Industrial Ventilator Damper
Refer to product table below for applicable product codes covered by this
document
Product Type & Application
Bradford Ventilation Industrial Ventilator Dampers are designed to be used
with the Hurricane ® and EcoPower® ventilators. Industrial Ventilation
Dampers are suitable for applications where manual or powered control of air-
flow to the ventilator is required.
Compliance with the NCC
There are no relevant clauses within the NCC for this product to comply with.
Evidence of Suitability
There are no relevant clauses within the NCC to show compliance with – refer
to the Additional Data section of this PTS for other compliance data.
Conditions of Storage, Use & Maintenance
- Store in the original packaging in a cool and dry area.
- The electronics and electrical components are designed for indoor installation only and should not come into contact with water.
- This product requires regular inspection and maintenance, which should be increased in frequency when used in harsh environments.
- Do not attempt to repair – contact Bradford Ventilation.
Refer to the product warranty at bradfordventilation.com.au for more information.
Limitations of Use
- Do not use for exhausting hazardous, abrasive, explosive materials and vapour.
- This product is not suitable for bushfire (BAL) rated areas.
- Seek technical advice from Bradford Ventilation on application suitability if unsure.
- This product is not sealed and therefore not suitable for the containment of smoke, preventing air entry or isolation of specific volumes of air.
- The products are designed to be used with Bradford Ventilation Hurricane ® and EcoPower ® ventilators only.
- IMPORTANT – Do Not Modify This Product: Performance and safety are only achieved by the product or configuration listed in this PTS.
Specific Design or Installation Instructions
- It is recommended the dampers are installed by the factory at the time of ventilator purchase. Retrofitting a damper requires the removal of the ventilator turbine and varipitch assembly, and access from above and below the roof.
- The damper is designed with clearance to the internal ventilator throat or flashing to avoid interference during operation.
- Even when the damper is closed, an adequate make-up area must be provided as per the Hurricane® and EcoPower® installation manual.
- Type 1 and Type 2 Damper do not require electrical connection for operation.
- Type 1, 2 and 5 dampers flap will fold down to open. Adequate clearance must be provided.
- Type 5 and Type 6 Damper require 240VAC or 24VAC for operation.
- Ensure that the vent and damper are installed in an area where the operation of the damper is not obstructed or restricted by the building structures.
- WARNING: Isolate power before installation. Electrical wiring must be carried out by a licensed electrician.
- Important Note: This product is not sealed – see specific advice under Limitations of Use.
For general installation guidance refer to the product installation guide at www.bradfordventilation.com.au
Product Technical Statements are referenced as suitable documentary evidence
to support the use of a product for a Performance
Requirement or a Deemed-to-Satisfy Provision of the BCA under Part A5.2(1)(f).
Document Reference: Industrial Ventilator Damper_Bradford Ventilation_PTS524_A
Industrial Ventilator Damper
Applicable Product Codes (SKU) – Type 1 Damper – Manual Butterfly Type Damper
Manual cord operated damper that allows user to control the level of
ventilation required. This split-disc manual cord is designed for
Hurricane®EcoPower® ventilators. The springs on this damper hold the disc unit
closed when the unit is not retained in the open position.
Size | 300mm | 400mm | 450mm | 500mm | 600mm | 700mm | 900mm |
---|---|---|---|---|---|---|---|
Code | 61732 | 61733 | 61734 | 61735 | 61736 | 61737 | 61739 |
Product Assembly – Type 1 Damper – Manual Butterfly Type Damper
Applicable Product Codes (SKU) – Type 2 Damper – Manual Butterfly Type
Damper with Cam Cleat
Manual cord and cleat operated damper that allows the user to control the
level of the ventilation required. This split-disc manual damper is designed
for Hurricane® and EcoPower® ventilators. The cleat allows the damper to be
locked in open whilst the springs hold the unit closed when the cleat is
released.
Size | 300mm | 400mm | 450mm | 500mm | 600mm | 700mm | 900mm |
---|---|---|---|---|---|---|---|
Code | 61740 | 61741 | 61742 | 61743 | 61744 | 61745 | 61747 |
Product Assembly – Type 2 Damper – Manual Butterfly Type Damper with Cam Cleat
CSR Bradford Locked Bag 1345 North Ryde BC NSW 1670 For further technical
advice csrbradford.com.au call 1300 850 305 or visit
csrbradford.com.au
CSR Bradford is a business division of CSR Building Products Limited MN 55 008
631 356 The contents of this brochure are copyright protected and may not be
reproduced in any form without prior written consent of CSR Bradford.
Recommendations and advice regarding the use of the products described in this
brochure are to be taken as a guide only, and are given without liability on
the part of the company or its employees. We reserve the right to change
product specifications without prior notification, please refer to the CSR
Bradford website for the latest revision of this document. The purchaser
should independently determine the suitability of the product for the intended
use and application.
Document Reference: Industrial Ventilator Damper_Bradford Ventilation_PTS524_A
Industrial Ventilator Damper
Applicable Product Codes (SKU) – Type 5 Damper – Electric Butterfly Type
Damper
An electrically operated split-disc electric damper which allows the user to
control the level of air-flow. The Type-5 damper is designed for Hurricane®
and EcoPower® ventilators. The electric dampers can be operated by a switch
(not included). The damper actuator is available in 24VAC and
Actuator Voltage | 300mm | 400mm | 450mm | 500mm | 600mm | 700mm | 900mm |
---|---|---|---|---|---|---|---|
24V AC Type | 83944 | 83945 | – | 83947 | 83948 | 83949 | 79486 |
240V AC Type | 61748 | 61749 | 61750 | 61751 | 61752 | 61753 | 61755 |
Product Assembly – Type 5 Damper – Electric Butterfly Type Damper
**Electrical Connection Diagram – Type 5 Damper – Electric Butterfly
Type Damper**
240VAC ( damper supplied with 4 pin plug)
24 VAC (Damper supplied with stripped leads)
Wire colour | Function |
---|---|
Red | System potential 24 VAC |
Purple | Actuating signal 0 VAC (Close Damper) |
Orange | Actuating signal 0 VAC (Open Damper) |
Electrical Specification – Type 5 Damper – Electric Butterfly Type Damper
Actuator Voltage| Actuator Manufacturer| Operating Voltage| Power Consumption|
Operating Time
(Opening or Closing)| Actuator IngressProtection
---|---|---|---|---|---
24V AC Type| Siemens| 24V AC ~50/60 Hz| 1W| 150 seconds| IP54
240V AC Type| Siemens| 240V AC ~50/60Hz| 1W| 150 seconds| IP54
An electrically operated single-disc electric damper which allows the user to control the level of air-flow. The Type-6 damper must be fitted into a Hurricane® or EcoPower® ventilators with a special base. The electric dampers can be operated by a switch (not included). The damper actuator is available in 24VAC and 240VAC.
Actuator Voltage | 300mm | 400mm | 450mm | 500mm | 600mm |
---|---|---|---|---|---|
24V AC Type | – | 83962 | – | 99432 | 91146 |
240V AC Type | 61756 | 61757 | 61758 | 99431 | 91145 |
Product Assembly – Type 6 Damper – Electric Disc Type Damper
Electrical Connection Diagram – Type 6 Damper – Electric Disc Type Damper
24 VAC (Damper supplied with stripped leads)
Wire colour | Function |
---|---|
Red | System potential 24 VAC |
Purple | Actuating signal 0 VAC (Close Damper) |
Orange | Actuating signal 0 VAC (Open Damper) |
Electrical Specification – Type 6 Damper – Electric Disc Type Damper
Actuator Voltage| Actuator Manufacturer| Operating Voltage| Power Consumption|
Operating Time (Opening or Closing)| Actuator Ingress
Protection
---|---|---|---|---|---
24V AC Type| Siemens| 24V AC ~50/60 Hz| 1W| 150 seconds| IP54
240V AC Type| Siemens| 240V AC ~50/60Hz| 1W| 150 seconds| IP54