Hyfire TAU-TH-01 Taurus Heat Detector User Guide

October 30, 2023
Hyfire

TAU-TH-01 Taurus Heat Detector

Product Information

TAU-TH-01 HYFIRE TAURUS HEAT DETECTOR
The TAU-TH-01 Hyfire Taurus Heat Detector is a wireless device designed to detect heat and provide early warning of a fire. The device comes with a base and a removable tag.

The package includes:

  • TAU-TH-01 Hyfire Taurus Heat Detector
  • Taurus QR code
  • Manual QR code
  • Product code
  • Product name

The device is also available in black plastic, identified by the product code TAU-TH-01-BL.
It is important to keep a minimum spacing of 2 meters between other wireless equipment in the area to avoid signal interference.

Product Usage Instructions

  1. Unlock the removable tag from the base of the detector.
  2. Remove the battery compartment cover on the base of the detector.
  3. Switch on the programming switch in the base of the detector to the ON position
  4. Remove the insulating tab from the batteries and ensure they are kept in their lodgement.
  5. The detector’s LED will signal 4 times red.
  6. Mount the detector by screwing it into the base and twisting clockwise to lock it in place.

Please refer to the complete product manual for more information.

THE BOX

Hyfire-TAU-TH-01-Taurus-Heat-Detector-FIG-1

INSIDE THE BOX

  • 1 x Heat Detector with mounting base
  • 2 x CR123A batteries
  • 1 x Quick start guide
  • 1 x QR code

IMPORTANT TO CONSIDER
When mounting a wireless device a comprehensive radio survey should have been carried out to establish the location that provides the best coverage and optimum reach. Taking into consideration the building structure and materials, the survey identifies the wireless infrastructure required and product locations for optimum performance, identifying any factor that could prevent radio integrity.
Avoid fixing or mounting the unit close to the following:

  • Equipment that utilises large electrical currents
  • Large metal objects or structures
  • Fluorescent lighting fittings
  • Metal ceiling structures
  • IT cabling.

Keep 2 meters minimum spacing between other wireless equipment in the area to avoid signal interference.
EN54 approved environmental temperature range is -10°C to +55°C

UNBOXING

  • When unboxing the detector you will find the unit and its mounting base.
  • This comes with pre-formed mounting holes to mount the detector base and a securing screw on the base to ensure there is no unwanted removal.

MOUNTING STEPS

Proceed as follows to complete the device installation.

  • Remove the detector’s dust cover, intended to protect the unit during shipping.
  • Remove the detector from the base twisting anticlockwise.
  • Locate the mounting holes and mark them using a pencil on the desired surface you are drilling.
  • Using a suitable-sized drill bit (6 mm) drill the marked screw points on your chosen surface.
  • Ensure you use the correct fixings for the type of surfaceyou are mounting to
  • A plastic pop out tag is removable from the base to enable you to label the address of the detector, prior to fixing to the ceiling: pop out the device label tag from the base and insert it into the side.
  • Screw the base to the ceiling using all fixing holes and appropriate-sized screws
  • Remove the battery compartment cover on the base on the detector.
  • Ensure the programming switch in the base of the detector is in position ON.
  • Remove the batteries’ insulating tab ensuring the batteries are kept in their lodgement.
  • The detector’s LED will signal 4 times red.
  • Move the switch in the base of the detector to position 1.
  • The detector’s LED will blink few seconds green and then signal alternatively green / red 4 times.
  • Ensure you replace the battery cover as this forms part of the detectors anti tamper protection and refit the detector locating it into the base twisting clockwise.
  • Secure the screw on the base to ensure there is no unwanted removal using a M3 allen key.
  • Put the QR code available in the box either on the system map or on the dedicated pages at the end of translator or expander manual.
  • ADDRESS: Unit B12a, Holly Farm Business Park, Honiley, Warwickshire, CV8 1NP
  • T: +44 (0)1926 485282,
  • E: info@hyfirewireless.co.uk,
  • W: www.hyfirewireless.com

Contact information:

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals