BOSCH BMAC Series Multi Position Cased Coils Instruction Manual

June 12, 2024
Bosch

BOSCH BMAC Series Multi Position Cased Coils

Product Information

  • Product Name: Bosch Multi-Position Cased Coils
  • Series: BMAC Series
  • Compatibility: Cooling and Heat Pump Compatible
  • Manufacturer: Bosch Thermotechnology Corp.
  • Data Subject to Change: April 2023

Product Usage Instructions

Safety Instructions:

  • Read the safety precautions before installation.
  • Warnings in the document are identified by a warning triangle printed against a grey background.
  • Keywords at the start of a warning indicate the type and seriousness of the risk.

General:

  • The coils are approved for up flow or downflow, vertical, and horizontal installation.
  • If used with a furnace, the coil must be installed downstream (in the air outlet) of the furnace.

Codes & Regulations:

  • The product is designed and manufactured to comply with national codes.
  • Installation should be done in accordance with national and local codes/regulations.
  • The responsibility of compliance lies with the installer.
  • The manufacturer assumes no responsibility for equipment installed in violation of any codes or regulations.

Key to symbols and safety instructions

Key to symbols
Warnings

Warnings in this document are identified by a warning triangle printed against a grey background.
Keywords at the start of a warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken.

The following keywords are defined and can be used in this document:

  • DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
  • WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
  • CAUTION indicates a hazardous situation which, if not avoided, could result in minor to moderate injury.
  • NOTICE is used to address practices not related to personal injury.

Important information
This symbol indicates important information where there is no risk to people or property.

Safety
Please read safety precautions before installation

WARNING:

  • These instructions are intended as an aid to qualified licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance and possibly resulting in fire, electrical shock, property damage, personal injury or death.
  • Disconnect all power to the unit before starting any service and maintenance. Failure to do so could cause severe electrical shock resulting in personal injury or death.

WARNING: INSTALLATION REQUIREMENTS

  • Installation or servicing of this unit can be hazardous due to parts, components and system pressure. Qualified and proper trained service personnel should perform installation and repair . Failure to do so could cause severe electrical shock resulting in personal injure or death.

General

These coils are approved for up flow or downflow, vertical and horizontal installation. For furnace applications, the coil must be installed downstream (in the air outlet) of the furnace.

Codes & regulations
This product is designed and manufactured to comply with national codes. Installation in accordance with such codes and/or prevailing local codes/regulations is the responsibility of the installer . The manufacturer assumes no responsibility for equipment installed in violation of any codes or regulations.
The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and disposal of refrigerants. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. Should you have any questions please contact the local office of the EPA.

Inspection upon unit arrival
As soon as unit is received, it should be inspected and noted for possible shipping damage during transportation. It is carrier ’s responsibility to cover the cost
of shipping damage. Manufacturer or distributor will not accept a claim from contractors for any transportation damage.

Clearances
Following clearances should be provided during installation:

  1. Maintenance and service access, including coil cleaning and coil assembly removal
  2. Refrigerant piping and connections
  3. Condensate drain line

For ensure the proper installation, Select a solid and level site. Ensure enough space required for installation and maintenance.

Dimensional data

Figure 3

Table 1

Model Dimensions inch [mm] Weight /Shipping (LBS [kg])
Unit Height “H” Unit Width “W” Supply Duct “A” “W1” Liquid line /Vapor

Line
BMAC2430ANTD| 20 [508]| 14½ [368]| 13 [330]| 13½ [343]| ⅜ / ¾| 45.6/62.1 [20.7/28.2]
BMAC2430BNTD| 20 [508]| 17½ [445]| 16 [407]| 16½ [419]| ⅜ / ¾| 48/66 [21.8/29.9]
BMAC3036ANTD| 20 [508]| 14½ [368]| 13 [330]| 13½ [343]| ⅜ / ¾| 45.6/62.1 [20.7/28.2]
BMAC3036BNTD| 20 [508]| 17½ [445]| 16 [407]| 16½ [419]| ⅜ / ¾| 48/66 [21.8/29.9]
BMAC3036CNTD| 20 [508]| 21 [553]| 19½ [495]| 20 [508]| ⅜ / ¾| 51.8/74.3 [23.5/33.7]

Figure 4

Model Dimensions inch [mm] Weight /Shipping (LBS [kg])
Unit Height “H” Unit Width “W” Supply Duct “A” “W1” Liquid line /Vapor

Line
BMAC4248BNTF| 30 [762]| 17½ [445]| 16 [407]| 16½ [419]| ⅜ /⅞| 74.3/93.2 [33.7/42.3]
BMAC4248CNTF| 30 [762]| 21 [533]| 19½ [495]| 20 [508]| ⅜ /⅞| 74.3/97.8 [33.7/44.4]
BMAC4248DNTF| 30 [762]| 24½ [622]| 23 [584]| 23½ [597]| ⅜ /⅞| 78/102.9 [35.4/46.7]

Table 2

Figure 5

Model Dimensions inch [mm] Weight /Shipping (LBS [kg])
Unit Height “H” Unit Width “W” Supply Duct “A” “W1” Liquid line /Vapor

Line
BMAC4860CNTF| 30 [762]| 21 [533]| 19½ [495]| 20 [508]| ⅜ /⅞| 83/106.7 [37.6/48.4]
BMAC4860DNTF| 30 [762]| 24½ [622]| 23 [584]| 23½ [597]| ⅜ /⅞| 86.4/111.3 [39.2/50.5]

Table 3

Installation Instructions

Parts
Contact your distributor for authorized replacement parts.

Pre-installation instructions
Carefully read all instructions for installation prior to installing product. Make sure each step or procedure is understood and any special considerations are taken into account before starting installation. Assemble all tools, hardware and supplies needed to complete the installation. Some items may need to be purchased locally. Make sure everything needed to install the product is on hand before starting.

Installation and trap connection

  • See Fig.6 & 7 for coil installation and drain connection.

  • Installation steps for cased coil:

    • Shut off or disconnect gas furnace’s power and remove gas pipe if necessary.

    • Disconnect and remove a sufficient portion of the supply ductwork to provide clearance for the cased coil.

    • Ensure that the coil is level. Seal the gap between coil and furnace.
      See Figure 6 & 7. In case that coil and furnace sizes are not matched, use proper size of sheet metal or other material to fill the gap and seal the gap to prevent air leak

    • Reconnect the ductwork to the coil case, and seal any leakage.

    • Reconnect power line on gas furnace, turn on the furnace to check any sign of leakage.

Figure 6

Figure 7

Drain application

Condensate drain piping
Consult local codes for special requirements.
To provide extra protection from water damage, it is always recommended to install an additional drain pan, provided by installer, under the entire unit with a separate drain line. Manufacturer will not be responsible for any damages due to the failure to follow these recommendations.

Plastic drain pan installation

WARNING:

  • Do not use the coil pan shipped with the unit on OIL furnaces or any application where the temperature of the drain pan may exceed 275 °F . A field fabricated metal drain pan can also be used for these type of applications. Failure to follow this warning may result in property damage and/or personal injury.

The coil drain pan has a primary and an optional secondary drain with 3/4” NP T female connections; use either PVC or copper pipe and hand tighten to a torque of approximately 37 in-lbs. to prevent damage to the drain pan connection. An insertion depth between .355 to .485 inches (3-5 turns) should be expected at this torque setting.
Use male 3/4” NPT threaded fitting for outside connection and make sure the drain holes are not blocked.
Insulation may be needed for drain line to prevent sweating.
Drain pan has two drain connections on each side to provide flexibility of connection and drainage. Make sure pan has proper pitch and plugged if second connection is not used.
If the secondary drain line is required, run the line separately from the primary drain and terminate it where it can be easily seen.
Water coming from this line means the coil primary drain is plugged and needs clearing.
Install a trap in the drain line below the bottom of the drain pan. If using a copper drain line, solder a short piece of pipe to the connector before installing a drain fitting. DO NO T over torque the 3/4” copper connector to the plastic drain connection. Use a wet rag or heatsink material on the short piece to protect plastic drain pan, complete the drain line installation (Fig.8 ). Use (Fig.9) as a template for typical drain pipe routing. This figure shows how to avoid interference with vent piping.

Figure 8

Figure 9

Refrigerant connections

NOTICE:

  • Gently remove the sealing plug of vapor line, use one wrench to fix the valve base, loosen the nut with another wrench,take out the flange pad and and sealing ring. The nitrogen pressure is about 10 PSIG.

To prevent refrigerant leak, use proper tools to ensure clean, burr-free cut.

NOTICE:

  • TXV bulb MUST be protected (wrapped with wet rag) or removed, while brazing the tubing. Overheating of the sensing bulb will affect the functional characteristics and performance of the comfort coil.

Use brazing shield when brazing close to the cabinet surface and wet rag to protect rubber grommet. Brazing alloy should be at least 5% silver content.

Airflow performance [CFM vs pressure drop]:

Model| | | | Pressure Drop (Inches of Water)| | |
---|---|---|---|---|---|---|---
0.05| 0.1| 0.15| 0.2| 0.25| 0.3| 0.35| 0.4
BMAC2430ANTD| 307| 485| 618| 729| 823| 911| 991| 1063
BMAC2430BNTD| 327| 527| 682| 810| 925| 1024| 1122| 1217
BMAC2430CNTD| 360| 585| 748| 893| 1019| 1132| 1238| 1348
BMAC3036ANTD| 307| 485| 618| 729| 823| 911| 991| 1063
BMAC3036BNTD| 327| 527| 682| 810| 925| 1024| 1122| 1217
BMAC3036CNTD| 360| 585| 748| 893| 1019| 1132| 1238| 1348
BMAC4248BNTF| 456| 638| 810| 953| 1077| 1191| 1284| 1390
BMAC4248CNTF| 505| 726| 932| 1098| 1244| 1375| 1494| 1604
BMAC4248DNTF| 533| 857| 1105| 1319| 1509| 1675| 1824| 1956
BMAC4860CNTF| 439| 699| 906| 1071| 1224| 1362| 1487| 1589
BMAC4860DNTF| 466| 764| 978| 1157| 1313| 1466| 1590| 1695

Table 2 Pressure drop for cooling and heat pump coils
*Data based on wet coil with entering air at 80°F DB / 67°F WB without air filter.

Water blow-off could occur in certain installation positions if the airflow setting exceeds the maximum values listed.

Model / Coil| Maximum airflow setting,CFM|
---|---|---
Upflow| Horizontal Left| Downflow| Horizontal Right
BMAC2430ANTD| 1125| 1050| 1050| 1125
BMAC2430BNTD| 1125| 1050| 1050| 1125
BMAC2430CNTD| 1250| 1200| 1050| 1250
BMAC3036ANTD| 1200| 1050| 1050| 1200
BMAC3036BNTD| 1250| 1200| 1050| 1250
BMAC3036CNTD| 1250| 1200| 1050| 1250
BMAC4248BNTF| 1800| 1800| 1700| 1500
BMAC4248CNTF| 1800| 1800| 1700| 1700
BMAC4248DNTF| 1800| 1800| 1700| 1800
BMAC4860CNTF| 1850| 1850| 1750| 1750
BMAC4860DNTF| 2000| 2000| 1850| 1850

Table 3

TXV replacement information

The TXV replacement options noted in this sheet supersede those in the installation guide. Please reference this sheet for all refrigerant metering options.

  1. Remove the screws and front coil panel.

  2. Remove the rubber plugs from the liquid and vapor lines.

  3. Remove relevant ties and pipe insulation.

  4. Unwrap and remove the TXV sensing bulb.

  5. Remove the equalizer tube from vapor pipe. Wrap the TXV and coil panel with a wet rag to prevent overheating while brazing. Use a shield plate to prevent the copper pollution.
    WARNING: Wrap the TXV and coil panel with a wet rag to prevent overheating while brazing; and use a shield plate to prevent the fire and copper pollution.

  6. Disconnect the input pipe ,Wrap the TXV and coil panel with a wet rag
    to prevent overheating while brazing,Use a nitrogen flow and braze all connections while brazing. Use a shield plate to prevent the copper pollution.

  7. Remove the TXV fixed screws.

  8. Replace a new TXV, wrap the TXV with a wet rag or dip into water to prevent overheating while brazing.

  9. Allow tubing to cool and pressurize line sets with 150 PSI of nitrogen to check braze connections and flow assembly for leaks. Make repairs as needed.
    Figure 10

  10. Dry the TXV.

  11. It is recommended to insulate the TXV and liquid line.

  12. Connect and secure the TXV to the coil panel, Wrap a wet rag to prevent overheating while brazing. Use a shield plate to prevent the copper pollution.

  13. Clean a straight section of the vapor line in original position. Use the straps to secure the TXV sensing bulb on top of the vapor line as picture, about 45 degrees.

  14. Insulate the entire vapor line and sensing bulb. It is also recommended to insulate the TXV and liquid line between the valve and coil to prevent condensation in hot humid environments.

  15. Replace the front coil panel and secure in place. Follow the steps in the installation guide for vacuum requirements and system start up procedures.

  16. Allow system to run for a minimum of 10 minutes in the cooling mode, charge the system to 10degrees of sub cooling, Adjust the expansion valve to achieve 9 (± 3 degrees) of superheat.

  17. Allow system to run for an additional 10 minutes to verify the sub cooling and superheat readings.

Expansion Valve (TXV) Spare Parts

Cased Coil Model Number Spare Parts Material Number – Expansion Valve (TXV)
BMAC2430ANTD 8733948235
BMAC2430BNTD 8733948235
BMAC3036ANTD 8733948235
BMAC3036BNTD 8733948235
BMAC3036CNTD 8733948235
BMAC4248BNTF 8733941929
BMAC4248CNTF 8733941929
BMAC4248DNTF 8733941929
BMAC4860CNTF 8733941932
BMAC4860DNTF 8733941932

Table 4

Figure 11

United States and Canada
Bosch Thermotechnology Corp. 50 Wentworth Avenue Londonderry, NH 03053
Tel: 866-642-3198
Fax: 954-776-5529
www.boschheatingandcooling.com
BTC 770101101 D / 04.2023

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals