HFI-OM-240-01
Mains Line Switch Module
GENERAL DESCRIPTION
The HFI-OM-240-01 is a device that switches on or off third party ancillary devices that are installed on an household mains high voltage line; this device’s switch is controlled indirectly by the fire security system’s control panel.
The HFI-OM-240-01 can be used in a hard wired or in a wireless application context.
REQUIREMENTS AND COMPATIBILITY
The HFI-OM-240-01 must be used only in fire security systems based on the Argus Security’s wired and / or wireless protocol.
In a wired application the HFI-OM-240-01 requires a HFI-OM-RM-01 relay output mini-module.
In a wireless application, the HFI-OM-240-01 requires a SGMCB-EOLM interface module and a HFW-BOM-03 wireless battery powered output module.
IMPORTANT NOTES ON WIRING
Place a disconnector on the mains line; the disconnector must be placed outside the installation box, so as to be easily reachable. Disconnector’s contacts distance between each other must be of at least 3mm.
Overcurrent protective devices (fuses, circuit breakers…) must be installed outside the installation box.
Refer to and follow national codes of wiring and cabling practice and other internationally recognized standards.
Apply scrupulously the instructions given in this manual, especially the safety warning notes and the wiring procedures.
Disconnect the household mains line from its power supply source, from the beginning to the end of the installation / maintenance phases.
Make sure that the installation box, after installation / maintenance, remains sealed, preserving its original IP rating.
Mains line’s wires are intended to be connected only to their suitable
terminal blocks.
Connecting these wires to the wrong terminal blocks will damage irreparably
the HFI-OM-240-01 and be an hazard to final users.
Do not exceed maximum allowed loads on the household mains line.
Only competent and authorized personnel are allowed to access the installation box.
IMPORTANT NOTES ON INSTALLATION
HFI-OM-240-01 must always be installed into a suitable installation box.
You can choose between the UA-BBOE-WFR-01 wall box model, obtainable from your system supplier, or other suitable boxes purchasable on the market. In any case:
– use only external boxes with a UL94-5V flammability class and
– cable glands must have a flammability class UL94V-1 or better.
TECHNICAL SPECIFICATIONS
Analogue loop’s voltage range From 18 V (min) to 40 V
(max)
Activated current draw from analogue loop 12.5 mA at 24 V
Operating temperature range From -30 °C (min) to
+70 °C (max)
Humidity 95% RH
max (no condensation)
IP rating ( HFI-OM-240-01 only) 21C
IP rating ( UA-BBOE-WFR-01 installation box) 65
Supply shall be provided by Limited Power source (LPS)
MAINS LINE LOAD SPECIFICATIONS
Allowed load types Resistive / inductive
Maximum allowed load (RESISTIVE type)
5 A at 250 VAC
5 A at 30 VDC
Maximum allowed load (INDUCTIVE type) Power factor (cos Φ) = 0.4 L/R time
constant = 7 ms
1.5 A at 250 VAC
1.5 A at 30 VDC
INSTALLATION
1. Fix the installation box in the planned location. If a UA-BBOE-WFR-01
is used, fixing screws insertion locations are highlighted in picture 1.
2a. Wired application: Install the HFI-OM-RM-01 under the HFI-
OM-240-01 module; be sure that the connectors under the HFI-OM-240-01
enter properly into the HFI-OM-RM-01 female connectors (extractable
terminal blocks must be previously removed).
2b. Wireless application: install the SGMCB-EOLM under the HFI-
OM-240-01 module; be sure that the connectors under the HFI-OM-240-01
enter properly into the SGMCB-EOLM female connectors.
3a. If a UA-BBOE-WFR-01 is used, fix the HFI-OM-240-01 directly into
the box: use the 4 supplied fixing screws (picture 2).
3b. If not using a UA-BBOE-WFR-01 , fix the adaptor plate into the box;
fixing screws insertion locations of the plate are highlighted in picture 4.
Fix the HFI-OM-240-01 to the plate: use the 4 supplied fixing screws
(picture 5).
4. Fit the cable glands into the entries of the box. UA-BBOE-WFR-01 is
already equipped with knock-out holes for this purpose (picture 3).
5. Feed the cables into the box, giving them sufficient length for a secure
connection.
6. Fix the loop cables to their suitable terminal blocks on the HFI-
OM-240-01 ( check the following wiring paragraphs ).
7. Fix the mains line cables to their suitable terminal blocks on the HFI-
OM-240-01 ( check the following wiring paragraphs ).
8. After wiring is performed, close the box and seal it with the provided
screws.
9. Test the HFI-OM-240-01.
The UA-BBOE-WFR-01 wall box is designed with 12 cable entry knockout holes (6 M16/20 and 4 M25/32) distributed on its sides; these entries allow sealed, gland fitted cables to be introduced in the box itself.
ANALOGUE LOOP WIRING
- LOOP IN (+)
- LOOP OUT (+)
- LOOP IN (-)
- LOOP OUT (-)
HFW-BOM-03 WIRING
- HFW-BOM-03 24 VDC OUTPUT (+)
- HFW-BOM-03 24 VDC OUTPUT (-)
CHECK INTERFACE DEVICE’S DOCUMENTATION
It is warmly suggested to read the installation manuals for the HFI-OM- RM-01 , SGMCB-EOLM and HFW-BOM-03 interface modules to have a complete vital knowledge of installation know-how for these devices.
Hyfire Wireless Fire Solutions Limited – Unit B12a, Holly Farm Business Park, Honiley, Warwickshire, CV8 1NP – United Kingdom
HOUSEHOLD MAINS LINE WIRING
- COMMON (C)
- NORMALLY OPEN (NO)
- NORMALLY CLOSED (NC)
ALWAYS INSTALL THE SAFETY COVER
For safety reasons, the household mains line terminal blocks are equipped with a detachable cover; if not working on these terminal blocks for installation or maintenance reasons, ALWAYS KEEP THE SAFETY COVER INSTALLED IN ITS PLACE !!!
TESTING
Generate an alarm on the fire security system and check that the HFI-
OM-240-01 ‘s relay switches over from Normally Closed (NC) to Normally Open
(NO), thus handling the output as per fire security system design.
In an hard wired application the control panel activates the underlying HFI-
OM-RM-01 ‘s output LED indicator (if enabled by the control panel).
WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that are highly resistant to environmental deterioration. However, after 10 years of continuous operation, it is advisable to replace the devices in order to minimize the risk of reduced performance caused by external factors. Ensure that this device is only used with compatible control panels. Detection systems must be checked, serviced and maintained on a regular basis to confirm correct operation. Smoke sensors may respond differently to various kinds of smoke particles, thus application advice should be sought for special risks. Sensors cannot respond correctly if barriers exist between them and the fire location and may be affected by special environmental conditions. Refer to and follow national codes of practice and other internationally recognized fire engineering standards. Appropriate risk assessment should be carried out initially to determine correct design criteria and updated periodically.
WARRANTY
All devices are supplied with the benefit of a limited 5 years warranty relating to faulty materials or manufacturing defects, effective from the production date indicated on each product. This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect handling or usage. Product must be returned via your authorized supplier for repair or replacement together with full information on any problem identified. Full details on our warranty and product’s returns policy can be obtained upon request.
Hyfire Wireless Fire Solutions Limited – Unit B12a, Holly Farm Business Park,
Honiley, Warwickshire, CV8 1NP – United Kingdom
15
DoC-VM240
HFI-OM-240-01
For use in compatible fire detection and alarm systems
info@hyfirewireless.co.uk L20-VM240-14EN (vA.5)