TRANE Technologies 4TWR5 Heat Pumps Installation Guide
- June 9, 2024
- Trane Technologies
Table of Contents
- Safety
- Unit Location Considerations
- Unit Preparation
- Setting the Unit
- Refrigerant Line Considerations
- Refrigerant Line Routing
- Refrigerant Line Brazing
- Refrigerant Line Leak Check
- Evacuation
- Service Valves
- Electrical – Low Voltage
- Electrical – High Voltage
- Start Up
- System Charge Adjustment
- Temperature Measurements
- Sub cooling Charging in Cooling (Above 55º F Outdoor Temp.)
- 1 1/2 Ton Heat Pump
- 2 Ton Heat Pump
- 3 Ton Heat Pump
- 4 Ton Heat Pump
- 5 Ton Heat Pump
- 1 1/2 Ton Heat Pump
- 2 1/2 Ton Heat Pump
- 3 1/2 Ton Heat Pump
- 2 Ton Heat Pump
- 3 Ton Heat Pump
- 4 Ton Heat Pump
- 5 Ton Heat Pump
- Subcooling Charging Below 55º F Outdoor Temp. (In Heating Only)
- Subcooling Charging Below 55º F Outdoor Temp. (In Heating Only)
- Checkout Procedures and Troubleshooting
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
TRANE Technologies 4TWR5 Heat Pumps
Safety
WARNING
This information is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and/or property damage. The manufacture or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.
WARNING
These units use R-410A refrigerant which operates at 50 to 70% higher pressures than R-22. Use only R-410A approved service equipment. Refrigerant cylinders are painted a “Rose” color to indicate the type of refrigerant and may contain a “dip” tube to allow for charging of liquid refrigerant into the system. All R 410A systems use a POE oil that readily absorbs moisture from the atmosphere. To limit this “hygroscopic” action, the system should remain sealed whenever possible. If a system has been open to the atmosphere for more than 4 hours, the compressor oil must be replaced. Never break a vacuum with air and always change the driers when opening the system for component replacement. For specific handling concerns with R-410A and POE oil reference Retrofit Bulletins SS-APG006-EN and APP-APG011-EN or APP-APG012-EN
WARNING
UNIT CONTAINS R-410A REFRIGERANT!
R-410A operating pressures exceed the limit of R-22. Proper service equipment
is required. Failure to use proper service tools may result in equipment
damage or personal injury.
SERVICE
USE ONLY R-410A REFRIGERANT AND APPROVED POE COMPRESSOR OIL.
WARNING
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclockwise until the valve stem just touches the rolled edge. No torque is required. Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and /or property damage.
WARNING
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and troubleshooting of this product,
it may be necessary to work with live electrical components. Failure to follow
all electrical safety precautions when exposed to live electrical components
could result in death or serious injury.
WARNING
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
WARNING
Scroll compressor dome temperatures may be hot. Do not touch the top of compressor; it may cause minor to severe burning.
Unit Location Considerations
Unit Dimensions and Weight
Table 2.1
Unit Dimensions and Weight
Models| H x D x W (in)| Weight* (lb)
4TWR5018N| 33 x 30 x 33| 174
4TWR5024N| 33 x 30 x 33| 174
4TWR5030N| 29 x 30 x 33| 163
4TWR5036N| 37 x 34 x 37| 199
4TWR5042N| 45 x 34 x 37| 227
4TWR5048N| 45 x 34 x 37| 250
4TWR5060N| 45 x 34 x 37| 251
4TWR5018H| 29 x 26 x 29| 141
---|---|---
4TWR5019H| 33 x 30 x 33| 174
4TWR5024H| 33 x 30 x 33| 174
4TWR5030H| 29 x 34 x 37| 216
4TWR5036H| 37 x 34 x 37| 199
4TWR5042H| 45 x 34 x 37| 227
4TWR5048H| 45 x 34 x 37| 250
4TWR5060H| 45 x 34 x 37| 278
- Weight values are estimated uncrated
When mounting the outdoor unit on a roof, be sure the roof will support the
unit’s weight.
Properly selected isolation is recommended to alleviate sound or vibration
transmission to the building structure.
Refrigerant Piping Limits
- The maximum TOTAL length of refrigerant lines from outdoor to indoor unit should NOT exceed 150 feet (including lift).
- The maximum vertical change should not exceed 50 feet.
- Service valve connection diameters are shown in Table 5.1.
Note: For other line lengths, Refer to Refrigerant Piping Application Guide, SS-APG006-EN or Refrigerant Piping Software Program, 32- 3312-03 (or latest revision).
Suggested Locations for Best Reliability
Ensure the top discharge area is unrestricted for at least five (5) feet above the unit.
Three (3) feet clearance must be provided in front of the control box (access panels) and any other side requiring service.
It is not recommended to install in a location where noise may distract the
building occupants. Some examples of these types of locations are sleeping
quarters and by windows of a living area. Please discuss location with the
building owner prior to installation.
Avoid locations such as near windows where condensation and freezing defrost vapor can annoy a customer.
Position the outdoor unit a minimum of 12” from any wall or surrounding shrubbery to ensure adequate airflow.
Outdoor unit location must be far enough away from any structure to prevent
excess roof runoff water or icicles from falling directly on the unit.
Cold Climate Considerations
NOTE: It is recommended that these precautions be taken for units being
installed in areas
where snow accumulation and prolonged below freezing temperatures occur
- Units should be elevated 3-12 inches above the pad or rooftop, depending on local weather. This additional height will allow drainage of snow and ice melted during defrost cycle prior to its refreezing. Ensure that drain holes in unit base pan are not obstructed preventing draining of defrost water.
- If possible, avoid locations that are likely to accumulate snow drifts. If not possible, a snow drift barrier should be installed around the unit to prevent a build-up of snow on the sides of the unit.
Coastal Considerations
If installed within one mile of salt water, including seacoasts and inland waterways, models without factory supplied Seacoast Salt Shields require the addition of BAYSEAC001 (Seacoast Kit) at installation time.
Unit Preparation
Prepare The Unit For Installation
STEP 1 – Check for damage and report promptly to the carrier any damage
found to the unit.
STEP 2 – To remove the unit from the pallet, remove tabs by cutting with
a sharp tool.
Setting the Unit
Pad Installation
When installing the unit on a support pad, such as a concrete slab, consider the following:
- The pad should be at least 1” larger than the unit on all sides.
- The pad must be separate from any structure.
- The pad must be level.
- The pad should be high enough above grade to allow for drainage.
- The pad location must comply with National, State, and Local codes.
Refrigerant Line Considerations
Refrigerant Line and Service Valve Connection Sizes
Table 5.1
| Line Sizes| Service Valve Connection Sizes
---|---|---
Model| Vapor Line| Liquid Line| Vapor Line Connection| Liquid Line Connection
4TWR5018N| 3/4| 3/8| 3/4| 3/8
4TWR5024N| 3/4| 3/8| 3/4| 3/8
4TWR5030N| 3/4| 3/8| 3/4| 3/8
4TWR5036N| 7/8| 3/8| 7/8| 3/8
4TWR5042N| 7/8| 3/8| 7/8| 3/8
4TWR5048N| 7/8| 3/8| 7/8| 3/8
4TWR5060N| 1-1/8| 3/8| 7/8| 3/8
4TWR5018H| 3/4| 3/8| 3/4| 3/8
---|---|---|---|---
4TWR5019H| 3/4| 3/8| 3/4| 3/8
4TWR5024H| 3/4| 3/8| 3/4| 3/8
4TWR5030H| 3/4| 3/8| 3/4| 3/8
4TWR5036H| 7/8| 3/8| 3/4| 3/8
4TWR5042H| 7/8| 3/8| 7/8| 3/8
4TWR5048H| 7/8| 3/8| 7/8| 3/8
4TWR5060H| 1-1/8| 3/8| 7/8| 3/8
Factory Charge
The outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit, ten (10) feet of tested connecting line, and the smallest rated indoor evaporative coil match. Always verify proper system charge via sub cooling (TXV/EEV) or superheat (fixed orifice) per the unit nameplate.
Required Refrigerant Line Length
Determine required line length and lift. You will need this later in STEP 2 of
Section 14.
Total Line Length = __ Ft.
Total Vertical Change (lift) = __ Ft.
Refrigerant Line Insulation
Important: The Vapor Line must always be insulated. DO NOT allow the Liquid Line and Vapor Line to come in direct (metal to metal) contact.
Reuse Existing Refrigerant Lines
**** CAUTION
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
For retrofit applications, where the existing indoor evaporator coil and/or refrigerant lines will be used, the following precautions should be taken:
- Ensure that the indoor evaporator coil and refrigerant lines are the correct size.
- Ensure that the refrigerant lines are free of leaks, acid, and oil.
Refrigerant Line Routing
Precautions
Important: Take precautions to prevent noise within the building structure due to vibration transmission from the refrigerant lines.
Comply with National, State, and Local Codes when isolating line sets from joists, rafters, walls, or other structural elements.
For Example:
- When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type hangers.
- Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
- Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
- Isolate the lines from all ductwork.
- Minimize the number of 90º turns.
Refrigerant Line Brazing
Braze The Refrigerant Lines
STEP 1 – Remove caps or plugs. Use a deburing tool to debur the pipe
ends. Clean both internal and external surfaces of the tubing using an emery
cloth.
STEP 2 – Remove the pressure tap cap and valve cores from both service
valves.
STEP 3 – Purge the refrigerant lines and indoor coil with dry nitrogen.
STEP 4 – Wrap a wet rag around the valve body to avoid heat damage and
continue the dry nitrogen purge.
Braze the refrigerant lines to the service valves.
For units shipped with a field-installed external drier, check liquid line filter drier’s directional flow arrow to confirm correct direction of refrigeration flow (away from outdoor unit and toward evaporator coil) as illustrated. Braze the filter drier to the Liquid Line.
Continue the dry nitrogen purge. Do not remove the wet rag until all brazing is completed.
Important: Remove the wet rag before stopping the dry nitrogen purge.
Note: Install drier in Liquid Line.
NOTE: Precautions should be taken to avoid heat damage to baseman during brazing. It is recommended to keep the flame directly off of the baseman.
STEP 5 – Replace the pressure tap valve cores after the service valves
have cooled.
Refrigerant Line Leak Check
Check For Leaks
STEP 1 – Pressurize the refrigerant lines and evaporator coil to 150 PSIG
using dry nitrogen.
STEP 2 – Check for leaks by using a soapy solution or bubbles at each
brazed location.
Remove nitrogren pressure and repair any leaks before continuing.
Evacuation
Evacuate the Refrigerant Lines and Indoor Coil
Important: Do not open the service valves until the refrigerant lines and indoor coil leak check and evacuation are complete.
STEP 1 – Evacuate until the micron gauge reads no higher than 350
microns, then close off the valve to the vacuum pump.
STEP 2 – Observe the micron gauge. Evacuation is complete if the micron gauge does not rise above 500 microns in one (1) minute.
Once evacuation is complete blank off the vacuum pump and micron gauge, and close the valves on the manifold gauge set.
Service Valves
Open the Gas Service Valve
Important: Leak check and evacuation must be completed before opening the service valves.
NOTE: Do not vent refrigerant gases into the atmosphere.
STEP 1 – Remove valve stem cap.
STEP 2 – Using an adjustable wrench, turn valve stem 1/4 turn
counterclockwise to the fully open position.
STEP 3 – Replace the valve stem cap to prevent leaks. Tighten finger
tight plus an additional 1/6 turn.
Open the Liquid Service Valve
WARNING
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclockwise until the valve stem just touches the rolled edge. No torque is required. Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and /or property damage.
Important: Leak check and evacuation must be completed before opening the service valves
STEP 1 – Remove service valve cap.
STEP 2 – Fully insert 3/16” hex wrench into the stem and back out
counterclockwise until valve stem just touches the rolled edge (approximately
five (5) turns.)
STEP 3 – Replace the valve cap to prevent leaks. Tighten finger tight
plus an additional 1/6 turn.
Electrical – Low Voltage
Low Voltage Maximum Wire Length
Table 11.1 defines the maximum total length of low voltage wiring from the outdoor unit, to the indoor unit, and to the thermostat.
Table 11.1
24 VOLTS
WIRE SIZE| MAX. WIRE LENGTH
18 AWG| 150 Ft.
16 AWG| 225 Ft.
14 AWG| 300 Ft.
Low Voltage Hook-up Diagrams
**With TEM 3, 4, 6, 8
**
With TAM 4, 5, 7, 9
- Units with pigtails require wirenuts for connections.
- In AC systems for multiple stages of electric heat, jumper W1 and W2 together if comfort control has only one stage of heat.
- Y2 for TEM6
2 Stage HP Thermosta
Defrost Control
Defrost controls have a selectable termination temperature. As shipped, defrost will terminate at 47°F. For a higher termination temperature, cut Jumper J2 to achieve 70°F. See Service Facts shipped in the outdoor unit for more information.
Pin Identification on J5 (See Illustration)
- TEST_COMMON (Shorting to FRC_DFT causes the control to initiate Forced Defrost. Leaving this pin open results in the normal mode of operation.)
- FRCDFT = Forced Defrost (Short TEST COMMON to this pin for two (2) seconds to initiate a forced defrost. Remove the short after defrost initiates.)
Defrost Control Checkout
Normal operation requires:
- Status LED on board flashing 1 time/second in standby or 2 times/second with a call for heating or cooling.
- 24V AC between R & B
- 24V AC between Y, Y0 & B with unit operating
- Defrost initiation when FRC_DFT pin is shorted to TEST_COMMON pin.
If a defrost control problem is suspected, refer to the service information in control box.
Electrical – High Voltage
High Voltage Power Supply
WARNING
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and troubleshooting of this product,
it may be necessary to work with live electrical components. Failure to follow
all electrical safety precautions when exposed to live electrical components
could result in death or serious injury.
The high voltage power supply must agree with the equipment nameplate.
Power wiring must comply with national, state, and local codes.
Follow instructions on unit wiring diagram located on the inside of the control box cover and in the Service Facts document included with the unit.
High Voltage Disconnect Switch
Install a separate disconnect switch at the outdoor unit.
For high voltage connections, flexible electrical conduit is recommended whenever vibration transmission may create a noise problem within the structure.
High Voltage Ground
Ground the outdoor unit per national, state, and local code requirements.
Start Up
System Start Up
STEP 1 – Ensure Sections 7 through 12 have been completed.
STEP 2 – Set System Thermostat to OFF.
STEP 3 – Turn on disconnect(s) to apply power to the indoor and outdoor
units.
STEP 4 – Wait one (1) hour before starting the unit if compressor
crankcase heater accessory is used and the Outdoor Ambient is below 70ºF.
STEP 5 – Set system thermostat to ON.
System Charge Adjustment
Temperature Measurements
STEP 1 – Check the outdoor temperatures. Sub cooling (in cooling mode) is the only recommended method of charging above 55º F ambient outdoor temperature. See Section 14.2.
See Section 14.2 for Outdoor Temperatures Above 55º F
For outdoor temperatures below 55º F, see Section 14.3.
Note: It is important to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient temperature is above 55º F.
See Section 14.3 for Outdoor Temperatures Below 55º F
For best results the indoor temperature should be kept between 70º F to 80º F.
Sub cooling Charging in Cooling (Above 55º F Outdoor Temp.)
STEP 1 – Use the refrigerant line total length and lift measurements from Section 5.3.
Total Line Length = __ Ft.
Vertical Change (Lift) = __ Ft.
STEP 2 – Determine the final subcooling value using total Line Length and Lift measured in STEP 1 and the charts below
For 018N – 060N Models:
1 1/2 Ton Heat Pump
2 Ton Heat Pump
3 Ton Heat Pump
4 Ton Heat Pump
5 Ton Heat Pump
Design Subcooling Value = __º F
(from nameplate or Service Facts)
Sub cooling Correction = __º F
Final Sub cooling Value = __º F
For 018H – 060H Models:
1 1/2 Ton Heat Pump
2 1/2 Ton Heat Pump
3 1/2 Ton Heat Pump
2 Ton Heat Pump
3 Ton Heat Pump
4 Ton Heat Pump
5 Ton Heat Pump
Design Subcooling Value = __º F
(from nameplate or Service Facts)
Subcooling Correction = __º F
Final Subcooling Value = __º F
STEP 3 – Stabilize the system by operating for a minimum of 20 minutes.
At startup, or whenever charge is removed or added, the system must be operated for a minimum of 20 minutes to stabilize before accurate measurements can be made.
STEP 4 – Measure the liquid line temperature and pressure at the outdoor unit’s service valve.
Measured Liquid Line Temp = __ º F
Liquid Gage Pressure = __ PSIG
Final Sub cooling Value = __ º F
STEP 5 – Use the final sub cooling value, refrigerant temperature and pressure from STEP 4, to determine the proper liquid gage pressure using Table 14.2.
Example: Assume a 12º F Final Sub cooling value and liquid temp of 90º F.
STEP 6 – Adjust refrigerant level to attain
proper gage pressure.
Add refrigerant if the Liquid Gage Pressure is lower than the chart value.
- Connect gages to refrigerant bottle and unit as illustrated.
- Purge all hoses.
- Open bottle.
- Stop adding refrigerant when liquid line temperature and Liquid Gage Pressure matches the charging chart Final Sub cooling value.
Recover refrigerant if the Liquid Gage Pressure is higher than the chart value.
STEP 7 – Stabilize the system.
- Wait 20 minutes for the system condition to stabilize between adjustments. Note: When the Liquid Line Temperature and Gage Pressure approximately match the chart, the system is properly charged.
- Remove gages.
- Replace service port caps to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
STEP 8 – Verify typical performance.
Refer to System Pressure Curves in the Service Facts to verify typical
performance.
STEP 9 – Record System Information for reference. Record system pressures
and temperatures after charging is complete.
Outdoor model number = _____
Measured Outdoor Ambient = __ º F
Measured Indoor Ambient = __ º F
Measured Liquid Line Temp = __ º F
Measured Suction Line Temp = __ º F
Liquid Gage Pressure = __ PSIG
Suction Gage Pressure = __ PSIG
Subcooling Charging Below 55º F Outdoor Temp. (In Heating Only)
The Subcooling Charging method in cooling is not recommended below 55º F outdoor temperature. The only recommended method of charging at outdoor temperatures below 55º F is weighing in the charge in heating mode.
STEP 1 – Determine additional charge. Note: The nameplate charge value
represents the amount of refrigerant shipped in the outdoor unit and is
compatible with 10 feet of AHRI rated refrigerant lines and the smallest AHRI
ratedcoil.
Using the method below, find the charge associated with the additional length
of tubing above 10 ft. and record it below.
Subcooling Charging Below 55º F Outdoor Temp. (In Heating Only)
Measured Suction Line Temp = __ º F
Liquid Gage Pressure = __ PSIG
Suction Gage Pressure = __ PSIG
Calculating Charge Using the Weigh-In Method
STEP 1 – Measure in feet the distance between the outdoor unit and the
indoor unit. (Include the entire length of the line from the service valve to
the IDU.) Subtract 10 ft from this entire length and record on line 1.
STEP 2 – Enter the charge multiplier (0.6 oz/ft). Each linear foot of
interconnecting tubing requires the addition of 0.6 oz of refrigerant.
STEP 3 – Multiply the total length of refrigerant tubing (Line 1) times
the value on Step 2. Record the result on Line 3 of the Worksheet.
STEP 4 – This is the amount of refrigerant to weighin prior to opening
the service valves
Weigh-In Method can be used for the initial installation, or anytime a system charge is being replaced. Weigh-In Method can also be used when power is not available to the equipment site or operating conditions (indoor/outdoor temperatures) are not in range to verify with the subcooling charging method
- Total Line length (ft) – 10 ft __
- Charge multiplier x _0.6 oz___
- Step 1 x Step 2 = _____
- Refrigerant (oz) = _____
STEP 2 – Stabilize the system by operating for a minimum of 20 minutes.
At startup, or whenever charge is removed or added, the system must be
operated for a minimum of 20 minutes to stabilize before accurate measurements
can be made.
STEP 3 – Check the liquid line temperature and liquid gage pressure to obtain
a minimum of 10º subcooling in heating mode.
Measured Liquid Line Temp = __ º F
Liquid Gage Pressure = __ PSIG
STEP 4 – Add charge if a minimum of 10º subcooling is not obtained with the namplate charge plus additional charge previously added.
STEP 5 – Return to site for adjustment.
Important: Return in the spring or summer to accurately charge the system in the cooling mode with outdoor ambient above 55º F.
Checkout Procedures and Troubleshooting
Operational And Checkout Procedures
Final phases of this installation are the unit Operational and Checkout
Procedures. To obtain proper performance, all units must be operated and
charge adjustments made.
Important: Perform a final unit inspection to be sure that factory tubing
has not shifted during shipment. Adjust tubing if necessary so tubes do not
rub against each other when the unit runs. Also be sure that wiring
connections are tight and properly secured
CHECKOUT PROCEDURE
After installation has been completed, it is recommended that the entire system be checked against the following list:
-
Leak check refrigerant lines. ..[ ]
-
Properly insulate suction lines and fittings.. [ ]
-
Properly secure and isolate all refrigerant lines…[ ]
-
Seal passages through masonry. If mortar is used, prevent mortar from coming
into direct contact with copper tubing…. [ ] -
Verify that all electrical connections are tight… [ ]
-
Observe outdoor fan during on cycle for clearance and smooth operation…. [ ]
Troubleshooting
Trane – by Trane Technologies (NYSE: TT), a global climate innovator – creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.
The AHRI Certified mark indicates Trane U.S. Inc. participation in the AHRI
Certification program. For verification of individual certified products, go
to ahridirectory.org.
Trane has a policy of continuous data improvement and it reserves the right to
change design and specifications without notice. We are committed to using
environmentally conscious print practices.
18-BC76D1-11E-EN 29 Jul 2022 Supersedes 18-BC76D1-11D-EN (July 2022)
References
- DWG.no - DWG Cad Software | DWG View | DWG til PDF | Norsk nettside som går gjennom nyheter og muligheter innen 2D og 3D design
- Trane Heating & Air Conditioning
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>