Intellihot iE6 Tankless Heat Pump Water Heaters Owner’s Manual
- June 12, 2024
- Intellihot
Table of Contents
Intellihot iE6 Tankless Heat Pump Water Heaters
INNOVATION AT WORK
Introducing The Electron Series COz Powered Tankless Heat Pump Water Heater
Efficient and Healthy
Model iE1:
Heating Output: Up to 90,000 BTU/h First Hour Rating : 154 Gallonst
How Does it Work?
How Does it Work?
- CO2-based heat pump
- Touch Screen Display
- Cellular, Bluetooth, and optional BMS
- Smart Grid Ready CTA-20.:’.15 Module
- All-stainless on-demand heat exchanger
- Twin electric heating elements
- Glycol Concentration Sensor
LowestGWP
The iE1 uses CO2 refrigerant which has the lowest impact on the environment
with a Global Warming Potential (GWP) of 1, zero Ozone Depleting Potential
(ODP) and better cold weather performance.
Efficient & Healthy
The iE1 absorbs and stores energy from the air in a specially-designed thermal
battery. This energy is then used to heat water ondemand without storing it,
thereby mitigating Legionella risks. This process is both efficient and
healthy.
Grid Connection
This unit is smart grid ready which allows it to collect and store energy when
it’s most costeffective, maximizing return on investment and cutting
operational costs.
Key Features
-
Multi-Storey Ready
Suitable for high-pressure, high-rise, multi family buildings -
24/7 Factory Monitoring
Via built-in cellular connectivity and on-board predictive diagnostics -
High Temperature Capable
Produces water up to 170° F -
Power Large Buildings
Can be scaled to meet the demand of larger commercial properties by seamlessly cascading multiple units via Bluetooth -
Mitigates limescale
All-stainless heat exchanger with LJ00 times higher water velocity ( compared to tanks) mitigates limescale buildup -
Built-in Backup
Twin auxiliary electric heating elements provide redundancy and peace of mind -
Free Up Space
Can be installed indoors or outdoors -
Solar Ready
The iE1 unit is solar-ready and can be upgraded to use solar energy via an optional solar attachment within minutes.
Additional Electron Products
iE6
The iE6 heat pump unit is installed outside, and the thermal battery, iB3, is
installed inside with a simple fluid connection between them.
A key feature of the iE6 is its modular construction. This unit consists of 6
individual Heat pump units, each with its own controller and compressor.
Unlike other heat pump systems, this eliminates unnecessary doubling up of
equipment to ensure high reliability with lower upfront costs. Automatic
rotation and self-balancing ensure equal wear and tear
iB3
The iB3 is a three-pack remote thermal battery to be installed indoors in the
companion of the iE6.
The larger iE6 unit is paired with the thermal battery iB3 and installs just
like traditional boiler-tank systems simplifying installation and taking out
the guesswork. The iE6 heat pump unit is installed outside, and the thermal
battery, iB3, is installed inside with a simple fluid connection between
them..
Specifications
iE1 iE6 iB3
Type| Indoor / Outdoor, Floor Mounted| Outdoor, Floor Mounted| Indoor, Floor
Mounted
---|---|---|---
Power Source| Electric| Electric| Electric
Supply Voltage| 208 VAC, 60 Hz| 208 VAC, 60 Hz 3 phase| 208 VAC, 60 Hz 3 phase
Supply Current
| Max 75 Amps (90 Amp Breaker required), Optional models available with lower max amps (20A, 50A)| ****
Max LIO Amps
(Minimum 50 Amp Breaker required)
| ****
Max 70 Amps
(Minimum 90 Amp Breaker required)
Electrical Input| 15.LikW| 21.LikW| 36.7 kW
Heating Output| Up to 90,000 BTU/h| Up to 300,000 BTU/h|
COP| Up to Li.2| Up to Li.2|
Compressor Type| Rotary| Rotary|
Safety Devices
| Pressure Switch, Thermal Cutout,
Overheat Protection
| ****
Pressure Switch
| ****
Thermal Cutout, Overheat Protection
Resistive Heating Elements | 2x6kW | None | 3 x 12kW |
---|---|---|---|
Ambient Air Operating Range | -10°F to 110°F | -10°F to 110°F | **** |
Air Flow Requirement | 3500 CFM | 21,000 CFM | NA |
Outlet Water Temperature Range | 100°F to 170°F | 100°F to 190°F | 100°F to 170°F |
Temperature Stability | |||
First Hour Rating | 15″1 Gallons | 570 gallons when paired with one iE6 | |
Connectivity | Cellular and Bluetooth | Cellular and Bluetooth | Cellular and |
Bluetooth
---|---|---|---
Operational Modes| Efficiency, Hybrid, Electric, Self-learning| Self-
Balancing, Self-learning| Efficiency, Hybrid, Electric, Self-learning
Grid Connectivity
| Via CTA-20″15 module (customer
supplied)/ JA13/JA1Li
| Via CTA-20″15 module (customer supplied)/ JA13/ JA1Li| Via CTA-20″15 module (customer
supplied)/ JA13/JA1Li
Cascading Protocol| Masterless, Up to Li units| Masterless, Up to Li units|
Masterless, Up to Li units
Noise Level| Up to 55 dBA| Up to 60 dBA| NA
Domestic Heat Exchanger| Stainless Steel, 316L| NA| Stainless Steel, 316L
Energy Storage
| Water-Propylene-Glycol based Thermal Battery| Each iE6 can be paired with
upto Li iB3 (Thermal Battery)| Water-Propylene-Glycol based Thermal Battery
Water Inlet & Outlet Connections| 1.5″ NPT Female| 2″ NPT Female| 2″ NPT
Female
---|---|---|---
Unit Dimensions H X W X D (Inches)| 73.5 X 30.5 X 32.25| 89 X 81.5X 33.5| 70.8
X 30.5 X 9″1.5
Shipping Weight/ Unit Weight| 730 lbs / 650 lbs| 3300 lbs / 3100 lbs| 600 lbs
/ 500 lbs
Water Pressure Min/ Max (PSIG)| 30 / 160| | 30/160
Clearance
Back | 2Li” | 2Li” | 2Li” |
---|---|---|---|
Front | 30″ | 2″1″ | 30″ |
Top | 8″ | 8″ | 8″ |
Sides | 12″ | 32″ | 2Li” |
Certifications* | Energy Star, NSF 372, UL 60355-2-LI0, |
CSA,C22.2
| Energy Star, UL 60355-2-LI0, CSA C22.2| Energy Star, NSF 372, UL 60355-2-LI0,
CSAC22.2
---|---|---|---
Warranty
| 1 Year on Parts and Compressor, 3 Years on Thermal Battery| |
Note: Due to lntellihot’s Policy of continuous product improvements, design
and technical specifications are subject to change without notice. *In Process
delivering 110°F to the fixtures
FAQs
-
Why are current tank-based heat pump designs problematic?
Current tank-based designs mandate storing large volumes of water and keeping this water stratified at various temperatures. Stratification is necessary to enable tank-based heat pumps achieve COPs greater than 1.5. Unfortunately, water stagnation and stratification temperatures between 77° F – 113° F +foster the ideal conditions for the growth of Legionella bacteria. It is generally presumed that bacteriacontaminated water from this area will be “sanitized” by the hotter water above it, but this method is not guaranteed and places the burden of Legionella risk on the engineers and customers. lntellihot reinvented the Heat Pump Water Heater to fundamentally eliminate these root causes. There is no tank and water is heated on-demand, substantially mitigating Legionella risks. The result: clean, safe, healthy, and efficient hot water. -
Will the Electron series require mixing valves?
No, mixing valves are not required. The Electron series water heaters will be ASSE – 1082 compliant. The ASSE-1082 standard equates Electron Series T ankless Heaters to thermostatic mixing valves and temperature-limiting devices. Also, the Electron can control water temperature within the tolerances of ASSE 1017 / 1071 standards, and thus, no mixing valves are needed when using Electron units. -
What is the typical maintenance on these units?
The Electron iE1 is designed for long life and low maintenance. Only one item needs to be serviced at intervals indicated by a “Maintenance Alert” bar on the display. This is the Wye strainer which prevents large debris in the water supply from entering the unit. The unit has sophisticated predictive diagnostics capability, and the life of critical components are shown on the 11 Life Screen .11 It provides guidance for when these parts should be changed. -
What is the life of the thermal battery and are there any safety or disposal issues to be aware of?
The Thermal Battery is estimated to last over 10 years under normal wear and tear. The battery is designed with high-grade stainless-steel components and factory-supplied food-grade propylene glycol. This food-grade glycol can be safely disposed of in a regular drain. The Thermal Battery can be sent to a typical metal recycling facility. Note: non-biodegradable glycol, especially ethylene glycol (e.g., automotive grade) or non-lntellihot supplied formulations, should never be used to charge the Thermal Battery. Doing so may cause irreparable damage and bodily harm, including death.
https://www.cdc.gov/legionella/wmp/overview/growth-and-spread.html
lntellihot1s Mission
We believe in empowering our customers with efficient, healthy, and
sustainable solutions that are great for them and the planet.
lntellihot, Inc. 11-877-835-1705 I lnfo@intellihot.com I www.intellihot.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>