Current LED21ED17/YXX Type B LED Lamp 120-277V Installation Guide

June 12, 2024
current

Current LED21ED17/YXX Type B LED Lamp 120-277V

Product Information

The LEDL100 is a Type B LED Lamp designed for use with a voltage range of 120-277V. It is available in three different wattages: LED21ED17/YXX, LED35ED17/YXX, and LED45ED17/YXX. This lamp is not intended for use in emergency light fixtures or exit signs. It is important to follow the instructions provided to avoid personal injury, product damage, and the voiding of the warranty. The lamp should not be connected to a voltage higher than 277 volts and should not be used with a ballast or igniter. Using a HID ballast or igniter will void the warranty. Additionally, installation with voltage above 277 VAC or with a phase cut dimmer will also void the warranty. Operating the lamp at high ambient temperatures may reduce its lifespan. The product comes with a fuse kit that should be installed on the line as shown in the schematic diagram. Only use a Type 2AG, 4A, 350Vac, Slow Blow fuse or its equivalent for replacement.

Product Usage Instructions

  1. Before starting, turn off the power to the fixture and remove the existing HID lamp from the fixture.
  2. Open the fixture’s junction box and locate the line and neutral wires, as well as the socket black and white wires. Disconnect these wires from the HID ballast, ignitor, and capacitor (if present) at the locations marked with CROSS marks in the schematic diagram.
  3. Using UL listed wire connectors, connect the line wire to the black wire from the socket and the neutral wire to the white wire from the socket.
  4. Install the fuse kit from the package onto the line as shown in the schematic diagram.
  5. Close the fixture’s junction box and clean the area before applying the re-lamp caution label to a visible location on the fixture.
  6. Optional: If your application requires an E39 mogul base, screw the adapter (not included) onto the lamp base, not into the socket. Tighten securely.
  7. For open fixtures or fixtures with wire cages, install the Current HID LED retrofit lamp into the socket.
  8. For enclosed fixtures, install the Current HID LED retrofit lamp into the socket and close the fixture.
  9. Turn on the power to the fixture.

RISK OF FIRE OR ELECTRIC SHOCK
This product is rated 120-277 V, however in the US it should only be used on branch circuits permitted in Section 210.6 of the US National Electrical Code for E26/E39/EX39 lamp holders. LED Retrofit Kit installation requires knowledge of luminaire electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician. Install this kit only in luminaries that have the construction features and dimensions shown in the drawings and where the input rating of the retrofit kit does not exceed the input rating of the luminaire. To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects. Do not make or alter any open holes in an enclosure of wiring or electrical components during kit installation. Installers should examine all parts that are not intended to be replaced by the retrofit kit for damage and replace any damaged parts prior to installation of the retrofit kit. THE RETROFIT KIT IS ACCEPTED AS A COMPONENT OF A LUMINAIRE WHERE THE SUITABILITY OF THE COMBINATION SHALL BE DETERMINED BY AUTHORITIES HAVING JURISDICTION. PRODUCT MUST BE INSTALLED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH THE APPLICABLE AND APPROPRIATE ELECTRICAL CODES. THE INSTALLATION GUIDE DOES NOT SUPERSEDE LOCAL OR NATIONAL REGULATIONS FOR ELECTRICAL INSTALLATIONS. Installers should not disconnect existing wires from lamp holder terminals, but should cut existing lead wires away from the lamp holder and make new electrical connections to lamp holder lead wires by employing applicable connectors. Do not use with ballast or igniter. Ensure Misapplication fuse and fuseholder are connected between Phase or Hot lead and the eyelet connection of the lamp holder per the wiring diagram. Not for use with dimmers. Install this kit only in a luminaire with a lamp compartment greater than 78 cubic inches, approximately 3.5 x 3.5 x 6.5 inches rectangular or 6 inch diameter x 6.5 inch deep cylindrical shaped area.

CAUTION
RISK OF FIRE OR ELECTRIC SHOCK

  • Apply provided re-lamp caution label onto the fixture in a location where readily visible by the user during and after installation. RISK OF FIRE OR ELECTRIC SHOCK, OVERHEATING OR LAMP DAMAGE
  • Check the condition of the socket in the fixture. If the socket shows signs of corrosion, arcing, or any other type of damage like the pictures below, replace the socket with a new one.
  • Ensure EX39 socket is spring loaded to securely grip lamp screw base. Tighten lamp securely into socket

Save These Instructions

Use only in the manner intended by the manufacturer. Not for use in emergency light fixtures or exit signs. If you have any questions, contact the manufacturer at 1-800-327-0097. This lamp operates from 120-277V mains. Do not connect to voltage higher than 277 volts. Do not use with ballast or igniter. Use with HID ballast or igniter voids the warranty. Type B LED HID retrofit lamp installation with voltage above 277 VAC or phase cut dimmer voids the warranty. Operation at high ambient temperature may reduce lamp life. Replace fuse only with Type 2AG, 4A, 350Vac, Slow Blow, Littelfuse part number 0209004.MXP or equivalent.

Parts List

  • 1 LED lamp
  • 1 fuse kit
  • 1 re-lamp caution label

Tools Required

  • Screwdriver
  • Wire stripper/cutter
  • UL listed wire connectors

Installation Instructions

  1. Turn off power to the fixture. Remove existing HID lamp from the fixture.
  2. Open the fixture’s junction box and bypass the HID ballast, ignitor (if there) and the capacitor (if there) by disconnecting the line and neutral wires and socket black and white wires in the locations with “CROSS” marks in the schematic diagram.
  3. Connect the line to the black wire from the socket and the neutral to the white wire from the socket with UL listed wire connectors. The fuse kit in the package should be installed on the line as shown in the schematic diagram.
  4. Close the fixture’s junction box. Clean the area before applying the re-lamp caution label to a visible location on the fixture.
  5. Optional: For E39 mogul baseapplications, screw adapter (not included) onto lamp base, not into socket. Tighten securely.

For open fixture and fixture with wire cage
(Illustration below is one example.)

Install Current HID LED retrofit lamp into the socket.
For enclosed fixture
(Illustration below is one example.)

Install Current HID LED retrofit lamp into the socket and close the fixture.

Turn on power to th fixture.

www.LED.com. ©. 2023 Current Lighting Solutions, LLC. Tous les droits sont réservés. GE et le monogramme GE sont des marques de commerce de General Electric Company et sont utilisés sous licence. Les informations fournies peuvent être modifiées sans préavis. Toutes les valeurs sont des valeurs de conception ou typiques lorsqu’elles sont mesurées dans des conditions de laboratoire.

BEFORE YOU BEGIN
Read these instructions completely and carefully. To avoid personal injury and/or product damage, all of the instructions below must be followed

References