- GENERAL DESCRIPTION
- INSTALLATION
- DEVICE PROGRAMMING
- DETECTOR PLACEMENT
- LED INDICATORS
- MAINTENANCE
- TECHNICAL SPECIFICATIONS
- WARRANTY
- Hyfire Wireless Fire Solutions Limited
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Hyfire HFI-TA-05 Altair Series Analogue Category P Thermal Detector
The HFI-TA-05 is a thermal detector designed for open area protection and provides the earliest warning of fire while offering a high level of false alarm rejection. It continuously samples the temperature variation in the protected area to detect fire.
The HFI-TA-05 is compatible with control panels that use the Altair analog- intelligent addressable communication protocol for monitoring and control, providing high rates of information exchange and fast and secure responses. Before installing the detector, it is recommended to read the leaflet thoroughly and refer to the applicable European Standards and National Codes of Practice for guidance on location, spacing, and acceptable use. Also, seek guidance from the compatible control panel instructions to ensure appropriate design criteria and configuration specifications are followed.
Product Installation
The HFI-TA-05 detector must be mounted only on the compatible adaptor bases listed in the TECHNICAL SPECIFICATIONS table. Refer to the specific base’s literature for further details.
Product Wiring
After installing the base to the ceiling, wiring has to be carried out in order to connect the base to the analog loop and, so, to the installation. Analog loop wires must be correctly connected to the base’s terminals. Check the performed wiring by referring to the figure 2 diagram.
Remote Output Capability
Remote output capability is available as a standard feature. A remote indication lamp or a compatible platform sounder may be wired to the base terminals. Check power requirements and loop drive limits before wiring. If other equipment is connected to the remote output, its supply current must be eventually limited by using an adequate resistor. Consult the TECHNICAL SPECIFICATIONS table and assess the external device current absorption’s value
Short Circuit Isolators
The detector is equipped with bi-directional short-circuit isolators to help protect against wiring faults that may otherwise result in loop failure. In the event of a short circuit, isolators either side should open to maintain most functions. Normal operation can be restored after the fault has been corrected.
Product Device Programming
Device Programming – Address Setting
Detectors can be addressed using a special hand-held programming unit or they can be automatically addressed from the control panel (if this feature exists for the model used) after they have been installed. Addresses may be selected from a range from 1 to 240, although each device on the loop must have a unique address.
Device Programming – Thermal Sensitivity Setting
A choice of two thermal sensitivity levels is available. These two levels correspond to a Rate Of Rise (ROR) A1R category (most sensitive) and to a category BS (least sensitive), according to the EN 54 part 5 European normative. Sensitivity level can be selected through a hand-held programming unit or, if such feature is provided, directly through the control panel.
GENERAL DESCRIPTION
This type of detector (figure 1) continuously samples the temperature variation in the protected area to provide the earliest warning of fire, offering, at the same time, a high level of false alarm rejection. These detectors are designed for an open area protection and must only be connected to control panels that use the Altair analog-intelligent addressable communication protocol for monitoring and control, providing high rates of information exchange and fast and secure responses.
Note: Before installing this device please thoroughly read this leaflet and refer to the applicable European Standards and National Codes of Practice (e.g. BS5839-1:2002 for UK) for guidance on location, spacing and acceptable use. Also seek guidance from the compatible control panel instructions to ensure appropriate design criteria and configuration specifications are followed.
INSTALLATION
For the installation to the ceiling, the detector must be mounted only on the compatible adaptor bases listed in the “TECHNICAL SPECIFICATIONS” table. Refer to the specific base’s literature for further details.
WIRING
After having installed the base to the ceiling, wiring has to be carried out in order to connect the base to the analogue loop and, so, to the installation. Analogue loop wires must be correctly connected to the base’s terminals: check the performed wiring by referring to the figure 2 diagram.
REMOTE OUTPUT CAPABILITY
Remote output capability is available as a standard feature, so a remote
indication lamp or a compatible platform sounder (check power requirements and
loop drive limits) may be wired to the base terminals (Figure 3).
If other equipment is connected to the remote output, its supply current must
be eventually limited by using an adequate resistor. Consult the TECHNICAL
SPECIFICATIONS table and assess the external device current absorption’s
value.
SHORT CIRCUIT ISOLATORS
The detector is equipped with bi-directional short-circuit isolators to help
protect against wiring faults that may otherwise result in loop failure. In
the event of a short circuit isolators either side should open to maintain
most functions.
Normal operation can be restored after the fault has been corrected.
DEVICE PROGRAMMING
DEVICE PROGRAMMING – ADDRESS SETTING
Detectors can be addressed using a special hand-held programming unit or they can be automatically addressed from the control panel (if this feature exists for the model used) after they have been installed. Addresses may be selected from a range from 1 to 240, although, of course, each device on the loop must have a unique address
DEVICE PROGRAMMING – THERMAL SENSITIVITY SETTING
A choice of two thermal sensitivity levels is available; these two levels correspond to a Rate Of Rise (ROR) A1R category (most sensitive) and to a category BS (least sensitive), according to the EN 54 part 5 European normative. Sensitivity level can be selected through a hand-held programming unit or, if such a feature is provided, directly through the control panel.
DETECTOR PLACEMENT
- Position the detector centrally on its adaptor base ensuring it is level.
- Rotate clockwise applying gentle pressure. The detector will drop into its keyed location.
- Continue to rotate clockwise a few degrees until the detector has fully engaged in the adaptor base.
- When the detector is firmly engaged, check the alignment of the raised reference marks on the detector and on the base (figure 5).
IMPORTANT NOTES ON DETECTORS PLACEMENT
- Disconnect loop power before installing the detector.
- Dust covers help to protect the devices during shipping and when first installed.
- They are not intended to provide complete protection against contamination, therefore, detectors should be removed before construction, major re-decoration or other dust producing work is started.
- Dust covers must be removed before the system can be made operational.
ANTI -TAMPER DETECTOR LOCK
- The detector can be locked to its base as a deterrent to intentional removal performed by nonauthorized personnel.
- Using a cutter, remove the anti-tamper plastic detail, as illustrated in figure 6.
- To unlock the detector, insert the tip of a screwdriver into the side slot of the base by exerting only a light pressure (figure 7), and release the detector by turning it anticlockwise.
LED INDICATORS
This detector is equipped with dual LEDs that can illuminate Green, Red or Amber to indicate status condition:
- Green: blinking, indicates the normal operative status of the detector.
- Red: indicates an alarmed condition of the detector.
- Amber: if implemented in panel software, indicates a fault condition of the detector.
- LED indicators are managed directly by the control panel and the green blinking can be disabled by the installer either from the control panel itself or through the programming unit. Positioning of these LEDs is illustrated in figure 8.
IDENTIFICATION TAB
- The adaptor base is equipped with a plastic tab where identification data can be visibly displayed.
- Detach the tab from the base; write or label it with the required information, then insert it into its adaptor base’s slot.
TESTING THE DETECTORS – PRELIMINARY NOTE
- Detectors should be tested after installation and during periodic maintenance visits; it is recommended each device should be tested at least once per year.
- After each test reset the system and allow at least one minute for power stabilisation.
MAGNET TEST
Position the test magnet next to the detector, in correspondence of the raised mark, then move it 45 degrees anticlockwise (figure 10). The magnet test simulates heat on the thermistor and verifies the function of all electronic circuits of the detector and its communication with the control panel. The detector should trigger an alarm message to the control panel, and, success sively, the detector’s red LED should be activated by the control panel itself.
HEAT TEST
- Use a hair dryer of 1000-1500 W or an heat tool from an approved manufacturer. Direct the heat towards the detector from its side. Hold the heat source at about 15 cm away from the detector in order to prevent damage to its cover during testing.
- The detector should trigger an alarm message to the control panel, and, successively, the detector’s red LED should be activated by the control panel itself.
MAINTENANCE
- Before starting any maintenance work, isolate and disable the system in order to avoid accidental and unwanted alarm or fault conditions.
- Remove the detector from its mounting base to allow inspection in good light at ground level.
- Inspect the thermistor area and use a small, soft bristle brush to dislodge any evident contaminants such as insects, spider webs, hairs, etc. Use a small vacuum tube or clean, dry and compressed air to suck up or blow away any remaining small particles from the thermistor area. Wipe the exterior housing of the detector with a clean, damp, lint-free cloth to remove any surface film that can later attract airborne contaminants.
- After all detectors have been inspected, repositioned on their mounting bases and power has been re-applied, check correct operation by testing the device.
TECHNICAL SPECIFICATIONS
Power supply ***** | from 18 V (min) to 40 V (max) |
---|---|
Average standby current consumption | 45 uA @ 24 V |
Remote output max current consumption (externally limited) | 20 mA |
Compatible adaptor bases | HFI-DMBS-05 – “Low Profile Adaptor Base” |
Thermal alarm threshold (ROR A1R category) | 58 °C |
Thermal alarm threshold (BS category) | 78 °C |
Operating temperature range | -30 °C / +70 °C (no icing) |
Humidity | 95% RH (no condensation) |
IP rating | 40 (42 with base’s waterproof protection) |
- Product operates down to 15 V, but without LED indication.
- Check latest version of document TDS-A3500 for further data, obtainable from your supplier.
WARNINGS AND LIMITATIONS
Our devices use high-quality electronic components and plastic materials that
are highly resistant to environmental deterioration. However, after 10 years
of continuous operation, it is advisable to replace the devices in order to
minimize the risk of reduced performance caused by external factors. Ensure
that this device is only used with compatible control panels. Detection
systems must be checked, serviced and maintained on a regular basis to confirm
correct operation.
Smoke detectors may respond differently to various kinds of smoke particles,
thus application advice should be sought for special risks. Detectors cannot
respond correctly if barriers exist between them and the fire location and may
be affected by special environmental conditions. Refer to and follow national
codes of practice and other internationally recognized fire engineering
standards. Appropriate risk assessment should be carried out initially to
determine the correct design criteria and updated periodically.
WARRANTY
All devices are supplied with the benefit of a limited 5 years warranty relating to faulty materials or manufacturing defects, effective from the production date indicated on each product. This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect handling or usage. Product must be returned via your authorized supplier for repair or replacement together with full information on any problem identified. Full details on our warranty and product’s returns policy can be obtained upon request.
Hyfire Wireless Fire Solutions Limited
- Unit B12a, Holly Farm Business Park, Honiley, Warwickshire, CV8 1NP – United Kingdom
- info@hyfirewireless.co.uk
- www.hyfirewireless.com
EN 54-5:2017+A1:2018
EN 54-17:2005
HFI-TA-05
For use in compatible fire detection and alarm system
Category A1R and BS (category P)