GE current IND624 LED Exit or Stair Sign Instruction Manual
- June 3, 2024
- GE current
Table of Contents
GE current IND624 LED Exit or Stair Sign
IMPORTANT SAFEGUARDS
WARNING: RISK OF ELECTRIC SHOCK – NEVER CONNECT TO, DISCONNECT FROM, OR
SERVICE WHILE EQUIP-MENT IS ENERGIZED.
WARNING : FAILURE TO FOLLOW THESE INSTRUCTIONS AND WARNINGS MAY RESULT IN
DEATH, SERIOUS INJURY OR SIGNIFICANT PROPERTY DAMAGE – For your
protection, read and follow these warnings and instructions carefully before
installing or maintaining this equipment. These instructions do not attempt to
cover all installation and mainte-nance situations.
WARNING: RISK OF FIRE – Lamps are hot. Keep combustible material away
from hot parts. Observe lamp manufacture warnings, recommendations and
restrictions on lamp operation and maintenance. Make sure lamps are correctly
installed.
- All service shall be performed by qualified service personnel. This product must be installed and maintained in accordance with the applicable installation codes by a person familiar with the construction and operation of the product and the hazards involved.
- This product must be installed in accordance with the applicable installation codes and ordinances.
- Before wiring to power supply, turn off electricity at fuse or circuit breaker.
- Disconnect A.C. power and unplug battery before servicing.
- Consult your local building code for approved wiring and installation.
- May be used outdoors under cover. (0°C-50°C)
- Do not let power supply cord touch hot surfaces.
- Do not mount near gas or electric heater.
- Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
- The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
- Do not use this equipment for other than intended use.
- The AC voltage rating of this equipment is specified on the product label. Do not connect equipment to any other voltage.
IMPORTANT:
When relamping, only use LED lightsource specified in the sign. Using other LED light source may result in transformer damage or unsafe conditions. For battery backup models, battery in the unit may not be fully charged. After electricity is connected to unit, let the battery charge up for at least 24-hrs. The normal operation of the unit should take effect.
Wiring Diagrams
WARNING:
Unused wires must be capped using enclosed wire nuts.
INSTALLATION INSTRUCTIONS
GENERAL
This Exit may be shipped with an EXTRA FACE PLATE & RED LENS to make the sign double face. Replace the BACK PLATE with the the extra face plate & lens at the start of the installation process if the application calls for a double face sign.
BACK MOUNT INSTALLATION
Fig 1
-
Step 1. Extend unswitched 24-hour AC supply of rated voltage to junction box (NOT INCLUDED). Leave at least 18 inches of slack.
-
Step 2. Remove retainer screw from side of sign. Remove side panel and lens.
-
Step 3. Remove 7/8″ DIA KO and required mounting pattern from back plate. Use bushing provided to protect wires from metal edge. Secure wires using cable tie. Feed wires through 7/8″ DIA KO bushing.
-
Step 4. Connect ground in accordance with local codes. Connect power supply wires per schematic and color code as follows:
LINE 100 300V-ORANGE; NEUTRAL-WHITE. -
Step 5. Mount signs securely to junction box using mounting plate and screws provided.
-
Step 6. For battery backup models, connect battery leads. Turn ON AC supply and operate test switch. LED lamps will stay on in AC mode and remain on in Emergency mode. For AC only models, turn ON AC Supply.
-
Step 7. Carefully slide glass into sign frame channel and replace end panel and retainer screw.
CEILING or END MOUNT
Fig 2
- Step 1. Follow steps1 to 2 of backmount instructions.
- Step 2. Knock out the appropriate mounting pattern on top or side of unit to accommodate canopy. Use plastic bushings provided to protect wires from metal edge.
- Step 3. Fasten canopy to sign by means of (2) screws, star washers and nuts.
- Step 4. Secure mounting plate to junction box by choosing proper slots and using screws supplied with junction box. (NOT INCLUDED)
- Step 5. Feed wires through canopy and connect to power supply following step 4 of back-mount instructions.
- Step 6. Mount sign with canopy to Junction box using screws provided.
- Step 7. Fllow steps 6 to 7 of back-mount instructions.
OPERATION
- To test the equipment, depress the TEST switch. The CHARGE indicator will go out and the EXIT section will remain iluminated.
- Release the TEST switch. The EXIT section switches to AC mode and the CHARGE indicator will lluminate. The automatic charger will return and maintain the battery in a fully charged state.
NOTE: Allow the battery to charge for a minimum of 24 hours after installation or after a power failure before conducting a 90 minute test (see TESTING section).
MAINTENANCE:
CAUTION: Always turn OFF AC power to the equipment before servicing. Servicing should be performed only by a qualified service technician. Only manufacturer SUPPLIED or APPROVED replacement parts must be used.
BATTERY
The battery supplied in this equipment requires no maintenance. However, it should be tested periodically (see TESTING section) and replaced when it no longer operates the connected fixtures for the duration of a 30-second or 90-minute test.
TESTING:
NFPA 101, Life Safety Code requires that all emergency lighting equipment be tested every 30 days for a minimum of 30 seconds and tested yearly for a full 90-minute duration. Written records of testing are to be kept for examination by the authority having jurisdiction.