Sentronic Electronic Pressure Regulator Installation Guide
- June 4, 2024
- Sentronic
Table of Contents
Electronic Pressure Regulator
Installation Guide
PLUS Sentronic Electronic Pressure Regulator General
General
Sentronic PLUS is a 3-way proportional valve with digital control. The Data
Acquisition Software (DaS) that comes with Sentronic PLUS can be used to
adjust the valve’s control parameters to a specific application.
Command signals, feedback signals and control parameters can be viewed in
real-time and adjusted as required for an application. Sentronic PLUS can be
configured for dual loop control of process variables such as flow, force,
speed, RPM, and temperature.
Constru ction
Direct-operated poppet valve Body: See table below.
Internal parts: Stainless steel and brass Seals: FPM (fluoroelastomer) and NBR
(nitrile)
Specifications
Fluids: Air or neutral gas, filtered at 50 µm, condensate-free, lubricated
or unlubricated
Specifications
Fluids: Air or neutral gas, filtered at 50 µm, condensate-free, lubricated or
unlubricated
Ports: 1/8 – 1/4 – 1/2 – 1 (NPT or GTap)
Max. operating pressure: See table below.
Control range: See table below.
Temperature / fluid: 32ºF – 140ºF (0ºC – 60°C)
Temperature / ambient: 32ºF – 140ºF (0ºC – 60°C)
Command signal – analog: 0 – 10 V (impedance 100 KΩ) 0 – 20 mA/4 – 20 mA
(impedance 250 Ω)
Hysteresis: 1% of span
Linearity / pressure measurement: ± 0.5% of span
Repeatability: ± 0.5% of span
EXPLOSION SAFETY
Safety code: Ex II 3D Ex tc IIIC T135°C Dc X
Ex II 3G EX ec IIC T4 Gc X, 0 ≤ Ta ≤ = 50°C
Electrical Characteristics
Nominal Diameter DN (mm)| Voltage *| Max. Power (W)| Max. Current (mA)|
Insulation Class| Degree of Protection| Electrical Connection
---|---|---|---|---|---|---
1| 24 VDC = ±10%| 12| 500| F| IP 65| 5-pin M12 connector
or 7-pin DIN connector
3| 24 VDC = ±10%| 12| 500| F| IP 65| 5-pin M12 connector
or 7-pin DIN connector
6| 24 VDC = ±10%| 247)| 10001| F| IP 65| 5-pin M12 connector
or 7-pin DIN connector
12| 24 VDC = ±10%| 34| 1400| F| IP 65| 5-pin M12 connector
or 7-pin DIN connector
20| 24 VDC = ±10%| 44| 1800| F| IP 65| 5-pin M12 connector
or 7-pin DIN connector
* Max. ripple: 10 %
Specifications
∅
Ports| ∅
Orifice DN (mm)| Flow
---|---|---
Cv Flow Factor (lc Nm3/h)| at 6 Bar (I/min – ANR)
1/8 NPT or GTap| 1| 0.032 (0.028)| 30
1/8 NPT or GTap| 3| 0.21 (0.18)| 210
1/4 NPT or GTap| 6| 0.70 (0.60)| 700
1/2 NPT or GTap| 12| 1.39 (1.20)| 1400
1 NPT or GTap| 20| 5.57 (4.80)| 5600
Notes:1) For DN6, brass version Gori/1.8A, 44W
How to Order
Notes:1) 7-pin DIN connector allows crossover from 833-354 or 601 Series
analog Sentronic version; ships with field installable connector.2) Up to max.
12 bar.3) Only for pressure ranges from 30 to 50 4) bar. Feedback input is
needed for dual loop units. 5) Only for DN3 & DN6 6) Only for DN6 body type G
or H. Other versions are available on request. 7) For DN6, brass version
Gori/1.8A, 44W
Dimensions: Inches (mm), Weight in lbs. (kg)
1/8 NPT or GTap (DN1 and DN3)
Weight: 1.21 (0.55)
1/4 NPT or GTap
Weight: 1.87 (0.85)A) Thread M5 – depth 10 (on the opposite
side); tapped through hole for an M4 screw.
1/2 NPT or GTap
Weight: 3.64 (1.65)A) Thread M5 – depth 10 (on the opposite
side); tapped through hole for an M4 screw.
1 NPT or GTap
Weight: 7.50 (3.40)
A) Thread M8 – depth 15 (on the opposite side); tapped through-hole
for an M6 screw.
Connector Pin Out
PIN | Description |
---|---|
1 | +24 VDC Supply |
2 | Command Signal |
3 | +0 VDC Common (Supply) |
+0 VDC Common (Command Signal)* | |
4 | Analog output (Feedback) |
5 | Digital output (Pressure switch) |
Body | EMV screen |
*A 6-wire cable with a separate common for the command signal is used for cable lengths over 2 m to minimize the voltage drop for the command signal.
Accessories
5 Pin 12mm FEMALE Straight Field Attachable Connectors | Model Number |
---|---|
PG 9 Cable Gland | TCO5F20000000000 |
--- | --- |
5 Pin 12mm FEMALE 90 DEGREE Field Attachable Connectors •
PG 9 Cable Gland| TD05F20000000000
Micro Female 5 Pole Straight 6 Wire 24 AWG, Shielded|
---|---
3 Meter TCO503MMS000671 Y|
5 Meter| TCO505MMS000671Y
Micro Female 5 Pole 90 Degree 6 Wire 24 AWG Euro Color Code, Shielded|
---|---
3 Meter TD0503MMS000671Y|
5 Meter| TD0505MMS000671Y
PC Software & Cable Connectors| Model Number
---|---
DaS Light: Data Acquisition Software for SentronicD – basic parameters – free
download at Emerson.com/AVENTICS; full version upon request| Website Download
DaS Expert: Data Acquisition Software for SentronicD – full parameters|
Consult Factory
Parameter adapter USB, lm cable (this connector or 88100732 required for DaS
software usage)| N50930300100000
RS 232 cable converter; 2m cable with 9-pin Sub-D I| 88100732
Installation and Operating Instructions
-
Before putting it into operation carefully check all electrical connections and the supply voltage (24 VDC ±10 %).
Overload can destroy the electronics. Recommended pre-fuse T2.5 A. -
The electrical connection is made with a round connector M12x1. The connector must meet the requirements of DIN 60079-15. The product was tested with connector code no. 88100729.
WARNING:
Do not disconnect the plug while under voltage!
When disconnected from power, use supplied protection cover to ensure IP protection. -
Use shielded cables for the electrical connection of the valve. The shield, connector, and control cabinet must be EMC compliant. The valve body must be electrically connected to the ground (PE, machine ground). Do not run control cables parallel to high-voltage lines or servo-motor control cables.
-
Min. wire cross-section of supply voltage cable: 0.50 mm 2.
For longer cabling distances use larger cross-section cables as required. -
Make sure that the valve is under pressure when a setpoint signal is applied to the valve (applying a setpoint signal with no pressure on the valve will cause it to overheat).
-
Valve orientation – any; preferred orientation is coil up, especially when a dry condensate-free air supply may not be maintained.
-
The valve is factory adjusted.
-
The product must be returned to the factory for repair.
Warning
These products are intended for use in industrial compressed air systems only.
Do not use these products where pressures and temperatures can exceed those
listed under SPECIFICATIONS.
Before using these products with fluids other than those specified, for non-
industrial applications, life-support systems, or other applications not
within published specifications, consult Numatics.
Through misuse, age, or malfunction, components used in fluid power systems
can fail in various modes.
The system designer is warned to consider the failure modes of all component
parts used in fluid power systems and to provide adequate safeguards to
prevent personal injury or damage to equipment in the event of such failure.
System designers must provide a warning to end users in the operating manual
if protection against a failure mode cannot be adequately ensured.
System designers and end users are cautioned to review specific warnings found
in instruction sheets packed and shipped with these products.
Electrical Connection
- The valve must only be supplied with 24V DC at a tolerance of +15%/-10% and a max. ripple of 10% (no supply via diode bridge). Overvoltage or a ripple rate exceeding these tolerances can damage the electronics.
- The max. current at the digital output is 200 mA/4.8W (PNP output). The output is protected against short circuits and overload.
- If a relay (inductive load) is connected to the digital output, a freewheel diode or a varistor must be used.
- A shielded cable must be used for protection against interference and EMC.
- The valve housing must be connected to the ground potential with low resistance via the ground connection (ØM4).
The eyelet of the grounding cable must be inserted between two toothed washers and fastened with a screw (M4). The tightening torque corresponding to the screw must be observed.
Visit our website atEmerson.com/AVENTICS
Read User Manual Online (PDF format)