reinforcing bars as the only down conductor network and all
such steelwork is bonded during building construction – a move which may, of
course, lead in turn to the danger of side-flashing from the structural
steelwork to any electrical equipment cabling later installed close to it.
The
greatest source of high energy transients caused by lightning comes from the
shift in local earth potential with respect to far earth potential due to the
injection of very large currents through a finite impedance. An idealised
process plant consists of a well-bonded equipotential plane tied down at one
point by a connection to ground. Lightning striking the single lightning
protection tower travels vertically straight into the mass of the earth and no
potential differences arise across the plant. (Potential referenced to far
earth changes dramatically but it is potential differences that causes current
to flow not actual potential.)
In practice, a ‘real’ plant has multiple ground connections through site
supply transformers and mats associated with each tall structure. As a result,
a portion of the lightning current travels horizontally through structural
bonds, pipework, cable trays, etc. Even this current is tolerable if the plant
is well bonded since no local significant potential differences can occur
across the enormous number of substantial parallel connections. Once a cable
leaves the main site, however, the full magnitude of the transient voltage
between ‘local’ and remote ground appears across that cable and the remote
circuit earth point. Instrumentation systems are often connected between plant
areas or distributed over great distances, the instrument loop cables thus
becoming vulnerable. Instruments are not deliberately earthed at different
points but the transient voltages are often greater than the insulation level
of the printed circuit board to case and other similar points of weakness
permitting surge currents to flow.
2.4 Lightning-induced transients
The enormous energy transfer constituting a lightning strike leads to
transient generation in nearby electrical systems in a variety of ways, e.g.
radio- frequency interference (RFI), induced voltages via magnetic or
capacitate coupling and surge currents caused by localized shifts in earth
potential. Considering these mechanisms in relation to process
instrumentation, RFI rarely rises above the nuisance level. Power utility
companies often map lightning strikes over very large areas using the extra
low frequency element of this radiation. Combined with reports of power
failures, this information is used to direct repair teams to the most likely
points of damage, thereby reducing supply downtime.
Inductive effects require the close proximity of lightning currents to signal
cables in order to achieve a measurable level of coupling. Generally, field
signal cables are screened or shielded to reduce general RFI and noise pickup.
Twisted pair cables are normally used, reducing voltages between lines to
levels which do not cause measurement errors, etc. However, common mode
voltages can still be generated at levels which can cause component damage in
sensitive systems.
2.5 Transient specifications
One of the most fundamental requirements of any concept of protection is to
define the nature of the hazard. Lightning is a natural phenomenon and widely
variable so this definition is not easy. Statistically, few recorded lightning
strikes exceed 200kA and 200kA/µs rate of rise, so these values are often used
in considering direct strikes and building protection network design. However,
instrumentation, control, telemetry and telecommunications systems would
become prohibitively expensive if protection against direct strikes were to be
required. Realistically therefore, protection is limited to preventing damage
caused by potential differences from nearby lightning strikes. It becomes a
matter of assessment of risk versus cost of protection in any estimate of
protection levels to be used. Studies by the CCITT (the International
Telegraph and Telephone Consultative Committee) and the IEEE (Institute of
Electrical and Electronic Engineering) have indicated that lightning-induced
transients in telephone systems are typically of the order of a few kV and
rarely more than 1kA at exchanges. However, currents can be higher at
subscribers premises, instruments at the far end of telemetry lines possibly
experience surge currents of 5kA between ‘near’ and ‘far’ earths, the long
lines serving to flatten the very steep initial pulse and lengthening decay
times.
In order to be able to test protection networks and provide comparison data,
various standard waveforms have been proposed over the years. These are all
defined in terms of magnitude and waveshape, and can refer to current
(normally associated with short-circuit conditions) or voltage (associated
with open-circuit faults). Waveforms are usually double exponential rise and
decay shapes, specified by two time periods; rise-time to peak value and
decay-time to 50% peak value. IEC 60060-2 describes a particular method of
determining
slopes, etc. and is more relevant for manufacturers of test apparatus. Instrumentation protection circuits are almost always specified in relation to 8/20µs current pulses of typically 3kA magnitude. An alternative waveform of 1kV 10/1000µs is often used to demonstrate voltage withstand capabilities. A more severe test proposed in IEC664 is often used in European specifications. Some aspects of military specifications for nuclear magnetic pulse (NEMP) protection are more severe, typically a square pulse to 10kV with 1kV/ ns rise-time and 15µs duration, e.g. DEF Std 0755 EMP Test E1. Our surge protection devices (SPDs) are tested against the 8/20µs surge current pulse. Typical waveforms are reproduced in figure 4. These are based on ANSI C62.41 (formerly IEEE587). However, from the end user’s point of view it should be remembered that the resistance of the SPD to the test is less important than the ‘limiting-voltage’ (i.e. the residual voltage out of the unit during the period of the transient pulse; this is also known as ‘let-through voltage’). This should be below the level at which equipment damage will be caused. The SPD specification should define the ‘limiting-voltage’ for a particular test condition or give some other similar indicator of true performance.
SURGE PROTECTION COMPONENTS
3.1 Introduction
Direct lightning strikes to equipment and cables are generally of such
magnitude that protection against such an eventuality is hardly practicable
and rarely contemplated. Induced transients, however, can be accommodated by
equipment and system design. Since not all circuits are likely to be exposed
to these transients an approach often taken is to use additional protective
components or devices connected between general purpose equipment, systems,
and external noise or transient sources.
Several components are available which can be used to prevent excessive energy
reaching sensitive parts of equipment or systems. These operate by diverting
surges to earth or disconnecting signal lines. An acceptable device is fast in
operation and capable of carrying large currents for short periods while
limiting the voltage across or the current through protected equipment to
levels below which damage can take place. Maintenance-free and self-resetting
devices are normally preferred where interruptions to service should be
avoided. Various types of components are described in sections 3.2 to 3.9 and
practical devices based on the most useful of these components in part 4.
3.2 Air or carbon spark gaps
Air spark gaps are generally connected between line and earth in locations
where a high voltage transient can ‘flash over’ to earth. The protection level
is a function of the gap distance, but is affected by environmental factors
such as air humidity. They are inexpensive but their insulation resistance can
fall significantly after several operations and frequent replacement may be
necessary.
Carbon spark gaps operate similarly to air gap protectors except that very
high current levels can literally vaporize the carbon electrodes and then
either reset to a much higher striking voltage or generate a fairly high
resistance to earth.
For modern SPDs, these ‘components’ are not practical and are, therefore, not
used.
3.3 Gas discharge tubes
Gas discharge tubes (GDTs) seek to overcome some of the disadvantages of air
or carbon spark gaps by hermetic sealing, thereby eliminating environmental
effects. Gas filling enables spark discharge conditions to be quite rigorously
controlled since the breakdown voltage of such a device is related to gas
pressure and electrode separation for a particular set of materials.
Typically, low voltage protection devices have electrode spacing of 1mm or so
in an argon/hydrogen mixture sealed within a ceramic envelope at about 0.1
Bar.
Devices are available with dc breakdown voltages from 90V upwards and various
current ratings, usually greater than 5kA. With fast rise-time pulses, the
breakdown voltage is higher than the nominal dc level due to the finite
transit time of ionized particles between the electrodes. For instance, a
typical tube rated at 200V dc breakdown, will strike at 900V or so with 1kV/µs
rise-time pulse injection. Generally, the striking voltage varies with the
square root of dV/dt and the tube will generally strike within 0.5µs.
Once fired, current flows between the tube electrodes and, for currents up to
1A, the tube is said to be in the ‘glow’ region with a tube voltage of 75 to
150V. Over 1A, the discharge changes to a true ionized plasma arc and the
current flowing can be many thousands of amps for only 10 to 30V across the
tube,
assuming that the surge source is capable of supplying such currents. As the
surge dies away, the level of current flow falls and the tube returns to the
glow region and then to the non-conducting state. It is possible that a high
capacity dc supply may cause the tube to ‘hold on’ by continuously supplying
current, In practice the output impedance of the power supply and any line
impedance will limit the current to a level that will cause the tube to reset
where a very high current supply is being used to supply multiple circuits and
the live resistance is low then each circuit should be separately fused to
prevent common mode failure of all circuits.
Two- and three- electrode tubes are available, the latter being used to
protect a two-wire floating system. If two 2-electrode GDT’s are used to
protect a two wire signal system, one GDT is likely to fire before the other.
During the short time interval when only one of the tubes has fired, one wire
is close to earth potential and the other is at a high voltage which can
produce equipment damage. The use of hybrid circuits removes this problem.
A three-electrode tube (figure 6) is superior for protecting two-wire cables.
As one electrode conducts, all the gas in the tube becomes ionized and all
electrodes are connected to earth. There is only one time delay before
conduction begins and the later surge on wire 2 is diverted directly to earth
without any additional time delay, thus preventing the surge current flowing
through the protected equipment.
One problem associated with GDTs is eventual ‘burn-up’ if significant
continuous power is applied accidentally or is present on the line. For this
reason
GDTs are restricted to low-power ac or dc circuits. Voltage overshoot can also
be a problem since arc formation, as noted earlier takes a significant time
relative to the surge rise-time. For instance, a 150V GDT will strike at 150V
(±20%) under slow rising voltage conditions but may let through up to 500 or
even 700V before striking under typical 1kV/µs rise-time impulses.
GDTs are generally considered to have a finite life of approximately 20 years
as a consequence of a deterioration in the tubes’ partial vacuum.
Note: the clamping diode voltage must be below the voltage created by the
ionized plasma for the tube to reset.
3.4 Zener diodes
Semiconductor devices such as Zener diodes are fast in operation, are
available in a wide range of voltages and provide accurate and repeatable
voltage clamping – albeit with limited surge current withstand capability
which, in standard Zener diodes is usually too low to handle surge currents.
However, modified ‘surge suppression’ diodes are available with power
capabilities of up to several kW for pulses less than 1ms. This is achieved by
increasing the junction area and thereby reducing current density within the
chip itself. Surge diodes with a capability of several kW can be rather large
and expensive so indiscriminate use is not common. The large junction area
also gives rise to a significant capacitance which may seriously affect loop
bandwidth unless provision for this is made in the design.
3.5 Metal oxide varistors
A varistor is a voltage-dependent resistor in which the increase in current
with voltage through the device is non-linear. Figure 7 compares the
characteristics of the three commonly used suppression components and shows
the difference between the ‘hard’ clamping action of a Zener diode and the
‘soft’ clamping action of a varistor. Varistors are made from metal oxide
particles (usually zinc) and are thus generally known as ‘metal-oxide
varistors’ or ‘MOVs’. The zinc oxide particles are compressed together so that
interparticle contact acts as a semiconductor junction. Millions of particles
mimic millions of diodes at various voltages, so, as voltage across the MOV
increases, more and more junctions become conducting and excess current is
bled off through the component with power being absorbed through the mass of
the MOV. The power handling capability per unit-volume of varistors is much
higher than that of the surge suppression diodes with modified junction areas
since the varistor effect is a feature of the total material of the component,
not just the semiconductor junction area. However, the millions of junctions
in a MOV lead to a much higher leakage current at low voltages (typically
specified as 0.1mA for small devices capable of passing 500A [8 to 20µs pulse]
and dissipating input energies of a few Joules, however modern devices can be
much better than this.
Response time to impulses is as fast as a Zener diode and varistors are mainly
applied to ac load protection where networks for single-phase and three-phase
supplies are easy to construct. Their characteristics of ‘soft’ voltage
clamping and high leakage current at nominal voltage (together with a tendency
for both characteristics to deteriorate with temperature changes and repeated
pulse diversion) mean that MOVs are rarely used for the accurate and
repeatable protection needed for instrumentation and communications equipment.
The conventional wisdom is that MOVs slowly deteriorate when subjected to a
series of high current pulses. This deterioration causes the working voltage
to decrease and the leakage current to increase.
Eventually the working voltage falls below the peak value of the normal supply
voltage and thermal runaway occurs in the varistor which becomes very hot and
fails by short circuiting. For this reason, some networks for mains
suppression use varistors in parallel to give a measure of redundancy.
Usually, a means of isolating a failed varistor and indicating the failure is
provided so the failed unit can be replaced or repaired before the second
varistor also fails. However, this rather gloomy picture of frequently failing
varistors is not justified by the power performance of these devices in
practice. There is some evidence that deterioration does not occur below a
certain pulse threshold. The single shot rating of almost all commercially
available varistors is very conservative and repetitive pulses below this
rating do not produce a corresponding deterioration. For example, a varistor
rated with a single shot capability of 6.5kA will typically absorb 400 surges
of 4.3kA without failing. In practice therefore, conservatively rated
varistors provide reliable suppression with a reasonable mean time between
failures (MTBF). However, it must be borne in mind that varistors used at or
in excess of their single shot pulse rating may short circuit.
The predominant cause of failure of SPDs used with mains supply systems is a
rise in the mains voltage for a considerable time which has not been
recognized. In these circumstances, the peak value of the supply voltage can
cause repetitive conduction through the SPD for several minutes. The resulting
dissipation causes over heating of the shunt voltage limiting components and
consequent device failure. Continuous (longer than 10 seconds) overvoltage is
a common problem with any badly regulated source of power. Almost all supplies
backed up by or derived from standby generators are subject to such surges.
Similarly, locations fed by long cables which are subject to large load
variations frequently have unexpectedly high voltages when a major part of the
load is removed. It is important therefore, when selecting an SPD, to make
sure the maximum rated continuous operating voltage exceeds the maximum
voltage expected during these prolonged surges. For example, a SD275X is
designed for use with a nominal supply of 240V and has a maximum continuous
voltage rating of 275V; however, if the supply voltage exceeds 275V for a
significant length of time (tens of seconds), then the SPD is being used
outside its rating and may fail. Thus, if a standby generator is used then the
regulator must be good enough to hold the output voltage to less than 275V at
all times. It is important to realise that this type of failure can occur with
any shunt voltage regulator and is not a particular failure of MOVs. It is
normally associated with MOVs because they are the most commonly used surge
limiters for ac mains supplies.
When used with supplies in which the neutral is not bonded to the earth
connection, care should be taken to prevent the maximum continuous voltage
applied to an SPD fitted between phase and earth being exceeded for any
significant length of time, even under fault conditions.
3.6 Fuses
Fuses can be used to great effect in protecting equipment from over currents.
However, as they rely upon thin sections of wire melting, they take a
significant time to operate and the current passing through while this occurs
can still be sufficient to damage sensitive electronics. Fuses also have the
major disadvantage of being usable only once – leaving lines disconnected
until the blown fuses are replaced.
3.7 Surge relays
Surge relays are designed to disconnect the signal lines in the event of high
current surges, thus protecting the associated equipment. Modern designs can
handle high power levels and both operating level stability and sensitivity
are good. Speed of response is their major disadvantage, the physical movement
of the relay contacts together with the generated arc taking milliseconds to
interrupt the current flow. The majority of lightning induced surges are less
than 100µs in duration and hence surge relays are too slow. Maintenance is
also needed to keep the relay contacts clean and to prevent cold welding of
contacts which can prevent the disconnection of lines under surge conditions.
When the relay does operate, signal lines are disconnected and reset so
contact bounce can prove a problem in data communications lines if the bounce
sequence is inadvertently interpreted as valid data.
Surge relays are primarily used to disconnect power surges created by failures
in the power system which are of a significant duration.
3.8 Circuit breakers
Circuit breakers are normally designed for power systems and though energy
handling capability can be increased to whatever level is considered
necessary, speed of response is of the order of tens of milliseconds,
generally too slow to be effective against transients of short duration.
3.9 Multi-stage hybrid circuits
It is generally necessary to use more than one type of component in a
protective network to obtain the best possible combination of desirable
characteristics. The most common combination forming a ‘multi-stage hybrid
circuit’ incorporates a high-current relatively slow-acting component with a
faster acting but lower power rated component in such a way as to minimise
voltage and current output. The design of such a circuit should also take into
account the possible consequences of surges below the operating point of the
high power component but above levels at which the lower power device can be
damaged. Table 1 summarizes the performance of basic protective components.
SURGE PROTECTION DEVICES (SPDs)
4.1 Introduction
The protective components described in part 3 can be combined to form surge
protection devices (SPDs) suitable for a variety of applications. This
publication is basically concerned with the protection of electronic equipment
and communications equipment – so the detailed use of lightning conductors to
protect buildings and other structures is not discussed. The relevant UK code
of practice, BS6651:1999, is available from the British Standards Institute
and includes a wealth of information and recommendations on the design and
installation of protective systems for buildings, together with detail on SPDs
in Appendix C.
Table 1 Performance comparison of basic protective elements
Component| Speed of response| Protective level (sensitivity)|
Energy handling capability| Stability| Comments
---|---|---|---|---|---
Gas-filled discharge tube| Fast (micro seconds)| Fair| High| Fair| High-energy
handling when so constructed, low-voltage ionization levels, versatile, self-
restoring, long-life, maintenance-free Initial high voltage resistance let
through
Air gap| Fast| Poor| High| Poor| Highly unstable and vulnerable to changes in
environmental condi- tions, will not divert transients under 600V which will
destroy solid- state equipment, requires maintenance
Surge Relay| Slow (millisecond)| Good| High| Good| Good in almost all areas
except speed of response – the millisecond response cannot prevent the
microsecond death of transistors requires maintenance, bulky
Carbon gap| Fast| Poor| High| Poor| Fairly fast response, but not completely
self-restoring (in case of high-energy transients), ionization level too high
to protect semiconductors, noisy in operation, requires maintenance
Zener diodes| Very fast (picoseconds)| Very good| Low| Very good| Fast
response, but seriously limited in energy-handling capability will not protect
equipment from external transients such as lightning or induction from power
lines, easily damaged
Circuit breakers| Slow| Fair| High| Fair| Very slow, require maintenance,
bulky
Fuses| Very slow| Good| High| Fair| Require replacement. Response time
determined by fuse current
Metal-oxide varistor| Very fast| Fair| High| Poor| ‘Soft’ voltage clamping
characteristic is not sufficiently accurate for modern low-power semiconductor
devices, characteristics change over lifetime/and number of pulses absorbed
This part describes several MTL range of SPDs making use of the components
described in part 3 in multi-stage ‘hybrid’ circuits or other networks
developed for various applications through the years. See part 5 for detailed
application advice.
4.2 Basic multistage hybrid SPD circuits
These are circuits where the best features of individual components are
combined to overcome their individual disadvantages – as shown by the block
schematic diagram in figure 8. MTL SPDs for signal line applications (i.e.
instrumentation, computer networking, telemetry, etc.) are based on high-
voltage high-current gas-discharge tubes (GDTs) for high energy handling, and
low voltage low-current surge suppression diodes for accurate and fast voltage
control. The two components are separated by a series impedance selected
according to the operational and design requirements of a particular unit. In
action, if the transient is below the value that strikes the GDT, while the
diodes clamp the voltage, impedances limit the peak current if the surge is
prolonged.
This type of SPD, exemplified by MTL SD range, is auto-resetting (i.e. after
operation it automatically resets itself to permit the protected equipment to
continue operating) and is maintenance free.
Earlier types of SPDs incorporated internal fuses which, in the event of a
prolonged surge, ‘blew’ so interrupting the loop until the SPD was replaced.
Some current SD range units are available with external replaceable fuses.
These fuses protect the circuit against prolonged over current from the
protected circuit. The fuses are mounted in a disconnect facility which is
useful for circuit isolation (NB. The fuse does not ‘blow’ under normal surge
conditions). These types of SD range units are shown in figure 9.
Alternative networks, based on metal-oxide varistors (MOVs), are a more recent
development which are used in SPDs designed for protecting equipment against
surges on ac power lines.
APPLICATIONS
5.1 The need for protection
In determining protection requirements, the balance to be achieved is the
relative cost of providing protection against the probability of damage and
the costs and consequences of such damage. Except in very exceptional
circumstances, the possibility of a lightning strike directly hitting
electronic instrumentation is usually discounted. Extreme cases such as wind
gauges on the highest point of an offshore rig are an example of a conspicuous
exception. In such a case, the gauge itself is destroyed but the equipment
connected to it can be protected by suitable SPDs.
The principal factors to be considered in determining this balance are:–
a) The risk of lightning-induced or other surges occurring on interconnecting
cables.
b) The cost of damage to equipment directly or indirectly connected to the
cables. This should include an assessment of the availability of spares and
the accessibility of the equipment should repairs be necessary.
c) The consequential cost of downtime caused before damage can be rectified,
such as loss of production or work in progress on a computer system.
d) The safety implications of damage. This factor is frequently difficult to
assess in purely financial terms if there is the possibility of human injuries
or fatalities. Thus, emergency shut-down (ESD) systems and fire alarm monitors
are typical of the systems which call for a high degree of protection for
safety reasons.
Some notes on other aspects of applications are discussed in detail in the
following sections.
5.2 Loop protection – general
For complete protection, it is usually necessary to protect both ends of a
loop, as any surge protection device can only provide local protection. SPDs
control voltage and divert surge currents relative to their local earth points
and therefore ‘remote’ devices need their own individual protection. However,
in average industrial plants many individual items of remote field
instrumentation are relatively inexpensive and easy to replace, the cost of
loop failure is not great, and the risk of damage from local surge currents is
slight – therefore, in these circumstances, it may be thought desirable to
confine protection to the control room end of the loop where much more vital
control equipment affecting the whole process (or a major part of it) may be
at risk.
However, there are some areas of application where field instrumentation
should be protected. These include loops which are vital to the process, field
devices which are inherently expensive (such as some types of transmitters),
and loops in which the field instrumentation is located in very remote or
inaccessible locations. Major users of SPDs for remote field instrumentation
include the utility companies which maintain what are often far-flung
distribution and monitoring systems. For these companies it is both
inconvenient and expensive to send an engineer many miles to replace fuses or
failed sensors, so it is economically good sense for them to provide remote
instrumentation with modern maintenance-free and auto-resetting SPDs.
We supply some unique SPDs designed specifically for use with particular items
of ‘field’ instrumentation. These devices incorporate proven hybrid surge
protection circuits and are designed for mounting within or on the
instrumentation for which they are specified.
Apart from instrumentation systems, other cabled connections which can be
affected by surge currents include computer LANs linking computers located in
more than one building. Where such connections are made by simple direct
wiring then shifts in earth potential of one building with respect to another
caused by a nearby lightning strike can lead to surge currents destroying or
damaging computers in one or both buildings.
5.3 SPD selection – general
Selecting SPDs for any particular application calls for a balance between
minimizing the effects on normal operation, high surge handling capability,
and secure voltage clamping. The hybrid circuit design for instrumentation
protection combines gas discharge tubes with voltage clamping diodes – and
hence these designs have some series impedance, controlled diode leakage and a
small voltage overshoot. An analysis of individual circuits must bear these
factors in mind.
Power supply lines (ac) are usually protected by SPDs incorporating MOVs. In
these applications, leakage current is not a significant factor but care
should be taken not to exceed the maximum continuous operating voltage as
discussed in section 3.5.
5.4 Surge protection for industrial process systems
While the importance of surge protection for industrial and process plants has
been appreciated for many years, the rapid development of computerized control
and security systems has made it even more imperative for modern process
systems which recognised that any externally-cabled connections (such as those
for control, safety, data communications, telemetry and maintenance systems)
are possible sources of potentially damaging surges. Complete protection can
only be provided by protecting all cable routes into plant structures.
Figure 10 illustrates a ‘typical’ industrial process layout and highlights
those areas which are most at risk from lightning and surge damage or most
likely to pass induced currents into sensitive or critical equipment and
where, there- fore, surge protection should be considered essential or
desirable.
5.5 Surge protection for building systems and communications networks
During the last decade enormous investments have been made throughout the
world in computers and electronic equipment designed for use in offices, other
commercial buildings and even in homes. At random, a few such examples include
computerized banking services (including ‘hole-in-the-wall’ cash dispensers),
process control in factories, evermore sophisticated telephone and other
global communications services, satellite and cable-TV services, and computer-
controlled fire and security services (including burglar alarms).
Unfortunately, these systems are all at risk from nearby lightning strikes if
left unprotected. Figure 11 illustrates a ‘typical’ commercial building layout
and indicates those areas where surge protection should be considered
essential or desirable.
5.6 Specific applications
This section lists suitable SPDs for various specific applications and, in
some instances, also discusses the choices in considerable detail – giving
examples which help to cast light on the considerations which need to be taken
into account when choosing SPDs for any specific purpose.
5.6.1 SPDs for process-variable transmitters (general)
This section considers the effects of including SPDs in loops based on process
variable transmitters (i.e. either ‘conventional’ or ‘smart’ 4 to 20mA 2-wire
transmitters for flow, temperature, pressure, level). It is assumed that the
transmitter is driven from a bulk dc power supply and terminates in a 250W
load resistor as part of an instrument or a control system input card. Other
types of process transmitter loop can be treated in a similar fashion with
small adjustments to loop voltage drops.
Transmitters are often supplied by the manufacturers with optional built-in
‘protection’ – generally a clamping diode network that, while certainly
reducing transmitter failure, can only handle relatively low-power surges.
Heavy surges (of the type likely to be caused by a nearby lightning strike)
will almost certainly destroy both the protection circuit and the transmitter.
Higher levels of protection – particularly for remotely located transmitters –
are therefore worth considering to avoid downtime losses and the considerable
cost of replacing equipment at some distance from the centre of operations.
In the following two sections, SPDs for the control equipment (5.6.2) and the
transmitter (5.6.3) are considered separately while subsection 5.6.4 considers
possible problems associated with using SPDs at both ends of a loop. See also
section 5.6.5 for SPDs suitable for use with vibration-probe loops.
5.6.2 SPDs for transmitter control equipment
Figure 12 illustrates a typical loop configuration with an SPD located at the
control room end of the loop only. The working voltage of the selected SPD
must be higher than the supply voltage to prevent unacceptable errors being
caused by leakage currents through the SPD diodes. The usual power supply
arrangement is a bulk dc supply with a common negative providing the system 0V
reference. This supply is normally a nominal +24V, so a 32V working voltage
SPD is suitable. A suitable SPD is Telematics’ SD32 which is provided with a
250mA replaceable fuse and a disconnect feature which is desirable for most
applications. An equivalent SPD without the replaceable fuse option is the
SD32X (the fuse is not necessary for correct SPD operation).
Including an SPD means that the power supply minimum output voltage must be
capable of tolerating the additional voltage drop incurred by the SPD
impedance. The line resistance of Telematics’ SD32 and SD32X SPDs are
negligible (4 and 2W respectively) so, for all practical purposes can be
ignored.
Leakage current for both devices is specified as not exceeding 5µA for a 32V
supply. The leakage current from the supply side to earth does not affect the
current delivered by the transmitter to the load resistor. As the supply
voltage increases, the leakage current through the diodes increases steadily
until at 36V it is of the order of 5mA. Any further rise in voltage
dramatically increases the leakage current and is likely to lead to the power
supply fuses blowing or other protective devices operating. With this proviso,
MTL SD32 or SD32X SPDs are the ideal choice for protecting the control
equipment end of the loop. For applications where a number of control loops
operate from a common control unit, the high packing density and simple DIN-
rail installation of these SPDs makes them particularly useful.
5.6.3 Field SPDs for process transmitters
SPDs are not necessarily needed for transmitters when the loop is within a
covered plant. However, if the transmitter variable is particularly vital to
the process or if it is remote and unprotected by any surrounding steelwork,
then protection is advisable. Transmitters on tall structures such as
distillation columns are also vulnerable to high voltages between the case and
the circuitry caused by lightning currents flowing down the structure (see
figure 13 for an example) – as also are transmitters located close to
structural steelwork used as lightning conductors, an increasingly common
practice. The transmitter illustrated in figure 13 would be subject to a
voltage stress of more than 100kV between its case and the internal
electronics. Any or all these factors must be taken into account when deciding
if protection is desirable.
SPDs fitted to transmitters should attempt to provide a preferential breakdown
path between lines and lines/earth so that any surge currents thus induced
flow along that path rather than through the transmitter circuitry. The type
of transient protection offered as an optional extra by most transmitter
manufacturers generally consists of surge suppression diodes or, occasionally,
varistors. The former type provides protection only against low-voltage and
the latter only against high-voltage surges. Devices incorporating hybrid
circuits combining gas discharge tubes, varistors and surge suppression di-
odes are the obvious answer but, until relatively recently, were not easy to
implement on account of the physical difficulties of packaging the more
complex network within the body of the transmitter.
The better solution is to use a ‘dedicated’ external SPD, designed
specifically for easy and convenient use with transmitters, such as our TP48
device. This is a small unit which is mounted by screwing it into a spare
‘cable entry’ on the transmitter casing as shown in figure 14. Three flying
leads are provided for connection to line 1, line 2 and earth as shown. It is
available both in a standard version and also in two ‘explosion-protection’
versions (i.e. intrinsically safe and flameproof). All versions are available
with a variety of screw-threads to suit virtually all currently available
transmitters and can be retrofitted to existing installations without
affecting loop wiring or performance. TP48 SPDs provide protection against ALL
surges up to 10kA and achieve 60V differential mode protection, figures much
better than those of the transmitter manufacturers’ options.
Alternatively, a separate SPD such as one of the SD range can be used but, if
this is done, it should be protected by a suitable weatherproof enclosure. If
this latter option is selected, then the field-mounted SPD must be locally
bonded since it is the local potential between the structure and the signal
cables which needs to be controlled. The SPD should therefore be bonded to the
mounting bracket of the transmitter (if possible) with a substantial and
secure cable (note that the TP48 is bonded to the transmitter – an eminently
satisfactory solution as you can’t get much closer than that!)
5.6.4 SPDs for comprehensive transmitter loop protection
When a transmitter or other field-mounted equipment is protected by an SPD
then the parallel paths created by the installation make it necessary also to
protect the control-room end of the loop. The majority of also to
installations take the form of the circuit shown in figure 15. The end-to-end
resistance of the two suppression circuits is very low (less than 10W in
total) and hence does not appreciably affect the circuit operation. For
example, with a 24V supply, a transmitter requiring a minimum of 12V and a
computer requiring 5V, the available voltage for line resistance and other
accessories is 7V – which is more than adequate for most applications.
The circuit shown in figure 15 illustrates the use of an SD32 SPD at the
control-room end to provide fuse protection to prevent a field short-circuit
fault affecting the operation of the rest of the circuit sharing the common
power supply. The circuit disconnect facility of the SD32 is useful for
maintenance purposes. If this latter facility is not needed, then an SD32X
(which does not include the replaceable fuse/disconnect link facility) can be
used instead of the SD32.
The maximum supply voltage can be allowed to exceed 32V by a small margin
since leakage current from the power supply rail to the 0V of the system does
not affect the measurement accuracy. However, the situation is not well
defined and voltages in excess of 35V could blow the fuse.
In a relatively small number of applications it is necessary to increase the
loop voltage for operational reasons. This can be because of:–
a) Extremely long land lines.
b) Additional equipment such as indicators or trip amplifiers at the
transmitter end of the loop.
c) The control-room equipment needs a signal voltage of more than 5V.
A possible circuit diagram for this situation is depicted in figure 16. The
maximum voltage for application to the circuit is determined by the 48V
maximum working voltage of the TP48. If it is not necessary to be concerned
about achieving a very low circuit current for detecting an open circuit
transmitter, then a voltage higher than 48V can be applied. Operationally, the
transmitter always consumes more than 4mA and the voltage drop created by this
current can be used to increase the supply volts. Generally however, it is
less complicated and usually practical to use a supply voltage of less than
48V.
5.6.5 SPDs for use with vibration sensors
The 3-wire transmitters used with vibration monitoring equipment are
invariably supplied by a –24V dc power supply, so the recommended SPD choice
to protect the control-room end of the loop is an SD32 or SD32X unit. See
figure 17. Where the probe and its driver must also be protected, then a
suitable field-mounted SPD such as the mSA30/2 should be used. Direct
connection of the field wiring to ground at more than one point is not
recommended since the resulting circulating current will cause measurement
problems. If it is considered desirable to ‘isolate’ the system from earth and
all three wires need protecting then this can be done by using the 4-channel
mSA30/2. Each channel has a resistance of 43W and hence the most effective
result is achieved by paralleling two channels and using them in the 0V line
which is most affected by resistance.
5.6.6 SPDs for temperature sensors
Sensors commonly used for temperature measurement are relatively simple
devices such as thermocouples (THCs) and resistance temperature detectors
(RTDs). While these are hardly immune to damage and destruction caused by
high-voltage transients and surge currents, the replacement cost is generally
so low that protection for them in the field is rarely provided unless they
are difficult to replace or the particular temperature measured is so vital to
the process that the cost or consequences of any downtime makes the
installation of an SPD worthwhile. In the control-room however, the receiving
and control equipment is also liable to damage from surges and the replacement
and downtime cost will almost certainly be more than enough to warrant the
installation of an SPD.
Signals from temperature sensors of the type described are usually of low
voltage and the end-to-end resistance of SPD channels is only significant for
RTDs. Temperature measurement with RTDs is resistance sensitive to the extent
that 3- and 4-wire RTD connections are used to eliminate the effects of lead
resistance changes on the measurement resistance change. RTDs in protected
circuits must be either 2-wire types (i.e. RTDs which are not particularly
inherently accurate and are therefore mainly suitable for use as an
overtemperature trip) or a 4-wire type in which a constant-current source is
used to compensate for variations in lead and SPD resistance. The working
voltage selected for an SPD to protect instrumentation connected to field
tempera- ture sensors is not critical since the leakage specification voltage
is likely to be orders of magnitude greater than the system operating voltage.
5.6.7 SPDs for temperature monitoring of large motors
Temperature monitoring of large motors is a case where SPDs should be
specified to protect panel instrumentation from power faults and transients on
the motor windings. Figure 18 illustrates a typical installation of this type
in which a thermocouple is used for temperature sensing. If the thermocouple
is insulated, then the transient potential between the thermocouple and the
motor structure is determined by the current flowing through the structure and
other return paths. The potential is therefore the supply voltage potentially
divided between the return path impedance and the source impedance plus the
fault voltage. Hence the return path must be of low impedance or the voltage
developed can be high. With a 440V 3-phase motor, the 250V with respect to
earth is likely to have a transient voltage of 100V or so until the protective
network operates. On higher voltage motors, unless the fault current is
restricted, the transient voltage is correspondingly higher and further
precautions such as installing an SPD as shown are necessary to protect the
instrumentation/monitoring circuits.
In general, SD07/SD07X SPDs are suitable for protecting THCs and RTDs in the
field and SD16/SD16X for protecting the related control-room instrumentation.
5.6.8 SPDs for weighing installations
Weighbridges are frequently located in exposed conditions and the load cells
associated with them are therefore susceptible to lightning induced surges
and it is advisable to protect both the ‘field’ load-cells as well as the
associated control-room equipment. We provide specialist SPDs (the LC30
system) designed for mounting under weighbridges and between silo legs and
which are suitable for virtually all strain-gauge, load-cell, weighbridge
cabins, silos, and process storage facilities.
The system covers working voltages up to 30V and handles maximum surge
currents of 10kA. The LC30 system components and their applications are
described in detail in TAN1006, ‘Surge protection for weighing systems’.
5.6.9 SPDs for miscellaneous low-voltage
Apart from temperature sensors, other low-voltage analogue loop field devices
which may need control-room and field protection include ac sensors,
photocells, microphones and turbine flowmeters. Suitable SPDs for these are
the SD07 and SD16 units and also the ‘X’ versions of both (see figure 21). For
slide wire displacement transducers, the recommended choices are usually the
SD07 and SD07X.
See also section 5.6.16 for other possible units.
5.6.10 SPDs for analogue output devices
For controller outputs such as I/P converters, the recommended SD range of
choices are the SD16, SD32 and SD55 units (and the equivalent ‘X’ versions),
the final choice depending upon the supply voltage. See figure 20.
See also section 5.6.16 for other possible units.
5.6.11 SPDs for switches
Depending upon the supply voltage of the system, suitable SPDs for switches
include the SD07, SD16, SD32 and SD55 modules – or the ‘X’ equivalents. Where
110V ac is used on status switches then the appropriate SPD is the SD150X.
See also section 5.6.16 for other possible units.
5.6.12 SPDs for alarms, LEDs, solenoid valves, etc.
The SD32 or SD32X are the recommended choices for these applications. See
figure 21.
See also section 5.6.16 for other possible units.
5.6.13 SPDs for primary and local ac mains supplies
Mains ac power lines are prime sources of noise and external transients
conducted into electronic systems. Aware of this, we provide a wide range of
products based on metal-oxide varistor circuits to address various aspects of
the problems posed by ac power lines and cables. Ideally, ALL distribution
boards, both primary and local, should be protected by suitable devices which,
in every case, should be mounted either on the board or as close to it as
possible.
Frequently mains supplies are distorted by high frequency signals which may be
fed into equipment from the mains supply. Alternatively, equipment may feed
signals back into the supply system which can cause problems in other
equipment connected to the same supply. These problems can be avoided by using
a unit which combines surge suppression and filtering. It is desirable to
avoid the ringing which occurs when a fast rise time pulse is applied to the
filter and these units utilize a special circuit to prevent this.
For primary distribution boards (i.e. those connected directly to the mains
supply feeding a building) the usual recommendation is a MA2000 Phase Shield
Series unit which is available in single and three phase versions for 110V or
240V supplies. This unit provides a level of protection which is more than
adequate for almost all situations, and being spur connected is not affected
by the current rating of the supply. If a single phase filtered supply is
required then in addition to the spur connected suppression facility a 20A
filtered supply can be made available by using the MA2001/F as illustrated in
figure 22.
Where a lower-power suppressed and filtered supply is required, for example
for a rack of instrumentation, then MA05 or MA10 units which are available in
a standard filter can or DIN rail mounting may be the better solution.
5.6.14 SPDs for telemetry systems
As the first providers of distributed cabled networks (much of it out of doors
and covering long distances) telephone systems were also one of the first
major users of surge protection devices, hence the application of surge
protection to telemetry is widely accepted and, generally, well understood.
Many telemetry systems use telephone lines (either private ‘dedicated’ or
public dial-up) for signal transmission and SPDs used for these applications
must be approved by national bodies responsible for providing communications
service. Bearing in mind the openly distributed nature of many telemetry
installations, it is clearly advisable to protect equipment at both ends of
the line and we have borne this in mind with product ranges available for
these applications.
Telephone systems use fairly high dc voltages for line supply and bell
operation. Typical system working voltages are of the order of 40 to 50V dc.
In the UK, ringing voltages are 120 to 140V but some systems can impose
ringing voltages of up to 270V. Electronic telecommunications equipment
includes ‘subscriber line interface circuits’ which have voltage withstands of
the order of 60V or so. SPD’s used in public telephone systems are required to
adhere to the R&TTE directive.
Standard Zener or surge diodes with breakdown voltages of the order of 180V
can provide clamping of transient surges but the power dissipation in the
component is high and leads either to an unacceptably high cost or to a
reduced life expectancy for the network. To solve this problem, ‘foldback’
diodes have been designed which behave as conventional Zener diodes below a
critical voltage known as the ‘voltage breakdown level’ or VBR, i.e. a small
amount of reverse leakage current. Above VBR, the device begins to conduct
very rapidly, the changeover taking place in picoseconds (10-12s). With a
conventional Zener diode, as voltage increases across it, current increases
through it with a slope resistance of typically 1 or 2W. With foldback diodes
however, the voltage across the unit collapses to a much lower value when the
current is flowing through it, thereby significantly reducing the internal
power dissipation.
Specialist SPDs for telemetry applications include the DP200 BT & RJ SPDs and
the TS range of surge protection devices. The former is designed for
installation between line jacks and telephone socket outlets to protect
equipment such as fax machines, modems, extension telephones etc. while the
latter units are designed to protect local PABX exchanges against surges on
incoming lines.
All these units handle surge currents up to 10kA. See also sections 5.6.15 and
5.6.16 for other related units.
5.6.15 SPDs for data communications equipment
In-house computer systems nowadays are generally extensively interconnected by
‘wide area networks’ (WANs) and ‘local area networks’ (LANs). So long as such
a system is confined to one building, it is difficult to conceive of a fault
leading to significant potential differences between computers. However, when,
as is increasingly the case, the network extends to more than one building,
the risk of computer damage caused by shifts in earth potential is obviously
increased. SPDs at both ends are normally the wisest solution as illustrated
by figure 23. If the connection is between totally separate systems belonging
to different companies or institutions, then the necessity to insert SPDs
between them is even greater so as to avoid disputes concerning who damaged
what.
The working voltage for the SPD relates to the maximum voltage of the
communications ‘driver’ cards which rarely exceed 12V, hence 16V working
voltage SPDs are generally adequate. EIA standards exist for data
communications and the number of SPD channels necessary depends upon the
particular implementation in use. For instance, the RS232C format specifies 25
lines between two computer systems. Most systems use 3 lines for data
transmission and possibly another 3 or 4 lines for ‘handshaking’ (i.e. data
communications control signals). RS422/423 systems are essentially 4-wire
circuits, hence 2 SPDs are necessary at each end.
The surge diodes and other semiconductor components in SPD circuits will
always produce some parasitic capacitance between lines and line-to-ground.
Thus, SPDs will act as RC networks with increasing attenuation of higher
frequencies. Quoting typical figures of insertion loss in dB at arbitrarily
chosen frequencies is not particularly helpful as the main reason high baud
rate transmission systems record unacceptably high error rates is modification
of the pulse shape caused by various LRC components in the transmission line.
Some systems are successful at 9.6kbaud while others are rejected at 1.2kbaud.
The easiest way of checking that correct operation is feasible is to
incorporate a practical test. The prime factor in correct system operation is
the ability of the receiving equipment to ‘reshape’ the signal into the
correct form.
Standard hybrid SPDs are therefore rarely capable of combining high bandwidth
data transmission with a high level of surge diversion capability. The need
for low clamping voltages and delicate impedance matching makes circuit design
difficult, particularly if high transmission speeds are required. The MTL SPDs
for data communication links, all of which exceed the IEEE 802.3
specifications, are specifically designed to overcome these difficulties as
far as possible. Applications for these devices include not only WANs and LANs
but also telemetry circuits (see also section 5.6.14 for the latter).
The choice for computer networks are the Net Shield surge protection devices
which permit high speed data transmission both within and between buildings.
Net Shield is available with RJ45 style connectors for easy installation and
it can also provide mains power protection which is crucial for the safety of
the system that it is protecting. The Atlantic Scientific Zone Barrier model
24534 is equipped with BNC connectors providing a clamping voltage of 30V
which will protect all 10Base-2 installations.
The Atlantic Scientific Zone Barrier 24540 is designed to protect Cat.5 Local
Area Networks with up to eight wire protection. This device also has the
benefit of an RJ45 connection system to allow for simple installation an peace
of mind. For even greater protection, the Zone Barrier 24550 is a dual port
10/100Base-T (Cat.5) protection system. The 24550 also has an RJ45 system for
straightforward connection.
5.6.16 SPDs for protecting instrumentation systems
Incoming signal cabling to electronic systems is usually by twisted pairs or
coaxial lines. Because of the wide choice of applications (see also sections
5.6.9 to 5.6.12 in particular), variety of data transmission speeds and system
characteristics, there are a number of choices of SPDs based on fast hybrid
circuitry.
Apart from the almost ‘universal’ DIN-mounting SD range discussed elsewhere
(see sections 5.6. 1 to 5.6.12 for these), other suitable ranges are available
from Eaton. Most of these cover virtually the same range of applications as
the SD range. Additionally, there is the CA range of ‘in-line’ co-axial SPDs
which insert into co-axial lines with minimal insertion loss and VSWR with
wide bandwidth. The CA range is available with a wide choice of terminations
to suit virtually all applications (including panel-bulkhead fitting).
The AirGuard range of radio frequency protectors cover WQWS, Wideband Quarter
Wave Stub, and NQWS, Narrowband Quarter Wave Stub requirements. Power ratings
from 37 Watts to 4555 Watts are available with surge ratings from 20 to 40kA.
A wide range of connector types from standard ‘N’ type and ‘N’ bulkhead, to
BNC, TNC, and UHF are available.
The GT range of surge protectors provides economic and robust protection in a
versatile broadband package with multiple frequency products which are ideal
for multi-disciplined wireless protection.
The SSDC/OEM range was designed for specific point-to-point and point to
multipoint wireless LMDS equipment. These devices protect both the RF signal
and the DC power on coax between the indoor unit and outdoor transceiver unit.
SSDC/OEM units have an LED DC status indicator and use solid state technology
that provides a 70% lower limiting voltage compared to gasttube technology.
5.6.17 SPDs for hazardous-area applications
‘Intrinsic safety’ is the commonest and generally preferred technique of
explosion protection for measurement and control instrumentation in process
‘hazardous areas’, i.e. areas where a potentially explosive atmosphere may
occur. We are the world’s leading supplier of intrinsically safe
instrumentation. This allows for close co-operation between the group
companies in the development of surge protection devices suitable for use in
protecting intrinsically safe circuits against lightning-induced transients or
other high-power fault surges.
The technique of intrinsic safety works basically by ensuring that under all
circumstances the amount of electrical power that can reach hazardous-area
process equipment from safe-area control equipment is limited to a maximum of
approximately 1W. To make sure this occurs, intrinsically safe (IS) interfaces
are generally included in the control loop at the safe-area end. IS interfaces
are of two kinds, either shunt-diode (i.e. Zener) safety barriers or galvanic
isolators. The former shunt fault currents to earth while the latter, as the
name suggest, ‘isolate’ fault currents. Safety barriers are less expensive but
isolators have the advantage that they can incorporate additional signal
processing circuits to provide a double function.
This brief introduction to surge protection in IS circuits has not touched on
the various IS certification requirements of national and international
standards authorities which can affect the implementation of surge protection
in these circuits, nor the stringent earthing requirements (except in the USA)
imposed upon surge protection systems.
Those with a particular interest in this application are advised to read
TAN1004, ‘Surge protection for intrinsically safe systems’ and also TAN1005,
‘Surge protection for Zone 0 locations’ in conjunction with this Application
Note.
EARTHING
6.1 Introduction
SPDs are designed to safeguard equipment by diverting surge currents and by
controlling impressed voltages across circuits, both of which are effects
requiring a low impedance earth connection. The overall security and
reliability of the protection provided can be negated by an indifferent
installation, so installation and earthing requirements are both of the first
importance. This section is concerned with earthing and, again, largely
introduces a subject which is treated in detail in TAN1003, ‘Earthing guide
for surge protection’ to which readers are referred for more details. For
installation information concerning specific Telematic and Atlantic Scientific
SPDs, see the appropriate product specifications and instruction sheets.
6.2 Earthing
Providing a low impedance connection to the electrical earth is a fundamental
requirement for all SPDs used to control line-to-line and line-to-earth
transients. All other ‘earths’ consist basically of bonding between various
return paths and are usually classified with respect to the source of the
fault current, e.g. computer earth, power earth, instrument earth, etc.
Structural ‘lightning’ protection is probably the only function for which a
‘real’ physical connection to the Earth’s mass is actually necessary. The
reasoning behind this is based on the fact that lightning is a flashover
between two charge centres, one of which is in the sky and the other in the
ground (when considering the necessity for protection against surges caused by
lightning, intra- and inter-cloud discharges are not important). The necessary
current flow between these two charge centres is essentially vertical. It is
the sheer magnitude of this vertical lightning current which will produce
large potential differences across plants should more than a small part of
that current be encouraged to flow horizontally. Figure 24 illustrates an
‘ideal’ plant while figure 25 shows a ‘real’ plant with a mixture of
structures, some of which are bonded to individual earth mats. Lightning
current flows into the column shown and down to the earth mat associated with
that particular structure. There is a parallel path through the plant’s
overall bonding network to additional earth mats and a division of lightning
current will take place which, to a first approximation, follows standard
Kirchoff’s law (i.e. is based on purely resistive impedances ignoring complex
contributions). In the example shown, the primary lightning current is 100kA
and, if 1% of that current follows the alternate route through a plant bond
of, say, 0.5W impedance, a potential difference of 500V is generated across
that connection. There is plenty of evidence, based on these considerations,
that lightning current will lead to large potential differences and cause
significant damage if direct vertical paths to earth are not provided.
Ironically, if the plant is completely isolated from the rest of the world,
the actual impedance of the earth connection is not important. If the direct
impedance is, say, 10ž, then with 100kA flowing, the entire plant
equipotential plane is elevated by 1MV. Since everything rises together,
however, there is no potential difference between one part of a plant with
respect to another and hence no problem. In the ‘real world’, the key
requirement is to provide
a direct primary vertical path to ground and to bond horizontally any
secondary paths. The vertical and horizontal connections must be of low
impedance to minimise voltages across their lengths but the earth impedances
are not particularly important except insofar as high impedances can lead to
difficulties at external isolation boundaries. It is certainly not the case
that earth impedances must be less than 1ž or any other favourite figure.
Whether rods or mats are used is a decision based largely on convenience and
cost and has also, perhaps, something to do with achieving a low enough return
path connection for power distribution system protection purposes.
An SPD earth is therefore yet another earth which must be bonded to the
transformer neutral star-point which is itself then connected to an earth mat
by way of the power supply central site reference point. The function of the
central reference point, usually a substantial busbar located in the
distribution room, is to make sure that all site ‘earths’ are related to the
same voltage which is then nominated as 0V for the site.
A conventional power supply distribution system for a building is shown in
figure 26. The incoming steel-wire armoured (SWA) power cable includes all
three phases and the neutral conductor, with the normal protective (earth)
conductor forming the armour of the cable. In the UK IEE wiring regulations,
this is defined as TN-S. Power within the building is usually distributed as a
single-phase supply with earth lines shown connected to the main installation
earthing bar (1). Any exposed conductive parts in the installation are
similarly connected to the main installation earthing bar (2). When SPDs are
installed the instrument ‘0’ volt system should be connected to the SPD bond
(3).
The SPDs must be earthed directly as soon as possible. This is best achieved
by bonding to the power supply distribution earth rail (5). If there is no
dedicated lightning stake/mat then bonding the SPD earth to the main
installation earthing bar through (4) and (5) will cause any surges to flow by
way of the distribution earth. This is not particularly dangerous since, if
all the equipment is bonded to this point, no relative voltages are generated
and no currents will flow through the personnel or distribution system
protective bonds.
The important earthing impedance for the SPD is the resistance of the bond
between the SPD and the electrical/instrument earth bar. For a more precise
and detailed analysis of the requirements of earthing and bonding, please
refer to TAN1003.
MAINTENANCE
7.1 Introduction
No regular maintenance or operational checks are needed for most SPDs. Any
faults which may develop are likely to be self-revealing in that the devices
will fail to earth with either open-circuit lines or short-circuit lines.
These are both ‘fail-safe’ in nature as system damage cannot be caused with
subsequent surges or over voltages. System operation is, of course,
interrupted if an SPD fails but this should not happen often – MTBF to RRE250
is well in excess of 200 years. After surge diversion, the MTL SPDs
automatically reset to the passive protection mode and not to ‘fail’ (however
safely!).
It is however advisable to check the earth connections periodically to make
sure no deterioration has taken place and that no modifications or additions
have been made which bypass the SPDs. SPD installations will only be effective
if all possible entry points of overvoltage and surge currents are secured. A
comprehensive and knowledgeable approach to lightning protection is needed and
it should be the responsibility of one nominated individual on each site.
He/she will need the wisdom of Solomon (or the beauty of the Queen of Sheba)
and a highly developed sense of diplomacy to be able to overrule the ‘earth’
requirements of the computer department, the instrumentation department, the
electrical department, etc. and anyone else who ‘knows what earthing is all
about’!
Some suitable test procedures for checking earth connections are included in
TAN1003. In a general sense, the simple tests described in section 8 of this
publication may also prove useful.
7.2 Fault finding
Before installation, the end-to-end resistance across an SPD can be checked
simply with an ordinary multimeter applied on one of the resistance ranges.
This should not exceed 50W for any MTL unit and will be noticeably lower for
some. Another check is to measure the resistance between lines and line to-
earth. This resistance will be very high unless the protection element has
failed safe or the meter output voltage is greater than the rating of the SPD
(unlikely for most SPDs).
Once units are installed, commissioned and working, frequent checking is not
recommended for any SPDs. Faults are generally self-revealing through loop
malfunction. In any installation except the simplest, there is a very real
chance that disconnecting and reconnecting large numbers of wires from SPDs to
perform routine testing can lead to crossed wires or misconnections. Reversed
polarity will not damage the SPDs (which are generally symmetrical about
earth) but it may cause problems for the protected equipment.
If problems do develop on a particular loop, then the SPD involved must be
removed from the circuit and checked for end-to-end resistance and line-toline
and line-to-earth insulation as described in the first paragraph of this
section. Should the unit fail any of these tests it must be replaced and
returned to Eaton’s MTL product line for repair.
Application problems can arise for the following reasons:–
(a) Using an SPD with the working voltage selected or set so low that signal
clipping occurs.
(b) Failing to take account of the SPD end-to-end resistance when setting loop
supply voltages.
(c) The SPD shunt capacitance causing signal loss or modification. (d) SPD
incorrectly wired into the loop.
7.3 Repair
The SD range is completely encapsulated and hence individual units can not be
repaired. Most other MTL SPDs can be repaired using conventional workshop
techniques (although any site repairs will invalidate the warranty).
MAINS SPD FIELD TESTING
8.1 Introduction
The following checks can be made, with the help of a multimeter:–
a) For an in-line SPD, the voltage-limiting component function (section 8.2)
and series continuity (section 8.3)
b) For a parallel (or ‘shunt’) SPD, the voltage-limiting component function
(section 8.2)
It is usually neither practical nor necessary to test the RFI filter
characteristic.
8.2 Checking voltage-limiting component function
These tests can be applied to both in-line and parallel SPDs.
8.2.1 Checking resistance
The simplest and safest method is to disconnect the SPD from the supply and
use a multimeter to check varistor failure by measuring the resistance between
the live-neutral terminals (figure 27) and the live-earth and neutral earth
terminals (figure 28). The live-neutral resistance should be close to 1MW, the
value of the safety bleed resistor; a significantly lower resistance indicates
probable varistor failure. For the live-earth and neutral-earth checks, the
resistance should normally exceed 10M.
8.2.2 Checking leakage current
The no-load current consumption can be checked with the circuit shown in
figure 29. This provides a more definitive indication of possible component
failure but is potentially less safe to apply.
Note: This test MUST only be performed by competent personnel taking all
necessary precautions – including the ESSENTIAL use of the safety isolation
transformer indicated in the diagram.
8.2.3 Checking low-current limiting voltage
If a high-voltage low-current source (or test set) is available, an accurate
assessment can be made of the voltage-limiting components by measuring their
low-current limiting voltage as shown in figure 30.
Note: a suitable high-voltage low-current source is provided by an
insulation tester providing at least 500V current limited at approximately
1mA.
8.3 Checking series continuity
This test can only be applied to in-line SPDs.
Continuity is checked (see figure 31) by using a multimeter to measure
resistance between the input and output terminals (i.e. live-live and neutral-
neutral). Allowing for meter lead resistance, this should be less than 1M.
AUSTRALIA
MTL Instruments Pty Ltd,
10 Kent Road, Mascot, New South Wales, 2020, Australia
Tel: +61 1300 308 374
Fax: +61 1300 308 463
E-mail: mtlsalesanz@eaton.com|
BeNeLux
MTL Instruments BV
Ambacht 6, 5301 KW Zaltbommel
The Netherlands
Tel: +31 (0)418 570290
Fax: +31 (0)418 541044
E-mail: mtl.benelux@eaton.com| CHINA
Cooper Electric (Shanghai) Co. Ltd
955 Shengli Road, Heqing Industrial Park
Pudong New Area, Shanghai 201201
Tel: +86 21 2899 3817
Fax: +86 21 2899 3992
E-mail: mtl-cn@eaton.com
---|---|---
FRANCE
MTL Instruments sarl,
7 rue des Rosiéristes, 69410 Champagne au Montd’Or
France
Tel: +33 (0)4 37 46 16 53
Fax: +33 (0)4 37 46 17 20
E-mail: mtlfrance@eaton.com| GERMANY
MTL Instruments GmbH,
Heinrich-Hertz-Str. 12, 50170 Kerpen, Germany
Tel: +49 (0)22 73 98 12 – 0
Fax: +49 (0)22 73 98 12 – 2 00
E-mail: csckerpen@eaton.com| INDIA
MTL India,
No.36, Nehru Street, Off Old Mahabalipuram Road
Sholinganallur, Chennai – 600 119, India
Tel: +91 (0) 44 24501660 /24501857
Fax: +91 (0) 44 24501463
E-mail: mtlindiasales@eaton.com
ITALY
MTL Italia srl,
Via San Bovio, 3, 20090 Segrate, Milano, Italy
Tel: +39 02 959501
Fax: +39 02 95950759
E-mail: chmninfo@eaton.com| JAPAN
Cooper Crouse-Hinds Japan KK,
MT Building 3F, 2-7-5 Shiba Daimon, Minato-ku,
Tokyo, Japan 105-0012
Tel: +81 (0)3 6430 3128
Fax: +81 (0)3 6430 3129
E-mail: mtl-jp@eaton.com| NORWAY
Norex AS
Fekjan 7c, Postboks 147,
N-1378 Nesbru, Norway
Tel: +47 66 77 43 80
Fax: +47 66 84 55 33
E-mail: info@norex.no
RUSSIA
Cooper Industries Russia LLC
Elektrozavodskaya Str 33
Building 4
Moscow 107076, Russia
Tel: +7 (495) 981 3770
Fax: +7 (495) 981 3771
E-mail: mtlrussia@eaton.com| SINGAPORE
Cooper Crouse-Hinds Pte Ltd
No 2 Serangoon North Avenue 5, #06-01 Fu Yu Building
Singapore 554911
Tel: +65 6 645 9864 / 5
Fax: +65 6 487 7997
E-mail: sales.mtlsing@eaton.com|
SOUTH KOREA
Cooper Crouse-Hinds Korea
7F. Parkland Building 237-11 Nonhyun-dong Gangnam-gu,
Seoul 135-546, South Korea.
Tel: +82 6380 4805
Fax: +82 6380 4839
E-mail: mtl-korea@eaton.com
UNITED ARAB EMIRATES
Cooper Industries/Eaton Corporation
Office 205/206, 2nd Floor SJ Towers, off. Old Airport Road,
Abu Dhabi, United Arab Emirates
Tel: +971 2 44 66 840
Fax: +971 2 44 66 841
E-mail: mtlgulf@eaton.com| UNITED
KINGDOM
Eaton Electric Ltd,
Great Marlings, Butterfield, Luton
Beds LU2 8DL
Tel: +44 (0)1582 723633
Fax: +44 (0)1582 422283
E-mail: mtlenquiry@eaton.com|
AMERICAS
Cooper Crouse-Hinds MTL Inc.
3413 N. Sam Houston Parkway W.
Suite 200, Houston TX 77086, USA
Tel: +1 281-571-8065
Fax: +1 281-571-8069
E-mail: mtl-us-info@eaton.com
Eaton Electric Limited,
Great Marlings, Butterfield, Luton
Beds, LU2 8DL, UK.
Tel: + 44 (0)1582 723633
Fax: + 44 (0)1582 422283
E-mail: mtlenquiry@eaton.com
www.mtl-inst.com
© 2016 Eaton
All Rights Reserved
Publication No. AN904-1002 Rev I 211016
October 2016
EUROPE (EMEA):
+44 (0)1582 723633
mtlenquiry@eaton.com
THE AMERICAS:
+1 800 835 7075
mtl-us-info@eaton.com
ASIA-PACIFIC:
+65 6 645 9888
sales.mtlsing@eaton.com
The given data is only intended as a product description and should not be
regarded as a legal warranty of properties or guarantee. In the interest of
further technical developments, we reserve the right to make design changes.
October 2016
AN904-1002 Rev I