SONOS EN54-23 Beacons and Sounder Beacons Instruction Manual

October 30, 2023
Sonos

SONOS EN54-23 Beacons and Sounder Beacons Instruction Manual
SONOS EN54-23 Beacons and Sounder Beacons

Fire Alarm Device: Beacon.
Type  A: For indoor use (Shallow Base)
Type B: For outdoor use (Deep Base)
Technical Datatsheet ATS00001

Head Type Coverage Volume CPR Number LPCB Number
ESBA3000R C-3-15 0832-CPR-F0007 717e/01
ESBA3000W C-3-15 0832-CPR-F0007 717e/02
ESBA4000R W-3.1-11.3 0832-CPR-F0009 717e/03
ESBA4000W W-3.1-11.3 0832-CPR-F0009 717e/04
Essential Characteristics EN54-23:2010 Subclause
--- ---
Duration of operation Pass
Provision for external conductors Pass
Flammability of materials Pass
Enclosure protection Pass
Access Pass
Manufacturers adjustments Pass
On-site adjustment behaviour Pass
Requirements for software controlled devices Pass
Coverage volume Pass
Variation of light output Pass
Minimum and maximum light intensity Pass
Light Colour White
Light temporal pattern and frequency of flashing Pass 0.5Hz/1Hz
Marking and data Pass
Synchronisation (Option with requirements) Pass
Durability Pass
Temperature Resistance Pass
Humidity resistance Pass
Shock and vibration resistance Pass
Corrosion resistance Pass
Electrical stability Pass

Shallow Base

Shallow Base
Shallow Base

Ensure the lens of the device is pointing to the floor

Wall

Wall

Deep Base

Deep Base
Deep Base

Ensure the lens of the device is pointing to the floor.

Ceiling

Ceiling

54-23 Coverage: C-3-15

Installation Manual

If required, the mechanism for locking the sounder to the base can be activated by removing the thin section of plastic shown in Fig. 1a with side cutters or a similar tool. To open a locked head, remove the small rubber bung from the hole on the side of the sounder, insert a tool into the hole and depress the clip whilst twisting the head. The O-ring and bung must be re- fitted to maintain the weatherproofing.

An alternative locking method is shown in Fig. 1b. Drive the hexagonal locking screw forward by turning a 1.5mm hexagonal key clockwise until the head is locked.

Wiring

Line Terminal Marking
Common Positive Supply IN (3) IN+
Beacon Negative Supply (1)

A separate earth terminal is provided on the deep base for connecting the screen or functional earth. On the shallow base, terminal 5 can be used for this purpose.

Flash rate

Switch 2 Flash rate: 0.5Hz =OFF/1Hz =ON (See Figure 2).
Flash rate

Technical Specification

Supply Voltage Range 17- 60Vdc
Switch on Surge @ 24Vdc <1.2mA

Current:
Alarm (Beacon) @ 24Vdc 0.5Hz| 20mA
Alarm (Beacon) @ 24Vdc 1Hz| 40mA
Beacon:
Flash RateLight Temporal Pattern| •  55ms ON, 945mS OFF; frequency flashing 1 second (1Hz)•  55ms ON, 1945mS OFF; frequency flashing 2 seconds (0.5Hz)
Flash Colour| White
Coverage (ceiling)| C-3-15 (530m3)
Coverage (wall)| W-3.1-11.3 (395.84m3)
Environmental:
Humidity| 5% to 95%
Temperature| -25°C to +70°C
Casing| High Impact Polycarbonate
IP Rating| Type A-IP21C (shallow base) Type B-IP33C (deep base) for EN54-3,EN54-23 installations with a cable gland (IP33C minimum)For other installations independently tested to IP65 (IP65 is not valid on EN54-3 and EN54-23 installations).
Synchronisation| Automatic

Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see: www.recyclethis.info.

Klaxon Signals is a registered trademark of Texecom Ltd. © 2014
St. Crispin Way, Haslingden, BB4 4PW
Tel: +44 1706 234800
Email: [email protected] www.klaxonsignals.com
Pulse Alert is a trademark of Texecom Ltd.

Klaxon logo

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals